Plan Review Details - Permit 12020362
Plan Review Stops For Permit 12020362
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-06-29 Cont ID  
Sent By shill Date 2012-06-29 Time 15:30 Rev Time 0.00
Received By shill Date 2012-06-29 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-06-28 Cont ID  
Sent By shill Date 2012-06-28 Time 17:15 Rev Time 0.00
Received By shill Date 2012-06-28 Time 17:15 Sent To  
Notes
2012-06-28 17:16:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 DOOR NOA SENT VIA EMAIL
  
 1. A 60 MINUTE DOOR IS REQUIRED FOR THE STORAGE UNDER
 EXIT STAIR, FBC 705.8.2, TABLE 715.4.
  
 PROVIDE DOCUMENTATION SHOWING FIRE RATING FOR THE DOOR
 PROPOSED, NOA 12-0223.29, VISION HOLLOW METAL LTD
 SINGLE OUTSWING DOOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-06 Cont ID  
Sent By shill Date 2012-06-06 Time 09:36 Rev Time 0.00
Received By shill Date 2012-06-06 Time 09:36 Sent To  
Notes
2012-06-06 09:37:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. A 60 MINUTE DOOR IS REQUIRED FOR THE STORAGE UNDER
 EXIT STAIR, FBC 705.8.2, TABLE 715.4.
  
 AS DISCUSSED, THE NEW PROPOSED DOOR CAN BE SENT VIA
 EMAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-22 Cont ID  
Sent By shill Date 2012-02-22 Time 14:27 Rev Time 0.00
Received By shill Date 2012-02-22 Time 14:27 Sent To  
Notes
2012-02-22 14:30:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A PLAN WHICH SHOWS PROPOSED DOOR LOCATION,
 FBC 106.
  
 2. PROVIDE INFORMATION REGARDING THE EQUIPMENT IN THE
 MECHANICAL ROOM. IN OUR DISCUSSION AT THE FRONT
 COUNTER, THE PERSON SUBMITTING THE PLAN WAS INFORMED
 THAT THIS INFORMATION WOULD BE REQUIRED. PROVIDE A
 DESCRIPTION IN WRITING OF THE USE OF THE ROOM SO THAT
 CODE REQUIREMENTS CAN BE DETERMINED.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2012-07-02 Time   Rev Time 0.00
Received By mdekle Date 2012-06-29 Time 16:14 Sent To  
Notes
2012-06-29 16:15:09APPROVED PER FM.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-05 Cont ID  
Sent By shill Date 2012-07-05 Time 15:07 Rev Time 0.00
Received By shill Date 2012-06-29 Time 15:30 Sent To  
Notes
2012-06-29 15:31:11TO ZONING (NEEDS HISTORIC REVIEW)
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-22 Cont ID  
Sent By shill Date 2012-02-22 Time 14:30 Rev Time 0.00
Received By shill Date 2012-02-15 Time 16:13 Sent To  
Notes
2012-02-15 16:13:34MISC 1