| 2012-03-01 17:15:23 | NEW SFR (R3) BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO THE |
| | PALM BEACH COUNTY BUILDING (2300 N. JOG RD) TO VERIFY |
| | IF IMPACT FEES ARE DUE. THEN, BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- WINDOWS ON SECOND FLOOR BEDROOM #3 DON'T COMPLY WITH |
| | THE EGRESS REQUIREMENTS OF SEC. R310. NEED OPENING WITH |
| | MIN. CLEAR HEIGHT OF 24" AND TOTAL CLEAR OPENING CAN'T |
| | BE LESS THAN 5.7 S.F. REVISE AS REQUIRED. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 613.13 |
| | FLORIDA STATUTE. ***NOTE: THIS MAY BE PROVIDED AT TIME |
| | OF PERMIT PICK UP. |
| | |
| | 4- THIS HOUSE IS LOCATED ON FLOOD ZONE A5. AND THE BASE |
| | FLOOD EELEVATION IS 7'. PLEASE PROVIDE DOCUMENTATION |
| | SHOWING THE PROPOSED FINISH FLOOR ELEVATION FOR THE |
| | MAIN HOUSE AND GARAGE. SEC. 94-546(B)(1) REQUIRES |
| | FINISH FLOOR ELEVATION TO BE AT LEAST 6" ABOVE BASE |
| | FLOOD ELEVATION. IF GARAGE FLOOR IS LESS THAN 7'-6" |
| | THEN, THE WALLS NEED TO BE FLOODPROOFED DESIGNED. |
| | |
| | 5- PLEASE PROVIDE ON PLANS TITLE BLOCK THE FIRM LICENSE |
| | NUMBER FOR "ARCHITECTURAL STUDIO, INC" AS REQUIRED BY |
| | SEC. 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE AND |
| | CHAPTER 481 FLORIDA STATUTE. |
| | |
| | 6- LOAD SCHEDULE INFORMATION ON SHEET G-1: |
| | A) REVISE ROOF TRUSSES ATTIC LIVE LOAD (BOTTOM CHORD OF |
| | TRUSS). ATTIC IN THIS HOUSE QUALIFIES FOR ATTIC WITH |
| | LIMITED STORAGE AS REQUIRED BY FOOTNOTES ON TABLE |
| | R301.5. IN ADDITION, AREA WHERE THE AIR HANDLER UNIT IS |
| | LOCATED NEEDS TO BE CONSIDERED. |
| | ALSO, TOTAL BOTTOM CHORD LOAD NEEDS TO BE REVISED. |
| | ACTUAL NUMBER SHOWN IS INCORRECT. NOW IT NEEDS TO BE |
| | COORDINATED WITH REVISED LOADING. |
| | |
| | B) SPECIFY THE BALCONY LOADS AS REQUIRED BY TABLE |
| | R301.5. |
| | |
| | 7- SPECIFY SIZE AND LOCATION OF ATTIC ACCESS ON SECOND |
| | FLOOR ROOF. SEC. R807.1. |
| | |
| | 8- PROVIDE DETAILS/SPECIFICATIONS SHOWING STAIR WINDERS |
| | COMPLIANCE WITH SEC. R311.5.3.2. SPECIFY DIMENSIONS ON |
| | NARROWER END. |
| | |
| | 9- A) PROVIDE SPECS FOR GARAGE DOOR LEADING TO THE |
| | HOUSE TO SHOW COMPLIANCE WITH OPENING PROTECTION SEC. |
| | R309. |
| | |
| | B) SPECIFY CEILING CONSTRUCTION ABOVE GARAGE TO SHOW |
| | COMPLIANCE WITH SEC. R309.2. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) FRONT DOOR. FLORIDA PRODUCT APPROVAL FL6234 |
| | SUBMITTED IS FOR 2004 CODE. NEED 2007 CODE. |
| | |
| | B) GARAGE DOOR. FLORIDA PRODUCT APPROVAL FL5675 |
| | SUBMITTED IS FOR 2004 CODE. NEED 2007 CODE. AND, NEED |
| | PRODUCT APPROVAL THAT MEETS THE DESIGN PRESSURES |
| | CALCULATED BY THE ARCHITECT ON SHEET A-2. |
| | |
| | C) COLONIAL SHUTTERS SHOWN ON THE EXTERIOR ELEVATIONS. |
| | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. SPECIFY |
| | ANCHOR TYPE AND SPACING TO BE USED TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | D) GARAGE OUTSIDE SWING DOOR. |
| | |
| | E) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 12- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE |
| | BOTTOM OF FORM. |
| | |
| | 13- PROVIDE BALCONY GUARDRAIL COMPLETE DETAILS AND |
| | SPECIFICATIONS TO SHOW COMPLIANCE WITH THE DESIGN LOADS |
| | OF TABLE R301.5 AND SEC. R312. |
| | |
| | 14- PROVIDE COMPLETE DETAIL/S SPECIFICATIONS FOR |
| | BALCONY FLOOR ASSEMBLY. SHOW WATERPROOFING AND FINISH |
| | MATERIAL TO SHOW COMPLIANCE WITH THE WIND LOADS OF SEC. |
| | R301.2.1.4.3. PROVIDE PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9N-3. |
| | |
| | 15- SOIL TEST REPORT PAGE 5 OF 8 RECOMMENDS FOOTINGS TO |
| | BE EMBEDDED AT LEAST 18" BELOW LOWEST ADJACENT GRADE. |
| | SIZE OF FOOTINGS SPECIFIED ON THE FOUNDATION PLAN DON'T |
| | PROVIDE THIS MINIMUM EMBEDMENT. ENGINEER OF RECORD TO |
| | REVIEW SOIL TEST REPORT FINDINGS AND ACKNOWLEDGE IN |
| | DRAWINGS IF BASED ON THE SOIL TEST REVIEW THE FOOTINGS |
| | NEED TO BE REVISED OR NOT. |
| | |
| | 16- DRAINAGE PLAN NEED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |