Plan Review Details - Permit 12020074
Plan Review Stops For Permit 12020074
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-03-29 Cont ID  
Sent By shill Date 2012-03-29 Time 11:32 Rev Time 0.00
Received By shill Date 2012-03-29 Time 11:32 Sent To  
Notes
2012-03-29 11:49:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. OUR RECORDS SHOW THAT THE WALL HAS NOT OBTAINED THE
 LEGALLY REQUIRED INSPECTIONS. THIS MUST BE ADDRESSED
 PRIOR TO ISSUANCE OF A PERMIT TO ALTER THE WALL. PLEASE
 APPLY FOR A REISSUE PERMIT TO OBTAIN THE REQUIRED FINAL
 INSPECTION.
  
 2. OUR RECORDS SHOW A 12"X16" FOOTING FOR THE EXISTING
 WALL. IT DOES NOT APPEAR THAT THIS IS ADEQUATE TO
 SUPPORT LOADS REQUIRED FOR THE PROPOSED IMPROVEMENT.
 EITHER ENGINEERING OR CALCULATIONS WILL BE REQUIRED.
  
 3. THERE IS A PARCEL HOLD PLACED ON THIS PROPERTY WHICH
 STATES THAT NEIGHBORS REPORTED THAT THERE WAS DAMAGE TO
 THE EAST AND WEST. THIS ISSUE WILL BE ADDRESSED DURING
 THE REISSUE PROCESS FOR THE WALL PREVIOUSLY
 CONSTRUCTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-14 Cont ID  
Sent By shill Date 2012-02-14 Time 10:55 Rev Time 0.00
Received By shill Date 2012-02-14 Time 10:55 Sent To  
Notes
2012-02-14 10:56:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL DETAIL TO SHOW HOW THIS
 PROPOSED IMPROVEMENT WILL RESIST WIND LOADS, FBC R301.
 DETAIL IS TO INCLUDE WIND DESIGN CRITERIA, (140MPH,
 EXPOSURE C). ENGINEERING MAY BE REQUIRED.
  
 2. AS DISCUSSED, PLEASE PROVIDE A COPY OF THE EXISTING
 WALL PLAN. AS DISCUSSED, IF POSSIBLE, CALL ME TO SEE
 THE PLAN PRIOR TO SUBMITTAL TO DETERMINE WHETHER THE
 EXISTING FOOTER WILL BE ADEQUATE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-29 Cont ID  
Sent By shill Date 2012-03-29 Time 11:49 Rev Time 0.00
Received By shill Date 2012-03-23 Time 10:01 Sent To  
Notes
2012-03-23 10:01:55TO SH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-14 Cont ID  
Sent By shill Date 2012-02-14 Time 10:56 Rev Time 0.00
Received By shill Date 2012-02-03 Time 10:33 Sent To  
Notes
2012-02-03 10:29:46TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-02-10 Cont ID  
Sent By astelly Date 2012-02-10 Time 16:58 Rev Time 0.00
Received By astelly Date 2012-02-10 Time 16:58 Sent To  
Notes
2012-02-10 17:11:07AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W PROVISO
 MAX HEIGHT WITHIN FRONT SETBACK: 4 FT. + 10% OR 53
 INCHES
 MAX HEIGHT BEYOND THE FRONT SETBACK: 6 FT. + 10% OR 79
 INCHES
  