Plan Review Details - Permit 12020282
Plan Review Stops For Permit 12020282
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By jwitmer Date 2012-03-27 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2012-03-27 Time 11:31 Sent To  
Notes
2012-03-27 11:43:28BUILDING PLAN REVIEW
 PERMIT: 12020282
 ADD: 2275 PALM BEACH LAKES BLVD
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC
 TEL: (561)282-8265
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 THE THREE ISSUES WERE RED LINED AS FOLLOWS:
 SHEETS LS-1.0 & A-1.0
 1) CORRIDOR DOOR E1 INFRONT OF EXAM ROOM # 7 TO BE
 REVERSED SWING IN THE DIRECTION OF EGRESS TRAVEL SEE
 2007/09 FBC-B 1008.1.2 OR FL INFORMAL INTERPRETATION
 4245.
  
 2) CORRIDOR DOOR C1 DIRECTLY OPPOSITE EXAM ROOM # 5 TO
 BE RESERVED SWING TO ALLOW DOOR TO NOT BLOCK EGRESS TO
 ROOM 1030 AND ALLOW DOOR TO LAY FLAT AGAINST THE
 CORRIDOR WALL PER
 2007/09 FBC-B 1005.2 SEE DOOR ENCROACHMENT.
  
 3) CORRIDOR DOOR SEPERATING CORRIDOR W1 & W2 WAS
 REVERSED AS REQUIRED BY 2007/09 FBC-B 1008.1.2 THIS
 CREATES A SECONDARY PROBLEM WITH 2007/09 FBC-B 11-4.
 13.6 THE REQUIRED 18 INCHES LATCH SIDE OF DOOR,
 CONTRACTOR SPOKE WWITH OWNER, BIFOLD DOORS TO BE
 REMOVED TO SOLVE THIS CODE ISSUE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-29 Cont ID  
Sent By jwitmer Date 2012-02-29 Time 13:26 Rev Time 0.00
Received By jwitmer Date 2012-02-28 Time 16:51 Sent To  
Notes
2012-02-28 16:55:19BUILDING PLAN REVIEW
 PERMIT: 12020282
 ADD: 2275 PALM BEACH LAKES BLVD
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC
 TEL: (561)282-8265
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) THE LS-1.0 SHEET INDICATES A NEW HANDICAPPED RAMP
 ON THE SIDE OF THE BUILDING. THE QUESTION IS THE FRONT
 ENTRY AN ACCESSIBLE ENTRANCE AND OR THE EXTERIOR DOOR
 THAT IS PART OF THE S2 CORRIDOR? THE SITE PLAN AS-1 AND
 NEW ACCESSIBILTY RAMP DOES NOT CONNECT TO AN ACCESSIBLE
 ROUTE OR PART OF THE EXIT DISCHARGE 2007/09 FBC-B
 11-4.1.2(1).
 2007 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1B) THE LS-1.0 NOR A-1.0 THE NEW ACCESSIBLE RAMP DOES
 NOT INDICATE THE USE OF A LOWER LANDING. 11-4.8.4.(2)
 LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT
 LESS THAN 72" OF STRAIGHT & LEVEL CLEARENCE.
  
 2A) NEITHER THE LS-1.0 NOR A-1.0 INDICATE THE USE OF
 FIRE RATED WALLS. THE FBC-B TABLE 508.2 REQUIRES WALLS
 TO BE FIRE RATED FOR INCIDENTAL USE AREAS (TABLE 508.2)
 ROOMA OR AREAS THAT ARE INCLUDED IN THIS CATEGORY ARE
 STORAGE ROOMS 100 SQ FT OR LARGER FOR BUILDINGS THAT DO
 NOT HAVE FIRE SPRINKLERS.
  
 2B) THE CONSTRUCTION OF THESE WALLS ARE AS FOLLOWS:
 FBC-B 508.2.2.1 CONSTRUCTION. WHERE TABLE 508.2
 REQUIRES A FIRE-RESISTANCE-RATED SEPARATION, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY A FIRE BARRIER CONSTRUCTED
 IN ACCORDANCE WITH SECTION 706 OR A HORIZONTAL ASSEMBLY
 CONSTRUCTED IN ACCORDANCE WITH SECTION 711, OR BOTH.
 WHERE TABLE 508.2 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF
 RESISTING THE PASSAGE OF SMOKE. THE PARTITIONS SHALL
 EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY OR
 FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY ABOVE OR TO
 THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, OR SUB
 DECK ABOVE.
  
 3A) SHEET LS-1.0 & A-1.0 DOOR # 1033 PLEASE REVIEW
 SECTION FBC-B 11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS, A MINIMUM OF 18 INCHES CLEARENCE AT THE LATCH
 SIDE.
  
 3B) SHEET LS-1.0 & A-1.0 DOOR # 1022 THAT LEADS INTO
 THE BREAK ROOM PLEASE REVIEW SECTION FBC-B 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS, A MINIMUM OF 18 INCHES
 CLEARENCE AT THE LATCH SIDE.
  
 4) SHEET LS-1.0 & A-1.0 THE DOOR BETWEEN CORRIDOR W 2
 AND THE COFFEE STATION 107 HAS TWO ISSUES, THE FIRST
 NOT HAVING THE MANEUVERING CLEARENCES REQUIRED BY FBC-B
 11-4.13.6 & SECTION FBC-B 11-4.4.1 PROTRUDING OBJECTS
 WITH THE TYPE OF FIRE EXTINGUISHER INDICATED AND
 LOCATION. OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE,
 TELEPHONES) WITH THEIR LEADING EDGES BETWEEN 27 INCHES
 AND 80 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED
 FLOOR SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM)
 INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES.
  
 5A) SHEET LS-1.0 & A-1.0 THE DOOR BETWEEN CORRIDOR W 2
 AND THE COFFEE STATION 107 SWINGS THE WRONG WAY, THIS
 BUILDING HAS AN OCCUPANT LOAD OF 69, OCCUPANT LOADS OF
 50 OR MORE THE DOOR SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL. FBC-B 1008.1.2.
  
 5B) SHEET LS-1.0 & A-1.0 THE DOOR BETWEEN CORRIDOR W1
 AND WAITING ROOM SWINGS THE WRONG WAY, THIS BUILDING
 HAS AN OCCUPANT LOAD OF 69, OCCUPANT LOADS OF
 50 OR MORE THE DOOR SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL. FBC-B 1008.1.2.
  
 5C) SHEET LS-1.0 & A-1.0 THE DOOR LOCATED AT 1033 DOES
 NOT INDICATE WHICH WAY THE OCCUPANTS SHOULD EXIT.
 OCCUPANTS NORMAL EXIT STRATEGY IS TO GO THROUGH THE
 FRONT EGRESS DOORS SINCE THIS IS THE PATH THEY CAME IN
 TO THE BUILDING. IF THIS HOLDS TRUE THEN THIS DOOR
 WOULD ALSSO NEED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL. FBC-B 1008.1.2.
  
 6) SHEET A-1.3 RAMP DETAILS:
  
 6A) DETAIL # 1 INDICATES FROM THE EDGE OF THE RAMP TTHE
 DIMENSION OF 1'-2" PLEASE REVIEWFBC-B 11-4.8.4(4) IF A
 DOORWAY IS LOCATED AT A LANDING, THEN THE AREA IN FRONT
 OF THE DOORWAY SHALL COMPLY WITH SECTION 11-4.13.6
 FIGURE 25-C WHICH REQUIRES 24".
  
 6B) DETAIL # 3 THE 18" HANDRAIL EXTENSIONS ARE TO BE
 PARALELL TO THE FLOOR OR GROUND SURFACES, NOT THE
 CONTINUATION OF THE SLOPE, 11-4.8.5(2) (GRAY BOX FL
 SPECIFIC).
  
 7) SHEET A-2.1 INDICATES INFILL OF WALLS WITH CONCRETE
 MASONRY UNITS & POURED REINFORCED CONCRETE BEAMS,
 ACI-530 CHAPTER 7 REINFORCED CONCRETE SECTION 7.5.3.1
 SHEAR REINFORCEMENT SHALL BE PROVIDED PERPENDICULAR TO
 THE DIRECTION OF APPLIED SHEAR FORCE. SPACING OF SHEAR
 REINFORCEMENT SHALL NOT EXCEED THE LESSER OF D/2 OR 48
 INCHES.
 DETAILS 4 & 6 ARE OF CONCERN.
  
 8) PRODUCT APPROVALS COULD NOT BE REVIEWED FOR WIND
 PRESSURES, SHEET A-2.0 DOES NOT PROVIDE THE WIND DESIGN
 CRITERIA;
 1609.6.2 WIND DESIGN PROCEDURES
 8.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 8.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 8.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 8.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 8.5 POSITIVE/ NEGATIVE PRESSURERS / COMPONENTS &
 CLADDING
  
 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-19 Cont ID  
Sent By rlecky Date 2012-03-19 Time 13:42 Rev Time 0.00
Received By rlecky Date 2012-03-19 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-21 Cont ID  
Sent By rlecky Date 2012-02-14 Time 08:05 Rev Time 0.00
Received By rlecky Date 2012-02-14 Time 09:41 Sent To  
Notes
2012-02-15 14:21:33PLEASE ADDRESS THE FOLLOWING COMMENTS:
  
 REVISE THE ELECTRICAL PLAN TO INCLUDE THE REQUIREMENTS
 FOR WIRING IN PATIENT CARE AREAS OF ALL EXAM AND
 TREATMENT ROOMS. NEC 517.10
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-04-04 Cont ID  
Sent By ddaniels Date 2012-04-04 Time 11:01 Rev Time 0.00
Received By ddaniels Date 2012-04-03 Time 10:20 Sent To B
Notes
2012-04-03 10:27:11 
 FIRE DEPARTMENT REVIEW ****APPROVED****
  
 1.) SUBMIT A LETTER TO CLARIFY THAT THIS IS A CHANGE OF
 OCCUPANCY AND WHAT TYPE.
 2.) SUBMIT A LETTER CONTAINING ANY INFORMATION ABOUT
 ANY PLANNED INSTALLATION OF F/A.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-04-02 Cont ID  
Sent By wjolin Date 2012-04-02 Time 13:28 Rev Time 0.00
Received By wjolin Date 2012-04-02 Time 13:28 Sent To  
Notes
2012-04-02 13:39:59PLANS REVIEWED AND FAILED BY CHIEF DANIELS ON 03/28/12.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-24 Cont ID  
Sent By ddaniels Date 2012-02-24 Time 12:55 Rev Time 0.00
Received By ddaniels Date 2012-02-22 Time 13:56 Sent To  
Notes
2012-02-24 12:57:52 
 PLEASE PROVIDE ADDITIONAL INFORMATION
  
 THIS APPEARS TO BE A CHANGE OF OCCUPANCY
  
 DERRICK DANIELS INTERIM BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 561 805-6733

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-04 Cont ID  
Sent By lmartine Date 2012-04-04 Time 14:35 Rev Time 0.00
Received By lmartine Date 2012-03-13 Time 10:29 Sent To  
Notes
2012-03-15 10:30:24C--5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-09 Cont ID  
Sent By hmoser Date 2012-03-09 Time 13:37 Rev Time 0.00
Received By hmoser Date 2012-02-13 Time 15:02 Sent To  
Notes
2012-02-13 15:02:27INCOMING SENT TO C05.JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2012-04-04 Cont ID  
Sent By jwitmer Date 2012-04-04 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2012-04-04 Time 15:57 Sent To  
Notes
2012-04-04 15:58:15IMPACT FEES ASSESSED ZERO DOLLARS DUE. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-03-09 Cont ID  
Sent By hmoser Date 2012-03-09 Time 11:22 Rev Time 0.00
Received By hmoser Date 2012-03-09 Time 10:25 Sent To  
Notes
2012-03-09 11:22:03PASS PROVISO
 1) PROVIDE MOTORIZED DAMPERS FOR OUT SIDE AIR
 PER SECTION 13-409.AB.3.3 SHUT OFF DAMPER CONTROLS
 2007 ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-03-23 Cont ID  
Sent By lwagner Date 2012-03-23 Time 08:32 Rev Time 0.00
Received By lwagner Date 2012-03-22 Time 08:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-16 Cont ID  
Sent By lwagner Date 2012-02-16 Time 11:34 Rev Time 0.00
Received By lwagner Date 2012-02-16 Time 09:12 Sent To  
Notes
2012-02-16 11:33:30FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE FOUR RESTROOMS SHOWN WILL BE REQUIRED TO BE
 ACCESSABLE PER FBC 11-4.1.3 (11) TOILET FACILITIES:
 IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH SECTION
 11-4.22....
  
 2. SHEET A-5.0 - THE REAR GRAB BAR AC6 IS REQUIRED TO
 BE 36" LENGTH. 11-4.17.6 SEE FIGURE 30 (A)
  
 3. SHEET P-1.0 SHOWS 3" PIPE 1/10" PER FOOT. 1/8" PER
 FOOT IS REQUIRED - PLUMBING 704.1
  
 4. PLEASE INCLUDE RISER DIAGRAMS FOR HOT AND COLD WATER
 AND SANITARY 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-02 Cont ID  
Sent By lfranco Date 2012-04-02 Time 14:23 Rev Time 0.00
Received By lfranco Date 2012-04-02 Time 14:23 Sent To  
Notes
***NONE***