Plan Review Details - Permit 12020313
Plan Review Stops For Permit 12020313
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-02-24 Cont ID  
Sent By jwitmer Date 2012-02-24 Time 07:49 Rev Time 0.00
Received By jwitmer Date 2012-02-23 Time 16:09 Sent To  
Notes
2012-02-23 16:58:14BUILDING PROVISO:
 SHEET A4.1 INDICATES THE WALL TYPE W1 AS A UL U465 &
 WALL TYPE W2 AS A UL U423, PLEASE PROVIDE THE
 UL DESIGN INFORMATION FOR THE INSPECTORS AT TIME OF
 FRAMING INSPECTION. STUD GAUGE, SPACING, INSULATION &
 DRYWALL THICKNESS ARE ALL LOCATED WITHIN THE LISTING OF
 THE PRODUCT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 10:00 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 09:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-02-23 Cont ID  
Sent By rlecky Date 2012-02-23 Time 09:37 Rev Time 0.00
Received By rlecky Date 2012-02-23 Time 09:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-02-23 Cont ID  
Sent By wjolin Date 2012-02-23 Time 10:49 Rev Time 0.00
Received By wjolin Date 2012-02-23 Time 10:06 Sent To  
Notes
2012-02-23 10:43:54303 BANYAN STREET - 3RD FLOOR
 PERMIT #12020313
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A4.1: VERIFY SIDELIGHT WILL HAVE A 1-HOUR FIRE
 RATING FOR ROOM #109.
  
 SHEET A4.1: PROVIDE BI-DIRECTIONAL CHEVRON ON EXIT SIGN
 IN CORRIDOR #002.
  
 SHEET A4.1/SHEET E1.1: LIGHTING PLAN WILL NEED TO BE
 REVISED TO MATCH THE EXIT SIGN LOCATIONS AND CHEVRONS
 SHOWN ON THE LIFE SAFETY PLAN.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 10:01 Rev Time 0.00
Received By rlecky Date 2012-04-26 Time 13:01 Sent To  
Notes
2012-04-26 13:01:34INCOMING SENT TO H MOSER DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-14 Cont ID  
Sent By hmoser Date 2012-03-14 Time 13:41 Rev Time 0.00
Received By hmoser Date 2012-02-14 Time 16:25 Sent To  
Notes
2012-02-14 16:48:13B01

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-04-26 Cont ID  
Sent By hmoser Date 2012-04-26 Time 14:11 Rev Time 0.00
Received By hmoser Date 2012-04-26 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-14 Cont ID  
Sent By hmoser Date 2012-03-14 Time 13:41 Rev Time 0.00
Received By hmoser Date 2012-03-14 Time 12:59 Sent To  
Notes
2012-03-14 13:41:22PLANS DENIED
 1) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS.
 FOR FRESH AIR. 2007 FBC (M)
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3
 2007 FBC (M)
 3) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS PER SECTION
 301.5 LABELING.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-02-16 Cont ID  
Sent By lwagner Date 2012-02-16 Time 15:01 Rev Time 0.00
Received By lwagner Date 2012-02-16 Time 12:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-02-29 Cont ID  
Sent By aaponte Date 2012-02-29 Time 08:44 Rev Time 0.00
Received By aaponte Date 2012-02-29 Time 08:44 Sent To  
Notes
2012-02-29 08:44:45INTERIOR TENANT IMPROVEMENT FOR OFFICE SPACE ONLY.