Plan Review Details - Permit 12020339
Plan Review Stops For Permit 12020339
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-03-09 Cont ID  
Sent By jwitmer Date 2012-03-09 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2012-03-09 Time 08:34 Sent To  
Notes
2012-03-09 14:54:23BUILDING PROVISO:
  
 1) SHEET A1.1 INDICATES THAT THE HIGH DENSITY MOBILE
 FILE STORAGE SYSTEM BY OTHERS,
 FBC-B TABLE 1607.1 OFFICE BUILDINGS FILE STORAGE SHALL
 BE DESIGNED FOR HEAVIER LOADS
 BASED ON THE ANTICIPATED OCCUPANCY.
  
 2) SHEET A1.3 DETAIL # 11 INDICATES A LOUNGE OR BREAK
 ROOM SINK, PLEASE REVIEW 2007/09
 FBC-B 11-4 1-7. NOTE THAT THE HEIGHT REQUIREMENT OF 34"
 TOP OF COUNTER TOP.
  
 3) PLEASE SEE NOTIFICATION: FBC-B 707.14.1 ELEVATOR
 LOBBIES. MEMORANDUM FROM THE
 BUILDING OFFICIAL & BATTALION FIRE CHIEF.
  
 (3). IF A TENANT IMPROVEMENT IS SUBMITTED WHICH
 PROPOSES TO RECONFIGURE A PORTION OF THE
 EXISTING BUILDING FLOOR AREA, WITH NO WORK BEING
 PROPOSED IN THE AREA OF THE ELEVATOR LOBBY,
 AND NO ELEVATOR LOBBY IS FOUND TO EXIST ON THE FLOOR,
 AND NO VALID PERMIT CAN BE EVIDENCED
 WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER
 8, 2006, THE TENANT IMPROVEMENT
 PERMIT MAY BE APPROVED. THE BUILDING OWNER WILL BE
 NOTIFIED OF AN UNSAFE CONDITION ON THE
 EXISTING STRUCTURE BY THE CITY FIRE MARSHAL?S OFFICE
 AND ASKED TO UNDERTAKE APPROPRIATE ACTIONS
 TO CORRECT THE SITUATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 16:32 Rev Time 0.00
Received By rlecky Date 2012-02-28 Time 16:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-02-23 Cont ID  
Sent By wjolin Date 2012-02-23 Time 11:22 Rev Time 0.00
Received By wjolin Date 2012-02-23 Time 10:51 Sent To  
Notes
2012-02-23 11:19:16777 SOUTH FLAGLER DRIVE - SUITE #800 (EAST TOWER)
 PERMIT #12020339
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E-2: PROVIDE FIRE ALARM NOTIFICATION DEVICE IN
 CONFERENCE ROOM #810.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-14 Cont ID  
Sent By hmoser Date 2012-03-14 Time 14:25 Rev Time 0.00
Received By hmoser Date 2012-02-15 Time 12:41 Sent To  
Notes
2012-02-15 12:42:48C 07

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-03-14 Cont ID  
Sent By hmoser Date 2012-03-14 Time 14:25 Rev Time 0.00
Received By hmoser Date 2012-03-14 Time 13:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-02-21 Cont ID  
Sent By lwagner Date 2012-02-21 Time 14:15 Rev Time 0.00
Received By lwagner Date 2012-02-21 Time 11:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-02-29 Cont ID  
Sent By aaponte Date 2012-02-29 Time 08:45 Rev Time 0.00
Received By aaponte Date 2012-02-29 Time 08:45 Sent To  
Notes
2012-02-29 08:46:13INTERIOR TENANT IMPROVEMENT FOR OFFICE SPACE.