Plan Review Details - Permit 12020230
Plan Review Stops For Permit 12020230
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-26 Cont ID  
Sent By jwitmer Date 2012-03-26 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2012-03-26 Time 13:35 Sent To  
Notes
2012-03-26 14:00:37BUILDING PLAN REVIEW
 PERMIT: 12020230
 ADD: 420 OKEECHOBEE BLVD
 CONT: DEALERSHIP SOLUTIONS
 TEL: (727)894-2182
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISO:
 WHEN THE WIND DESIGN CRITERIA IS CORRECT & NO APPROVALS
 ARE SUBMITTED THEN A PERMIT CAN BE ISSUED WITHOUT
 PRODUCT APPROVALS, THE PRODUCT APPROVALS CONSIDERED
 COMPONENTS & CLADDING WILL BE CONSIDERED A REVISION
 WITH SEPARATE REVIEW AND ASSOCIATED FEES.
 1) SHEET A000 PRODUCT APPROVAL INFORMATION
  
 THE SUMMARY OF THE PRODUCT APPROVALS DOES NOT HELP IN
 CODE COMPLIANCE REVIEW OR IN THE FIELD FOR INSTALLATION
 WHEN THE FULL PRODUCT APPROVALS ARE NOT SUBMITTED. WITH
 THE FULL PRODUCT REPORT PLEASE CIRCLE WHICH SUB-SYSTEMS
 ARE TO BE INSTALLED. MANY REPORTS PROVIDE OPTIONS FOR
 TYPE OF GLAZING, EACH HAVING THEIR OWN TEST PRESSURES.
 PLEASE NOTE THE ROOFING REPORT FL 3915 COULD NOT BE
 LOCATED ON LINE. DEPENDING ON THE ROOFING REPORT THERE
 MAY BE SUB-SYSTEMS AND VARYING PRESSURES WHICH MAY
 REQUIRE ENHANCED FASTENING IN ZONES 2 & 3.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-24 Cont ID  
Sent By jwitmer Date 2012-02-24 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2012-02-13 Time 15:49 Sent To  
Notes
2012-02-22 13:26:38BUILDING PLAN REVIEW
 PERMIT: 12020230
 ADD: 420 OKEECHOBEE BLVD
 CONT: DEALERSHIP SOLUTIONS
 TEL: (727)894-2182
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A000 PRODUCT APPROVAL INFORMATION
  
 THE SUMMARY OF THE PRODUCT APPROVALS DOES NOT HELP IN
 CODE COMPLIANCE REVIEW OR IN THE FIELD FOR INSTALLATION
 WHEN THE FULL PRODUCT APPROVALS ARE NOT SUBMITTED. WITH
 THE FULL PRODUCT REPORT PLEASE CIRCLE WHICH SUB-SYSTEMS
 ARE TO BE INSTALLED. MANY REPORTS PROVIDE OPTIONS FOR
 TYPE OF GLAZING, EACH HAVING THEIR OWN TEST PRESSURES.
 PLEASE NOTE THE ROOFING REPORT FL 3915 COULD NOT BE
 LOCATED ON LINE. DEPENDING ON THE ROOFING REPORT THERE
 MAY BE SUB-SYSTEMS AND VARYING PRESSURES WHICH MAY
 REQUIRE ENHANCED FASTENING IN ZONES 2 & 3.
  
  
 2) SHEET A100, 2007/09 FBC-B 503.1.2
 PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO BUILDINGS,
 ARE THESE TO BE CONSIDERED AS ONE OR TWO BUILDINGS ON
 THE SAME LOT WHERE FIRE RATED WALLS AND ALLOWABLE
 OPENINGS ARE A CONCERN? FBC-B TABLE 602 & 704.8 .
  
 3)SHEET A401,
 FBC-B 106.1.2.ADDITIONAL INFORMATION,
 PLEASE PROVIDE ADDITIONAL INFORMATION IN REGARDS TO
 WHAT APPEARS TO BE A DOOR SWING?
  
 4) SHEET A401,
 A) HIDDEN DOOR PLEASE INDICATE HOW THIS DOOR WILL
 COMPLY WITH FBC-B 11-4.13.6.
 THE 18 INCHES ON THE LATCH SIDE OF THE DOOR.
  
 B) PLEASE PROVIDE HOW THE HIDDEN DOOR WILL COMPLY WITH
 FBC-B 13.9 DOOR HARDWARE. HANDLES, PULLS, LATCHES,
 LOCKS, AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS
 SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND
 AND DOES NOT REQUIRE TIGHT GRIPPING, TIGHT PINCHING, OR
 TWISTING OF THE WRIST TO OPERATE.
  
 5) SHEET A401. PLEASE REVIEW BEVERAGE BAR AND
 ACCESSIBLE SINK (BAR) WITH THE CABINET ONLY BEING 21
 INCHES WIDE A FRONTAL APPROACH CAN NOT BE MADE, WITH
 THE BAR SINK BEING AGAINST THE WALL A SIDE APPROACH CAN
 NOT BE ACCOMPLISHED SINCE THE CENTERLINE OF THE WHEEL
 CHAIR WILL BE 24 INCHES FROM THE WALL.
  
 6) SHEET A401, WATER DISPENSER, PLEASE SEE PLUMBING
 COMMENT IN REGARDS TO THE REQUIRED DRINKING FOUNTAIN
 2007/09 PLUMBING CODE, SINCE THE FIRST DRINKING
 FOUNTAIN IS A REQUIRED FIXTURE THE ACCESSIBILITY CODE
 REQUIREMENTS APPLY 11-4.15. SAME ISSUES AS ABOVE FOR
 THE FRONTAL AND SIDE APPROACH.
  
  
 7) SHEET A300 COVERED DISPLAY AREA INDICATES THE USE OF
 A STUCCO CEILING SYSTEM BUT NO ADDITIONAL INFORMATION
 IS PROVIDED FOR WHAT TYPE OF MATERIALS WILL MAKE UP
 THIS SYSTEM?
 THE STRUCTURAL SHEETS INDICATES THIS BUILDING IS
 DESIGNED AS A TOTALLY ENCLOSED BUILDING .
 WILL THE PRESSURES BE GREATER UNDER THIS OPEN SPACE
 SIMILAR TO ROOF OVER HANGS? WILL A EFIS SYSTEM BE
 CONSIDERED FOR THIS APPLICATION IF SO PRODUCT APPROVALS
 FOR THIS SYSTEM WILL BE REQUIRED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED. RULE 9N3 (31)?.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 15:03 Rev Time 0.00
Received By rlecky Date 2012-02-27 Time 17:10 Sent To  
Notes
2012-02-28 15:03:4712020230
 420 OKEECHOBEE BLVD.
 FISKER CAR DEALER RENOVATION
  
 PROVISO:
 PROVIDE AN ENGINEERED DETAIL FOR THE COMPLETE LIGHT
 POLE MOUNTED ASSEMBLY WHICH PROVIDES A MINIMUM WIND
 LOAD CAPABILITY OF 140 MPH.
 PROVIDE THE SPECIFICATION AND LISTING FOR THE FISKER
 BATTERY CHARGING STATION. PROVIDE AN ELECTRIC
 DISCONNECT FOR CHARGERS IF RATED AT MORE THAT 60
 AMPERES. NEC 625.22
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-09 Cont ID  
Sent By wjolin Date 2012-04-09 Time 08:36 Rev Time 0.00
Received By wjolin Date 2012-04-09 Time 08:10 Sent To  
Notes
2012-04-09 08:21:38420 OKEECHOBEE BOULEVARD
 PERMIT #12020230
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 IN ADDITION TO THE FLORIDA BUILDING CODE, THE DESIGN
 SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE FLORIDA 2009 EDITION
 OF NFPA 1 AND NFPA 101.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-02-16 Cont ID  
Sent By wjolin Date 2012-02-16 Time 12:19 Rev Time 0.00
Received By wjolin Date 2012-02-16 Time 11:50 Sent To  
Notes
2012-02-16 12:19:01420 OKEECHOBEE BOULEVARD
 PERMIT #12020230
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 IN ADDITION TO THE FLORIDA BUILDING CODE, THE DESIGN
 SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE FLORIDA 2009 EDITION
 OF NFPA 1 AND NFPA 101.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THUMB-TURN LOCK TO BE EQUIPPED WITH A LOCK/UNLOCK
 INDICATOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2012-04-13 Time   Rev Time 0.00
Received By jwitmer Date 2012-03-20 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-03-16 Time   Rev Time 0.00
Received By rregueir Date 2012-02-13 Time 15:15 Sent To  
Notes
2012-02-13 15:16:07**DIGITAL PLANS** SEE PROJECTDOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-04-25 Cont ID  
Sent By rregueir Date 2012-04-25 Time 13:02 Rev Time 0.00
Received By rregueir Date 2012-04-17 Time 10:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-03-26 Cont ID  
Sent By jwitmer Date 2012-03-26 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2012-03-26 Time 13:34 Sent To  
Notes
2012-03-26 13:34:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-02-24 Cont ID  
Sent By rregueir Date 2012-02-24 Time 13:11 Rev Time 0.00
Received By rregueir Date 2012-02-13 Time 15:20 Sent To  
Notes
2012-02-24 13:11:20*** PROVISO ***
  
 1. PAGE M102: RTU 2 APPEARS TO BE WITHIN 10' OF AN
 ELEVATION CHANGE EXCEEDING 30". GUARDS ARE REQUIRED AT
 THIS OCATION PER FBC-M 304.10
  
 2. PAGE M102: ACCESS TO RTU 2 WOULD REQUIRE CLIMBING
 OVER A ROOF ELEVATION CHANGE EXCEEDING 30". A PERMANENT
 MEANS OF ACCESS IS REQUIRED AT THIS LOCATION PER FBC-M
 306.5.
  
 3. PAGE M501: FLEXIBLE DUCT DETAIL CALLS FOR 1" WIDE
 STRAP FOR SUPPORT. SUPPORTS SHALL BE MIN. 1.5" WIDE.
 ALSO, DETAIL CALL FOR MAX. 6' SPACING BETWEEN SUPPORTS.
 THE MAX. SPACING ALLOWED IS 5'. SEE FBC-M 603.5.6.6 FOR
 THESE AND ADDITIONAL REQUIREMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-02-16 Cont ID  
Sent By lwagner Date 2012-02-16 Time 09:06 Rev Time 0.00
Received By lwagner Date 2012-02-16 Time 09:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-04-06 Cont ID  
Sent By rregueir Date 2012-04-06 Time 10:38 Rev Time 0.00
Received By rregueir Date 2012-04-06 Time 10:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lfranco Date 2012-07-09 Time 15:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-04-13 Cont ID  
Sent By ajones Date 2012-04-13 Time 12:00 Rev Time 0.00
Received By ajones Date 2012-04-13 Time 11:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-16 Cont ID  
Sent By ajones Date 2012-03-16 Time 14:32 Rev Time 0.00
Received By ajones Date 2012-03-16 Time 14:32 Sent To  
Notes
2012-03-16 14:36:443-16-12- THE SITE PLAN SHOWN DOES NOT MATCH THE SITE
 PLAN APPROVED BY THE PLANNING DIVISION ON FEBRUARY 23,
 2012. PLEASE REVISED TO REFLECT THE APPROVED SITE PLAN.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]