Plan Review Details - Permit 12020390
Plan Review Stops For Permit 12020390
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2014-01-27 Cont ID  
Sent By shill Date 2014-01-27 Time 12:02 Rev Time 0.00
Received By shill Date 2014-01-27 Time 12:02 Sent To  
Notes
2014-01-27 12:03:04FINAL ELEVATION CERTIFICATE OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-01-16 Cont ID  
Sent By shill Date 2014-01-16 Time 15:45 Rev Time 0.00
Received By shill Date 2014-01-16 Time 15:45 Sent To  
Notes
2014-01-16 16:19:35****CORRECTIONS****
 ELEVATION CERTIFICATE REVIEW
 ELEVATION CERTIFICATE PREPARED BY MICHAEL J MILLER
 DATED 11/18/2013
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. ITEM B1, NFIP COMMUNITY NAME & COMMUNITY NUMBER
 REQUIRED, SHOULD BE "CITY OF WEST PALM BEACH, 120229"
  
 2. B6, FIRM DATE SHOULD BE MARCH 1, 1979.
  
 3. B7, FIRM PANEL EFFECTIVE/REVISED DATE SHOULD BE
 MARCH 1, 1979.
  
 4. FLORIDA STATUTE 472.025 SEALS STATES "EACH
 REGISTRANT SHALL OBTAIN AN IMPRESSION-TYPE METAL SEAL
 IN THAT FORM; AND ALL FINAL DRAWINGS, PLANS,
 SPECIFICATIONS, PLATS, OR REPORTS PREPARED OR ISSUED BY
 THE REGISTRANT IN ACCORDANCE WITH MINIMUM TECHNICAL
 STANDARDS SET BY THE BOARD SHALL BE SIGNED BY THE
 REGISTRANT, DATED, AND STAMPED WITH HIS OR HER SEAL.
 THIS SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE
 AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED."
  
 INK SEAL AND PHOTOCOPY SIGNATURE NOT ACCEPTABLE PER
 FLORIDA STATUTE.
  
 5. SECTION D, PAGE 2, APPEARS THAT THE SURVEYOR SIGNED
 SOMETHING WHICH WAS TAPED TO THE ELEVATION CERTIFICATE
 AND COPIED. SEE FLORIDA STATUTE REFERENCED IN ITEM 4.
 PLEASE PROVIDE AN ORIGINAL SIGNATURE.
  
 6. SECTION D, COMMENTS SECTION SHOULD ALWAYS INCLUDE
 INFORMATION ABOUT THE EQUIPMENT SERVICING THE BUILDING
 AND THE SOURCE OF THE LATITUDE / LONGITUDE, SEE
 INSTRUCTIONS.
  
 7. C2B, NEXT HIGHER FLOOR STATES N/A, BUT THIS IS A TWO
 STORY HOUSE. PLEASE REVISE.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-01-10 Cont ID  
Sent By rmcdouga Date 2014-01-10 Time 18:07 Rev Time 0.00
Received By rmcdouga Date 2014-01-10 Time 18:07 Sent To  
Notes
2014-01-10 18:08:31REVIEWED BALCONY RAILING SHOP DRAWINGS FOR CODE
 COMPLIANCE. ADDRESSES PROVISO REQUIREMENTS FOR THE
 BALCONY HANDRAILS ONLY. NO SEPARATE PERMIT IS REQUIRED,
 NO FEE PER ROBERT BROWN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-04-11 Cont ID  
Sent By jgomez Date 2012-04-11 Time 16:00 Rev Time 0.00
Received By jgomez Date 2012-04-11 Time 15:59 Sent To  
Notes
2012-04-11 16:02:59BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- JAMES BROOKS SAID HE WILL PROVIDE ALL THE STRUCTURAL
 INFORMATION FOR THE BALCONY GUARDRAIL UNDER A SEPARATE
 PERMIT. INFORMATION TO BE APPROVED BY THE ARCHITECT
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 1- ARCHITECT TO PROVIDE COMPLETE INFORMATION FOR
 BALCONY FLOOR ASSEMBLY ONCE OWNER DECIDES MATERIALS TO
 BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-04-02 Cont ID  
Sent By jgomez Date 2012-03-30 Time 11:21 Rev Time 0.00
Received By jgomez Date 2012-03-30 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-01 Cont ID  
Sent By jgomez Date 2012-03-01 Time 17:08 Rev Time 0.00
Received By jgomez Date 2012-03-01 Time 08:14 Sent To  
Notes
2012-03-01 17:15:23NEW SFR (R3) BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO THE
 PALM BEACH COUNTY BUILDING (2300 N. JOG RD) TO VERIFY
 IF IMPACT FEES ARE DUE. THEN, BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 2- WINDOWS ON SECOND FLOOR BEDROOM #3 DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310. NEED OPENING WITH
 MIN. CLEAR HEIGHT OF 24" AND TOTAL CLEAR OPENING CAN'T
 BE LESS THAN 5.7 S.F. REVISE AS REQUIRED.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 613.13
 FLORIDA STATUTE. ***NOTE: THIS MAY BE PROVIDED AT TIME
 OF PERMIT PICK UP.
  
 4- THIS HOUSE IS LOCATED ON FLOOD ZONE A5. AND THE BASE
 FLOOD EELEVATION IS 7'. PLEASE PROVIDE DOCUMENTATION
 SHOWING THE PROPOSED FINISH FLOOR ELEVATION FOR THE
 MAIN HOUSE AND GARAGE. SEC. 94-546(B)(1) REQUIRES
 FINISH FLOOR ELEVATION TO BE AT LEAST 6" ABOVE BASE
 FLOOD ELEVATION. IF GARAGE FLOOR IS LESS THAN 7'-6"
 THEN, THE WALLS NEED TO BE FLOODPROOFED DESIGNED.
  
 5- PLEASE PROVIDE ON PLANS TITLE BLOCK THE FIRM LICENSE
 NUMBER FOR "ARCHITECTURAL STUDIO, INC" AS REQUIRED BY
 SEC. 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 481 FLORIDA STATUTE.
  
 6- LOAD SCHEDULE INFORMATION ON SHEET G-1:
 A) REVISE ROOF TRUSSES ATTIC LIVE LOAD (BOTTOM CHORD OF
 TRUSS). ATTIC IN THIS HOUSE QUALIFIES FOR ATTIC WITH
 LIMITED STORAGE AS REQUIRED BY FOOTNOTES ON TABLE
 R301.5. IN ADDITION, AREA WHERE THE AIR HANDLER UNIT IS
 LOCATED NEEDS TO BE CONSIDERED.
 ALSO, TOTAL BOTTOM CHORD LOAD NEEDS TO BE REVISED.
 ACTUAL NUMBER SHOWN IS INCORRECT. NOW IT NEEDS TO BE
 COORDINATED WITH REVISED LOADING.
  
 B) SPECIFY THE BALCONY LOADS AS REQUIRED BY TABLE
 R301.5.
  
 7- SPECIFY SIZE AND LOCATION OF ATTIC ACCESS ON SECOND
 FLOOR ROOF. SEC. R807.1.
  
 8- PROVIDE DETAILS/SPECIFICATIONS SHOWING STAIR WINDERS
 COMPLIANCE WITH SEC. R311.5.3.2. SPECIFY DIMENSIONS ON
 NARROWER END.
  
 9- A) PROVIDE SPECS FOR GARAGE DOOR LEADING TO THE
 HOUSE TO SHOW COMPLIANCE WITH OPENING PROTECTION SEC.
 R309.
  
 B) SPECIFY CEILING CONSTRUCTION ABOVE GARAGE TO SHOW
 COMPLIANCE WITH SEC. R309.2.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FRONT DOOR. FLORIDA PRODUCT APPROVAL FL6234
 SUBMITTED IS FOR 2004 CODE. NEED 2007 CODE.
  
 B) GARAGE DOOR. FLORIDA PRODUCT APPROVAL FL5675
 SUBMITTED IS FOR 2004 CODE. NEED 2007 CODE. AND, NEED
 PRODUCT APPROVAL THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT ON SHEET A-2.
  
 C) COLONIAL SHUTTERS SHOWN ON THE EXTERIOR ELEVATIONS.
 AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. SPECIFY
 ANCHOR TYPE AND SPACING TO BE USED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.2.1.4.3.
  
 D) GARAGE OUTSIDE SWING DOOR.
  
 E) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 12- ENERGY CALCULATIONS: OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM.
  
 13- PROVIDE BALCONY GUARDRAIL COMPLETE DETAILS AND
 SPECIFICATIONS TO SHOW COMPLIANCE WITH THE DESIGN LOADS
 OF TABLE R301.5 AND SEC. R312.
  
 14- PROVIDE COMPLETE DETAIL/S SPECIFICATIONS FOR
 BALCONY FLOOR ASSEMBLY. SHOW WATERPROOFING AND FINISH
 MATERIAL TO SHOW COMPLIANCE WITH THE WIND LOADS OF SEC.
 R301.2.1.4.3. PROVIDE PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9N-3.
  
 15- SOIL TEST REPORT PAGE 5 OF 8 RECOMMENDS FOOTINGS TO
 BE EMBEDDED AT LEAST 18" BELOW LOWEST ADJACENT GRADE.
 SIZE OF FOOTINGS SPECIFIED ON THE FOUNDATION PLAN DON'T
 PROVIDE THIS MINIMUM EMBEDMENT. ENGINEER OF RECORD TO
 REVIEW SOIL TEST REPORT FINDINGS AND ACKNOWLEDGE IN
 DRAWINGS IF BASED ON THE SOIL TEST REVIEW THE FOOTINGS
 NEED TO BE REVISED OR NOT.
  
 16- DRAINAGE PLAN NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-16 Cont ID  
Sent By rlecky Date 2012-03-16 Time 08:34 Rev Time 0.00
Received By rlecky Date 2012-03-16 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-01 Cont ID  
Sent By rlecky Date 2012-03-01 Time 11:04 Rev Time 0.00
Received By rlecky Date 2012-02-28 Time 16:39 Sent To  
Notes
2012-02-29 09:55:2012020390
 124 COSTELLO ROAD
 NEW SFD
  
 MINIMUM 1/0 FEEDERS REQUIRED FOR 150 AMPERE SUB PANEL.
 NEC T. 310.16
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE I.E. FOYER, GUEST
 SUITE, BEDROOM 3. NEC 210.52
 A GFCI PROTECTED RECEPTACLE IS REQUIRED ON THE BALCONY.
 NEC 210.52
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
  
 ROBERT LECKY
 ELECTRIC PLAN REVIEWER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-18 Cont ID  
Sent By jgomez Date 2012-04-18 Time 08:37 Rev Time 0.00
Received By jgomez Date 2012-04-10 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-02 Cont ID  
Sent By jgomez Date 2012-04-02 Time 15:32 Rev Time 0.00
Received By jgomez Date 2012-03-14 Time 16:21 Sent To  
Notes
2012-03-14 16:21:31SENT TO R1 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-08 Cont ID  
Sent By lmartine Date 2012-03-08 Time 16:49 Rev Time 0.00
Received By lmartine Date 2012-02-16 Time 11:11 Sent To  
Notes
2012-02-22 11:12:27SENT TO R26 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-04-18 Cont ID  
Sent By jgomez Date 2012-04-18 Time 08:36 Rev Time 0.00
Received By jgomez Date 2012-04-13 Time 10:23 Sent To  
Notes
2012-04-18 08:37:05JAMES BROOKS SUBMITTED IMPACT FEES RECEIPT AND STAMPED
 PLANS. JG.
2012-04-13 10:23:43JAMES BROOKS TOOK ONE SET OF PLANS TODAY TO PAY THE
 IMPACT FEES. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-04-02 Cont ID  
Sent By jgomez Date 2012-04-02 Time 15:32 Rev Time 0.00
Received By jgomez Date 2012-04-02 Time 15:32 Sent To  
Notes
2012-04-02 15:32:45NEED IMPACT FEES STAMP AND PAID RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-03-02 Cont ID  
Sent By jgomez Date 2012-03-02 Time 14:32 Rev Time 0.00
Received By jgomez Date 2012-03-02 Time 14:32 Sent To  
Notes
2012-03-02 14:33:25PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY
 BUILDING (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-03-28 Cont ID  
Sent By rmcdouga Date 2012-03-28 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2012-03-27 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-06 Cont ID  
Sent By rmcdouga Date 2012-03-06 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2012-03-06 Time 14:27 Sent To  
Notes
2012-03-06 14:42:532007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SHOW COMPLIANCE WITH FBC M1602.4 FOR BALANCED RETURN
 AIR. THE TRANSFER DUCTS ARE REQUIRED TO BE 1.5 TIMES
 THE SUPPLY ENTERING THE ROOM AND UNDERCUTTING THE DOORS
 1 INCH. THE FIRST FLOOR GUEST SUITE AND SECOND FLOOR
 BEDROOMS # 2 & # 3 DO NOT COMPLY.
  
 2) SPECIFY THE SIZE OF THE TRANSFER GRILL FOR THE
 MASTER BEDROOM SUITE. FBC M1602.4(2) REQUIRES TRANSFER
 GRILLS TO USE 50 SQUARE INCHES OF GRILL AREA TO 100 CFM
 OF SUPPLY AIR FOR SIZING THROUGH THE WALL TRANSFER
 GRILLS AND UNDER CUTTING THE DOORS 1 INCH.
  
 3) REMOVE THE ARCHITECTS NAME FROM SHEET M1, UNLESS HE
 IS SIGNING AND SEALING THE DRAWINGS. FS 481
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By rmcdouga Date 2012-03-27 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2012-03-27 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-03-06 Cont ID  
Sent By rmcdouga Date 2012-03-06 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2012-03-06 Time 11:15 Sent To  
Notes
2012-03-06 11:38:182007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE MASTER BATH FIXTURES ARE NOT PROPERLY VENTED.
 FBC P3108.2 IN HORIZONTAL WET- VENT SYSTEMS, NOT MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
 PLEASE REVISE DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2012-04-17 Cont ID  
Sent By eschneid Date 2012-04-17 Time 16:38 Rev Time 0.50
Received By eschneid Date 2012-04-17 Time 16:11 Sent To  
Notes
2012-04-17 16:38:55CONDITIONAL PERMIT - REQUIRES LANDSCAPE AND IRRIGATION
 PRIOR TO C.O.

Review Stop Z ZONING
Rev No 2 Status F Date 2012-03-26 Cont ID  
Sent By eschneid Date 2012-03-26 Time 09:42 Rev Time 0.25
Received By eschneid Date 2012-03-22 Time 10:39 Sent To  
Notes
2012-03-26 09:42:06FAILED
  
 1) REPEAT COMMENT - A LANDSCAPE PERMIT IS REQUIRED TO
 BE SUBMITTED PRIOR TO ZONING APPROVAL OF THIS PERMIT.
  
 2) SEPARATE PERMITS REQUIRED FOR THE DRIVEWAY, POOL AND
 DECK.
  
 3) REPEAT COMMENT - THE LOWER ROOF OVERHANG ON THE EAST
 SIDE OF THE BUILDING EXTENDS FOUR (4) FEET FROM THE
 EASTERN WALL. SHEET AS-1 ESTABLISHES THE EAST SIDE AS
 BEING THE TEN (10) FOOT SETBACK SIDE, WITH THE WEST
 SIDE AS BEING THE FIVE (5) FOOT SETBACK SIDE. THIS
 SETBACK ASSIGNMENT RESULTS IN THE ROOF OVERHANG
 EXTENDING GREATER THAN THE PERMITTED THREE (3) FEET
 INTO THE SETBACK. IN ORDER TO KEEP THE FEATURE AS
 SHOWN, THE SETBACKS SHALL BE AMENDED ON SHEET AS-1 AS
 FOLLOWS: EASTERN SIDE SETBACK - EIGHT (8) FEET AND THE
 WESTERN SETBACK - SEVEN (7) FEET OR THE HOUSE WILL NEED
 TO BE SHIFTED ONE FOOT TO THE EAST AND BE 11 FEET OFF
 THE EAST PROPERTY LINE.
  
 PLEASE CONTACT ERIC SCHNEIDER @ ( 561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-08 Cont ID  
Sent By eschnied Date 2012-03-08 Time 11:56 Rev Time 1.00
Received By eschneid Date 2012-03-07 Time 16:41 Sent To  
Notes
2012-03-08 11:57:24FAILED
  
 1) A LANDSCAPE PERMIT IS REQUIRED TO BE SUBMITTED PRIOR
 TO ZONING APPROVAL OF THIS PERMIT.
  
 2) SEPARATE PERMITS REQUIRED FOR THE DRIVEWAY, POOL AND
 DECK.
  
 3) THE LOWER ROOF OVERHANG ON THE EAST SIDE OF THE
 BUILDING EXTENDS FOUR (4) FEET FROM THE EASTERN WALL.
 SHEET AS-1 ESTABLISHES THE EAST SIDE AS BEING THE TEN
 (10) FOOT SETBACK SIDE, WITH THE WEST SIDE AS BEING THE
 FIVE (5) FOOT SETBACK SIDE. THIS SETBACK ASSIGNMENT
 RESULTS IN THE ROOF OVERHANG EXTENDING GREATER THAN THE
 PERMITTED THREE (3) FEET INTO THE SETBACK. IN ORDER TO
 KEEP THE FEATURE AS SHOWN, THE SETBACKS SHALL BE
 AMENDED ON SHEET AS-1 AS FOLLOWS: EASTERN SIDE SETBACK
 - EIGHT (8) FEET AND THE WESTERN SETBACK - SEVEN (7)
 FEET OR THE HOUSE WILL NEED TO BE SHIFTED ONE FOOT TO
 THE EAST AND BE 11 FEET OFF THE EAST PROPERTY LINE.
  
 PLEASE CONTACT ERIC SCHNEIDER @ ( 561) 822-1446.
  