Plan Review Details - Permit 12020156
Plan Review Stops For Permit 12020156
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-03 Cont ID  
Sent By jwitmer Date 2012-08-03 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2012-08-01 Time 16:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-29 Cont ID  
Sent By jwitmer Date 2012-02-29 Time 13:40 Rev Time 0.00
Received By jwitmer Date 2012-02-29 Time 13:40 Sent To  
Notes
2012-02-29 13:55:59BUILDING PLAN REVIEW
 PERMIT: 12020156
 ADD: 2235 OKEECHOBEE BLVD
 CONT: TBD
 TEL: (561)594-1478
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A302 INDICATES THE USE OF ALUMINUM COMPOSITE
 PANELS PLEASE REVIEW FBC-B 1407.13 LABELING. MCM SHALL
 BE LABELED IN ACCORDANCE WITH SECTION 1703.5.
  
 1A)1703.5 LABELING. WHERE MATERIALS OR ASSEMBLIES ARE
 REQUIRED BY THIS CODE TO BE LABELED, SUCH MATERIALS AND
 ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY IN
 ACCORDANCE WITH SECTION 1703. PRODUCTS AND MATERIALS
 REQUIRED TO BE LABELED SHALL BE LABELED IN ACCORDANCE
 WITH THE PROCEDURES SET FORTH IN SECTIONS 1703.5.1
 THROUGH 1703.5.3.
  
 1B) 1703.5.1 TESTING. AN APPROVED AGENCY SHALL TEST A
 REPRESENTATIVE SAMPLE OF THE PRODUCT OR MATERIAL BEING
 LABELED TO THE RELEVANT STANDARD OR STANDARDS. THE
 APPROVED AGENCY SHALL MAINTAIN A RECORD OF THE TESTS
 PERFORMED. THE RECORD SHALL PROVIDE SUFFICIENT DETAIL
 TO VERIFY COMPLIANCE WITH THE TEST STANDARD.
  
 1C) 1703.5.2 INSPECTION AND IDENTIFICATION. THE
 APPROVED AGENCY SHALL PERIODICALLY PERFORM AN
 INSPECTION, WHICH SHALL BE IN-PLANT IF NECESSARY, OF
 THE PRODUCT OR MATERIAL THAT IS TO BE LABELED. THE
 INSPECTION SHALL VERIFY THAT THE LABELED PRODUCT OR
 MATERIAL IS REPRESENTATIVE OF THE PRODUCT OR MATERIAL
 TESTED.
  
 1D) 1703.5.3 LABEL INFORMATION. THE LABEL SHALL CONTAIN
 THE MANUFACTURER'S OR DISTRIBUTOR'S IDENTIFICATION,
 MODEL NUMBER, SERIAL NUMBER OR DEFINITIVE INFORMATION
 DESCRIBING THE PRODUCT OR MATERIAL'S PERFORMANCE
 CHARACTERISTICS AND APPROVED AGENCY'S IDENTIFICATION.
  
 1E) RULE 9N-3 FLORIDA STATE PRODUCT APPROVAL PROGRAM
 REQUIRES PRODUCT TESTING REPORTS PER 9N-3(31)(C)
 PRODUCTS INTRODUCED AS A RESULT OF NEW TECHNOLOGY.
  
 2) 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 5) POSITIVE & NEGATIVE PRESSURES/ COMPONENTS &
 CLADDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-31 Cont ID  
Sent By rlecky Date 2012-07-31 Time 11:20 Rev Time 0.00
Received By rlecky Date 2012-07-31 Time 08:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-10 Cont ID  
Sent By rlecky Date 2012-02-10 Time 09:59 Rev Time 0.00
Received By rlecky Date 2012-02-09 Time 12:48 Sent To  
Notes
2012-02-10 10:00:5412020156
 2235 OKEECHOBEE BLVD.
 COMMERCIAL REMODEL
  
 PLEASE ADDRESS THE FOLLOWING ITEMS.
  
 SHEET E-3:
  
 ELECTRICAL RISER AS ILLUSTRATED FROM MAIN #1 THROUGH
 THE TRANSFER SWITCH APPEARS TO INTERCHANGE THE FEEDERS
 FOR PANEL ?DB" AND THE EMERGENCY PANEL ?EDP? AND
 ISOLATE PANEL ?DB? WHEN THE FACILITY IS UNDER NORMAL
 POWER. NEC 215.5
 VERIFY EXISTING PANELS ?DA? AND ?DB? ARE RATED FOR 800
 AMPERES. NEC 215.5
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A GFCI PROTECTED RECEPTACLE FOR THE NEW WATER
 COOLER. NEC 422-52
 VERIFY THE ELECTRICAL SERVICE, WHICH APPEARS TO BE
 LOCATED IN A REMOTE STRUCTURE, MEETS THE REQUIREMENT
 FOR BONDING OF THE GROUNDED CONDUCTOR AT THE MAIN
 SERVICE DISCONNECTS AND THE REQUIREMENTS FOR GROUNDING
 OF THE SYSTEM AT THE MAIN STRUCTURE. NEC 250.24, 250.32
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED AT THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOM. NEC 110.22, 110.16
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-07-28 Cont ID  
Sent By wjolin Date 2012-07-28 Time 16:36 Rev Time 0.00
Received By wjolin Date 2012-07-28 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-14 Cont ID  
Sent By wjolin Date 2012-02-14 Time 14:53 Rev Time 0.00
Received By wjolin Date 2012-02-14 Time 14:22 Sent To  
Notes
2012-02-14 14:53:572235 OKEECHOBEE BOULEVARD
 PERMIT #12020156
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PERMITTED ONLY IN DESIGNATED AREAS. ALL OTHER
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING, FIRE RATED WALLS,
 FIRE RATED DOORS, EXIT SIGNS, EMERGENCY LIGHTING,
 TRAVEL DISTANCES, ETC.
  
 THE EXISTING DRIVE BETWEEN THE CUSTOMER PARKING AND THE
 MAIN ENTRY IS A FIRE LANE FOR THE BUILDING. FIRE LANES
 SHALL BE MARKED WITH FREESTANDING SIGNS READING, "FIRE
 LANE - NO PARKING BY ORDER OF THE FIRE DEPARTMENT."
 SIGNS SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND
 RED LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN
 HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN
 SIGHT OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60
 FEET APART. FLORIDA FIRE PREVENTION CODE SECTION
 18.2.3.5.3.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-08-23 Cont ID  
Sent By jwitmer Date 2012-08-23 Time 16:30 Rev Time 0.00
Received By jwitmer Date 2012-08-16 Time 13:39 Sent To  
Notes
2012-08-17 13:39:32IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-08 Cont ID  
Sent By eschneid Date 2012-08-08 Time 17:08 Rev Time 0.00
Received By eschneid Date 2012-07-18 Time 13:38 Sent To  
Notes
2012-07-18 13:40:06INCOMING SENT TO C09. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-19 Cont ID  
Sent By hmoser Date 2012-03-19 Time 13:32 Rev Time 0.00
Received By hmoser Date 2012-02-07 Time 14:05 Sent To  
Notes
2012-02-08 14:05:58INCOMING SENT TO C02. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-03-19 Cont ID  
Sent By hmoser Date 2012-03-19 Time 13:31 Rev Time 0.00
Received By hmoser Date 2012-03-19 Time 12:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2012-08-23 Cont ID  
Sent By mdekle Date 2012-08-22 Time 15:25 Rev Time 3.00
Received By eschneid Date 2012-08-20 Time   Sent To PC
Notes
2012-08-22 16:44:25PASSED
  
 THERE IS A DISCREPANCY BETWEEN THE SURVEY AND THE
 ARCHITECTURAL PLAN IN THE AREA FOR THE RELOCATED 32
 LINEAR FEET OF FOUNDATION PLANTING. THE SURVEY SHOWS 37
 FEET BETWEEN THE 2 EXISTING STAIRWAYS, OF WHICH 32 FEET
 WILL BE FOUNDATION PLANTING AND 5 FEET WILL BE THE
 LANDING FOR THE STAIRS. THE ARCHITECTURAL PLANS ONLY
 SHOW 29 FEET BETWEEN THE STAIRS. THE ARCHITECT HAS
 PROVIDED A LETTER STATING THAT THE SURVEY SHOWS THE
 CORRECT DIMENSIONS, NOT THE ARCHITECTURAL PLANS.
  
 THE EXTERIOR VISIBLE SIGNAGE FOR THIS SITE WILL REQUIRE
 A SEPARATE PERMIT(S). PLEASE NOTE THAT THE SUBMITTED
 PLANS SEEM TO HAVE MORE SIGNAGE THAN IS PERMITTED BY
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS.
 PLEASE NOTE THAT THE DEALER WALL, POSTER BOARDS, MENU
 BOARD, ETC. ARE CONSIDERED SIGNS. ADDITIONALLY, IF THE
 KEY DROP, DISPLAY PILLARS AND DIRECTIONAL PYLONS
 INCLUDE LOGOS OR VERBIAGE FOR CHEVROLET OR ROGER DEAN,
 THEY ARE CONSIDERED SIGNAGE.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2012-08-20 14:54:19GAVE TO E.S.

Review Stop Z ZONING
Rev No 2 Status F Date 2012-08-08 Cont ID  
Sent By eschneid Date 2012-08-08 Time 15:28 Rev Time 1.00
Received By eschneid Date 2012-07-23 Time 16:56 Sent To  
Notes
2012-08-08 15:28:33FAILED
  
 1) REPEAT COMMENT - PRIOR TO THE ZONING APPROVAL OF
 THIS PERMIT, A LANDSCAPE PERMIT SHALL BE SUBMITTED TO
 THE BUILDING DIVISION WHICH INCLUDES A LANDSCAPE PLAN,
 PREPARED BY A LANDSCAPE ARCHITECT, THAT SHOWS THE
 EXISTING CONDITIONS OF THE SITE AND THE PROPOSED
 DEVELOPMENT PLAN. THE EXISTING CONDITIONS PLAN SHALL
 INCLUDE, IN TABULAR DATA, THE EXISTING LANDSCAPE ON THE
 SITE, THE AMOUNT OF LANDSCAPE AREA, THE AMOUNT OF
 FOUNDATION PLANTING, ETC. THE PROPOSED DEVELOPMENT PLAN
 SHALL DEMONSTRATE, AT A MINIMUM, NO NET LOSS OF
 LANDSCAPE MATERIAL, LANDSCAPE AREA, AMOUNT OF
 FOUNDATION PLANTING, ETC.
  
 2) THE LANDSCAPE PLAN SUBMITTED WITH THIS APPLICATION
 WILL BE FULLY REVIEWED AS PART OF THE LANDSCAPE PERMIT;
 HOWEVER, THE STAFF HAS IDENTIFIED A FAILURE OF THE
 LANDSCAPE PLAN (AND CONSTRUCTION PLANS) TO MAINTAIN THE
 EXISTING AMOUNT OF FOUNDATION PLANTING. THE ZONING AND
 LAND DEVELOPMENT REGULATIONS REQUIRE THAT A MINIMUM OF
 30% OF THE LINEAR FEET AROUND A BUILDING CONTAINS
 FOUNDATION PLANTING. THE EXISING BUILDING DOES NOT MEET
 THE 30% MINIMUM REQUIREMENT; THEREFORE, THE FOUNDATION
 PLANTING MAY NOT BE REDUCED. THE PLAN SHOWS A REDUCTION
 OF 32 LINEAR FEET OF FOUNDATION PLANTING, WHICH IS NOT
 PERMITTED. THE ZONING STAFF MAY NOT APPROVE THE
 PROPOSED RENOVATIONS AS THEY REDUCE THE AMOUNT OF
 FOUNDATION PLANTING.
  
 3) THE RELOCATED PALM TREES REQUIRE THE APPROVAL OF A
 TREE ALTERATION PERMIT, WHICH SHALL BE SUBMITTED TO THE
 CITY'S ZONING DIVISION.
  
 4) THE EXTERIOR VISIBLE SIGNAGE FOR THIS SITE WILL
 REQUIRE A SEPARATE PERMIT(S). PLEASE NOTE THAT THE
 SUBMITTED PLANS SEEM TO HAVE MORE SIGNAGE THAN IS
 PERMITTED BY THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS. PLEASE NOTE THAT THE DEALER WALL, POSTER
 BOARDS, MENU BOARD, ETC. ARE CONSIDERED SIGNS.
 ADDITIONALLY, IF THE KEY DROP, DISPLAY PILLARS AND
 DIRECTIONAL PYLONS INCLUDE LOGOS OR VERBIAGE FOR
 CHEVROLET OR ROGER DEAN, THEY ARE CONSIDERED SIGNAGE.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-07 Cont ID  
Sent By eschneid Date 2012-03-07 Time 11:49 Rev Time 2.00
Received By eschneid Date 2012-03-07 Time 11:49 Sent To  
Notes
2012-03-07 11:49:49FAILED
  
 PLEASE PROVIDE THE RESPONSES IN WRITING.
  
 1) TWO COPIES OF A RECENT SURVEY, SHOWING THE SITE WITH
 THE IMPROVEMENTS RELATED TO THE REMOVAL OF THE USED
 VEHICLE BUILDING, OF THE PROPERTY IS REQUIRED. THE
 SURVEY SHALL INCLUDE THE BUILDING FOOTPRINT AND ITS
 SETBACKS AND THE EXISTING CURBING AND LANDSCAPE AREAS.
  
 2) THE SITE PLAN PROVIDED AS SHEET A100 IS NO LONGER
 CURRENT. IT SHALL BE REVISED TO MATCH THE CONDITIONS
 SHOWN FROM THE SURVEY REQUIRED IN COMMENT NO. 1.
  
 3) SHEET A201, NOTE #19, INDICATES THAT THERE WILL BE
 REMOVAL OF FOUNDATION PLANTING ON THE SOUTH SIDE OF THE
 BUILDING, WITH A RELOCATION OF MATERIAL. PRIOR TO THE
 ZONING APPROVAL OF THIS PERMIT, A LANDSCAPE PERMIT
 SHALL BE SUBMITTED TO THE BUILDING DIVISION WHICH
 INCLUDES A LANDSCAPE PLAN, PREPARED BY A LANDSCAPE
 ARCHITECT, THAT SHOWS THE EXISTING CONDITIONS OF THE
 SITE AND THE PROPOSED DEVELOPMENT PLAN. THE EXISTING
 CONDITIONS PLAN SHALL INCLUDE, IN TABULAR DATA, THE
 EXISTING LANDSCAPE ON THE SITE, THE AMOUNT OF LANDSCAPE
 AREA, THE AMOUNT OF FOUNDATION PLANTING, ETC. THE
 PROPOSED DEVELOPMENT PLAN SHALL DEMONSTRATE, AT A
 MINIMUM, NO NET LOSS OF LANDSCAPE MATERIAL, LANDSCAPE
 AREA, AMOUNT OF FOUNDATION PLANTING, ETC.
  
 4) THE EXTERIOR VISIBLE SIGNAGE FOR THIS SITE WILL
 REQUIRE A SEPARATE PERMIT(S). PLEASE NOTE THAT THE
 SUBMITTED PLANS SEEM TO HAVE MORE SIGNAGE THAN IS
 PERMITTED BY THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS. PLEASE NOTE THAT THE DEALER WALL, POSTER
 BOARDS, MENU BOARD, ETC. ARE CONSIDERED SIGNS.
 ADDITIONALLY, IF THE KEY DROP, DISPLAY PILLARS AND
 DIRECTIONAL PYLONS INCLUDE LOGOS OR VERBIAGE FOR
 CHEVROLET OR ROGER DEAN, THEY ARE CONSIDERED SIGNAGE.
  
 5) PLEASE PROVIDE EVIDENCE THAT THE NEW EXTERIOR
 LIGHTING WILL NOT CAUSE GLARE ONTO THE ADJACENT PUBLIC
 THOROUGHFARES (OKEECHOBEE BLVD. AND CONGRESS AVE.).
  
 6) PLEASE EXPLAIN WHAT OCCURS IN THE "NEW CAR DELIVERY
 AREA". IT APPEARS TO BE SHOWN AS OPEN SIDED ON SHEET
 A203, YET ON SHEET A805 THERE IS AN ENCLOSED AND AN
 OPEN OPTION. IF IT IS TO BE OPEN, THEN PLEASE REMOVE
 THE ENCLOSED OPTION FROM THE PLANS. IF THE AREA IS TO
 BE ENCLOSED, THEN THERE SHALL BE ADDITIONAL INFORMATION
 PROVIDED REGARDING THE AMOUNT OF NEW SQUARE FOOTAGE,
 THE TOTAL SQUARE FOOTAGE ON THE SITE AND THE PARKING
 CALCULATION FOR THE SITE BASED ON THE NEW OVERALL
 SQUARE FOOTAGE.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  