Plan Review Details - Permit 12020222
Plan Review Stops For Permit 12020222
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-05-02 Cont ID  
Sent By shill Date 2012-05-02 Time 11:08 Rev Time 0.00
Received By shill Date 2012-05-02 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-03-05 Cont ID  
Sent By rlecky Date 2012-03-08 Time 10:47 Rev Time 0.00
Received By shill Date 2012-03-05 Time 13:18 Sent To FIRE
Notes
2012-03-05 13:39:41****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE SCOPE ON THE PERMIT APPLICATION (WINDOW
 REPLACEMENT) DOES NOT MATCH THE PLANS (SUNROOM). PLEASE
 ADDRESS.
  
 2ND REVIEW, IT APPEARS THAT THIS IS A ROOM ENCLOSURE.
 PLEASE HAVE THE ENGINEER REVISE THE PLAN TO INCLUDE
 BUILDING CONSTRUCTION TYPE, FBC CHAPTER 5 TO DETERMINE
 WHETHER A FOAM EXTERIOR WALL IS PERMITTED FOR THIS
 STRUCTURE. NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO
 DEMONSTRATE COMPLIANCE. A CODE SUMMARY (BUILDING TYPE,
 OCCUPANCY CLASSIFICATION, BUILDING SIZE, FIRE
 SPRINKLERS, ETC.) MAY BE HELPFUL. SEE ALSO FBC TABLE
 601.
  
 APPLICATION DESCRIPTION DOES NOT MATCH PLAN. PLAN SHOWS
 ENCLOSURE OF A PORCH, APPLICATION STATES 2 WINDOWS WILL
 BE INSTALLED IN A ROOM. IS THIS CURRENTLY A ROOM, OR A
 SCREEN PORCH AS SHOWN ON PLANS?
  
 2. ADDRESSED.
  
 3. PROVIDE A SURVEY SHOWING LOCATION OF PROPOSED
 IMPROVEMENT AND DISTANCE TO PROPERTY LINE, FBC R 302.
  
 NOT ADDRESSED. PROVIDE INFORMATION REGARDING DISTANCE
 TO THE PROPERTY LINE OR ASSUMED PROPERTY LINE, SEE FBC
 TABLE 602. CONTRACTOR'S NOTE THAT A SURVEY IS NOT
 REQUIRED AS THERE IS NO CHANGE IN FOOTPRINT IS
 ACKNOWLEDGED; HOWEVER, THIS DOES NOT ADDRESS THE ISSUE
 OF FIRE RISK TO ADJACENT STRUCTURES AS YOU ARE
 PROPOSING TO CHANGE THE LOCATION OF THE EXTERIOR WALL.
  
 4. OK.
  
 NEW COMMENTS:
  
 5. REVISE PLAN TO SHOW 1 HOUR SEPARATION REQUIRED
 BETWEEN THIS UNIT AND THE UNIT ABOVE, FBC 711.3.
  
 6. IMPACT FEE ASSESSMENT WILL BE REQUIRED, 233-5025 FOR
 MORE INFORMATION.
  
 7. ALL COMMENTS TO BE ADDRESSED BY A DESIGN
 PROFESSIONAL LICENSED UNDER FS 471 OR 481.
  
 8. IT IS NOT CLEAR HOW THE WINDOWS ARE TO BE INSTALLED
 INTO THE FOAM PANELS, THIS INSTALLATION NOT COVERED BY
 THE PRODUCT APPROVAL. NO STRUCTURAL INFORMATION HAS
 BEEN PROVIDED. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED
 INSTALLATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-10 Cont ID  
Sent By shill Date 2012-02-10 Time 16:24 Rev Time 0.00
Received By shill Date 2012-02-10 Time 16:24 Sent To  
Notes
2012-02-10 16:42:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE SCOPE ON THE PERMIT APPLICATION (WINDOW
 REPLACEMENT) DOES NOT MATCH THE PLANS (SUNROOM). PLEASE
 ADDRESS.
  
 2. PROVIDE ROOM DESIGNATION(S) FOR THE ROOMS IN THE
 HOUSE ADJACENT TO THE PROPOSED SUNROOM. SHOW ALL
 OPENINGS. FBC R 310.
  
 3. PROVIDE A SURVEY SHOWING LOCATION OF PROPOSED
 IMPROVEMENT AND DISTANCE TO PROPERTY LINE, FBC R 302.
  
 4. ENGINEERING IS FOR A 20' HIGH BUILDING; OTHER
 PERMITS OBTAINED AT THIS ADDRESS STATE THAT BUILDING
 HEIGHT IS GREATER THAN 20'. PLEASE ADDRESS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-08 Cont ID  
Sent By rlecky Date 2012-03-08 Time 11:19 Rev Time 0.00
Received By rlecky Date 2012-03-01 Time 10:59 Sent To B
Notes
2012-03-01 11:19:2912020222
 1002 GREEN PINE BLVD. #G1
 ELITE ADD A ROOM SYSTEM
  
 CATEGORY I SUNROOMS DO NOT REQUIRE RECEPTACLES IN
 ACCORDANCE WITH FBC 2003.9 AND FBC DECLARATORY
 STATEMENT DCA09-DEC-351
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-08 Cont ID  
Sent By rlecky Date 2012-02-13 Time 09:04 Rev Time 0.00
Received By rlecky Date 2012-02-13 Time 09:12 Sent To  
Notes
2012-02-13 09:06:34ELECTRICAL PLAN REQUIRED FOR NEW ENCLOSED SPACE. NEC
 210.52 (A)
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-03-08 Cont ID  
Sent By ddaniels Date 2012-03-08 Time 11:10 Rev Time 0.00
Received By ddaniels Date 2012-03-08 Time 11:10 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-05-02 Cont ID  
Sent By shill Date 2012-05-02 Time 11:08 Rev Time 0.00
Received By shill Date 2012-04-23 Time 11:21 Sent To  
Notes
2012-04-24 11:22:40SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-09 Cont ID  
Sent By rlecky Date 2012-03-09 Time 11:50 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 16:47 Sent To  
Notes
2012-02-29 16:47:46ELECT BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-13 Cont ID  
Sent By rlecky Date 2012-02-13 Time 09:12 Rev Time 0.00
Received By rlecky Date 2012-02-09 Time 14:13 Sent To  
Notes
2012-02-10 16:42:382/10 TO ELEC
  
2012-02-09 14:13:41SENT TO BUILDING UNDER $5000 SHELF FOR REVIEW. JG.