Plan Review Details - Permit 12020213
Plan Review Stops For Permit 12020213
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-02 Cont ID  
Sent By shill Date 2012-04-02 Time 12:27 Rev Time 0.00
Received By shill Date 2012-03-30 Time 12:00 Sent To  
Notes
2012-04-02 12:28:06***PROVISO***
 ***REVISION REQUIRED***
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 OHD, STOREFRONT AND DOOR, EXHAUST LOUVERS, FAC9N-3.
 EITHER PROVIDE PRODUCT APPROVALS, REVIEWED BY DOR, OR
 PLAN REVIEW WILL BE PASSED WITH PROVISO THAT PRODUCT
 APPROVALS BE SUBMITTED AS A REVISION PRIOR TO
 INSTALLATION (WITH FEES).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-23 Cont ID  
Sent By shill Date 2012-02-23 Time 10:59 Rev Time 0.00
Received By shill Date 2012-02-16 Time 12:20 Sent To  
Notes
2012-02-23 11:21:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 OHD, STOREFRONT AND DOOR, EXHAUST LOUVERS, FAC9N-3.
 EITHER PROVIDE PRODUCT APPROVALS, REVIEWED BY DOR, OR
 PLAN REVIEW WILL BE PASSED WITH PROVISO THAT PRODUCT
 APPROVALS BE SUBMITTED AS A REVISION PRIOR TO
 INSTALLATION (WITH FEES).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-04-05 Cont ID  
Sent By rlecky Date 2012-04-05 Time 09:58 Rev Time 0.00
Received By rlecky Date 2012-04-05 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-03-15 Cont ID  
Sent By rlecky Date 2012-03-15 Time 15:13 Rev Time 0.00
Received By rlecky Date 2012-03-15 Time 09:52 Sent To  
Notes
2012-03-15 15:17:4012020213
 2471 OKEECHOBEE BLVD.
 COMMERCIAL TENANT IMPROVEMENT
  
 THIS REVIEW HAS BEEN UPDATED IN RESPONSE TO THE REVISED
 PLANS AND CORRESPONDENCE RECEIVED 3/12/12 FROM LOUCKS
 ENGINEERING.
  
 THE PLANS INDICATE THERE ARE TWO POINTS OF SERVICE TO
 THE BUILDING WITHOUT THE MAIN SERVICE DISCONNECTS BEING
 GROUPED IN ONE LOCATION. THE ARCHITECTURAL PLANS SHOW
 ONE BUILDING. THE ONE HOUR RATED FIRE AND SMOKE TENANT
 SEPARATION DOES NOT ESTABLISH A SEPARATE BUILDING. NEC
 230.2, 230.71
 THE SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT NEEDS TO BE A LITTLE MORE SPECIFIC AS TO THE
 WORDING, SIZE, HAZARD AND TYPE OF MATERIAL. NEC 110.22,
 110.16
 THE SPACE PROVIDED FOR THE ELECTRICAL EQUIPMENT NEEDS
 TO BE DEDICATED AND PROTECTED. NEC 110.26 (F)
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-13 Cont ID  
Sent By rlecky Date 2012-02-13 Time 16:12 Rev Time 0.00
Received By rlecky Date 2012-02-13 Time 11:26 Sent To  
Notes
2012-02-13 15:30:0512020213
 2471 OKEECHOBEE BLVD.
 COMMERCIAL TENANT IMPROVEMENT
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 PROVIDE DEDICATED SPACE FOR THE SERVICE PANEL BOARDS.
 NEC 110.26 (F)
 PRIMARY AND SECONDARY FEEDER CONDUCTORS TO THE
 TRANSFORMER APPEAR TO BE UNDER SIZED OR TRANSFORMER IS
 OVERSIZED FOR THE LOAD. PLEASE CLARIFY. NEC 215.2
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. THE PLANS SUGGEST THIS
 BUILDING IS ALREADY SERVED FROM ANOTHER LOCATION. NEC
 230.2, 230.71
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED AT THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOM. NEC 110.22, 110.16
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-02 Cont ID  
Sent By wjolin Date 2012-04-02 Time 14:14 Rev Time 0.00
Received By wjolin Date 2012-04-02 Time 13:57 Sent To  
Notes
2012-04-02 14:14:432471 OKEECHOBEE BOULEVARD
 PERMIT #12020213
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL ELECTRICAL PLAN REVIEWER
 COMMENTS HAVE BEEN SATISFIED.
  
 NOTE: A DETAILED FURNITURE DISPLAY (DISPLAY HEIGHT,
 DISPLAY WIDTH, AISLE MARKINGS ETC.) WILL BE REQUIRED TO
 BE SUBMITTED AND REVIEWED BY THE FIRE DEPARTMENT PRIOR
 TO OCCUPANCY.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-14 Cont ID  
Sent By wjolin Date 2012-02-14 Time 15:25 Rev Time 0.00
Received By wjolin Date 2012-02-14 Time 14:58 Sent To  
Notes
2012-02-14 15:25:042471 OKEECHOBEE BOULEVARD
 PERMIT #12020213
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PERMITTED ONLY IN DESIGNATED AREAS. ALL OTHER
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 INDICATE THE SCOPE OF WORK FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS. SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EACH FIRE-RATED WALL/PARTITION SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007. THUMB-TURN LOCK TO BE
 EQUIPPED WITH A LOCK/UNLOCK INDICATOR.
  
 **THE PLANS INDICATE THIS WORK TO BE "SHELL
 IMPROVEMENTS"; A FURNITURE AND AISLE LAYOUT PLAN WILL
 BE NEEDED FOR ANY FUTURE TENANTS. OCCUPANCY WILL NOT BE
 GRANTED WITHOUT A PLAN.
  
 SHEET E2: NO EMERGENCY LIGHTING COULD BE LOCATED TO
 MATCH THE LIGHTING NOTES.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-05 Cont ID  
Sent By rlecky Date 2012-04-05 Time 09:58 Rev Time 0.00
Received By rlecky Date 2012-04-04 Time 16:28 Sent To  
Notes
2012-04-04 16:29:13INCOMING SENT TO R LECKY. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-02 Cont ID  
Sent By wjolin Date 2012-04-02 Time 14:14 Rev Time 0.00
Received By wjolin Date 2012-03-12 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-23 Cont ID  
Sent By shill Date 2012-02-23 Time 13:22 Rev Time 0.00
Received By shill Date 2012-02-09 Time 11:37 Sent To  
Notes
2012-02-09 11:42:18EXPEDITED, C--3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-02-23 Cont ID  
Sent By hmoser Date 2012-02-23 Time 10:55 Rev Time 0.00
Received By hmoser Date 2012-02-23 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-02-14 Cont ID  
Sent By lwagner Date 2012-02-14 Time 10:33 Rev Time 0.00
Received By lwagner Date 2012-02-14 Time 10:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-02-23 Cont ID  
Sent By shill Date 2012-02-23 Time 13:21 Rev Time 0.00
Received By shill Date 2012-02-23 Time 13:21 Sent To  
Notes
2012-02-23 13:22:11INTERIOR ONLY (S/W AV)