Plan Review Details - Permit 12020360
Plan Review Stops For Permit 12020360
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-23 Cont ID  
Sent By jgomez Date 2012-02-23 Time 15:18 Rev Time 0.00
Received By jgomez Date 2012-02-23 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-16 Cont ID  
Sent By jgomez Date 2012-02-16 Time 13:22 Rev Time 0.00
Received By jgomez Date 2012-02-16 Time 13:17 Sent To  
Notes
2012-02-16 14:37:13ROOFING BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE WEBSITE, FLAT ROOF NOA
 07-0730.03 SUBMITTED WAS SUPERSEDED. PLEASE, VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AS REQUIRED
 BY DCA RULE 9N-3.
  
 2- ENGINEER WHO PROVIDED THE RAS 117 CALCULATIONS NEED
 TO REVISE THE CALCULATIONS REFERRING TO THE CURRENT NOA
 AND SPECIFIC APPROVED ASSEMBLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-23 Cont ID  
Sent By jgomez Date 2012-02-23 Time 15:18 Rev Time 0.00
Received By jgomez Date 2012-02-23 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-16 Cont ID  
Sent By jgomez Date 2012-02-16 Time 14:37 Rev Time 0.00
Received By jgomez Date 2012-02-15 Time 16:38 Sent To  
Notes
2012-02-15 16:39:35TO JG