Plan Review Details - Permit 12020021
Plan Review Stops For Permit 12020021
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-02-09 Cont ID  
Sent By jwitmer Date 2012-02-09 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2012-02-09 Time 12:54 Sent To  
Notes
2012-02-09 12:54:26BUILDING PLAN REVIEW
 PERMIT: 12020021
 ADD: 477 S ROSEMARY # 318
 CONT: STRATICON LLC
 TEL: (954)927-1845
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 02/09/2012
 12:30 PM
 RECEIVED FROM THE DESIGNER OF RECORD ROGER JANSSEN A
 LETTER INDICATING WHERE THEY WILL BE SPENDING THE 20%
 DISPROPORTIONATE COST TO COMPLY WITH FLORIDA
 ACCESSIBILITY REQUIREMENTS. SEE ATTACHMENT LETTERS.
  
 1) A REVISED FLOOR PLAN INDICATING COMPLIANCE FOR THE
 20% DISPROPORTIONATE COST INDICATING WHERE AND HOW
 COMPLIANCE WAS ACHIEVED.
  
 PLEASE NOTE: PLUMBING PROVISO: TO CAP OFF DRAIN & WATER
 LINES FOR CONCEALED TUB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-09 Cont ID  
Sent By jwitmer Date 2012-02-09 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2012-02-09 Time 08:01 Sent To  
Notes
2012-02-09 08:02:31BUILDING PLAN REVIEW
 PERMIT: 12020021
 ADD: 477 S ROSEMARY # 318
 CONT: STRATICON LLC
 TEL: (954)927-1845
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 PLEASE NOTE: WEST PALM BEACHADMINISTRATIVE CODE: 105.1
 REQUIRED. ANY OWNER, OR AUTHORIZED AGENT SHALL OBTAIN A
 PERMIT FOR A CHANGE IN OCCUPANCY.
 THE CITY RECORDS DO NOT INDICATE ANY CHANGE OF
 OCCUPANCY FOR 228 OR 318. PLEASE BE AWARE THAT THE
 CHANGE OF OCCUPANCY IS NOT THE TRIGGERING EVENT THAT
 INACTS THE ACCESSIBILITY REQUIREMENTS. THE TRIGGERING
 EVENT IS THE ALTERED AREAS (FBC-B-11-4.1.1(1)(A) AAND
 SECTION 11-4.1.3 ALTERED PORTIONS OF EXISTING
 BUILDINGSAND FACILITIES REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1.6SHALL COMPLY WITH THIS CODE. THIS
 PERMIT INDICATES $19,242.00 AMOUNT OF WORK TO BE
 COMPLETED UNDERTHIS PERMIT. 11-4.1.6(2) REQUIRES AN
 ADDITIONAL $3848.00 AMOUNT OF WORK TO BE ACCOMPLISHED
 TO BRING THIS UNIT UP TO MEET THE ACCESSIBILTY CODE,
 WHEN THE MONIES ARE SPENT THE CONTRACTOR DOES NOT HAVE
 TO DO ANY MORE WORK. AS LISTED BELOW ITEM 3 WE HAVE
 ASKED FOR EITHER THE CONTRACTOR OR DESIGNER OF RECORD
 TO CREATE A LIST ITEMIZING WHERE THES MONIES HAVE BEEN
 SPENT IN THE ORDER LISTED IN COMMENT 2A.
  
 THE PERMIT IS NOT ONLY A CHANGE IN OCCUPANCY BUT A
 LEVEL II ALTERATION. THE EXIST BLDG CODE LEVEL LI
 CHAPTER ALSO HAS A PORTION THAT DEALS WITH
 ACCESSIBILITY 706.1, THIS IS THE TRIGGERING DEVICE FOR
 THE ACCESSIBLITY REQUIREMENTS.
  
 1) THE PLANS SHEET A-1 INDICATE THIS TENANT BUILD OUT
 TO BE A CLASSROOM. PLEASE PROVIDE THE AGES OF THE
 OCCUPANTS AND ACTIVITY. FBC-B EDUCATIONAL OCCUPANCY ARE
 OCCUPANTS THAT ARE SIX OR MORE PEOPLE GATHERED TOGRTHER
 THROUGH THE 12TH GRADE. STUDENTS OVER THE 12TH GRADE
 THE OCCUPANCY TYPE IS CONSIDERED A BUSINESS OCCUPANCY.
 FBC-B 304.1 & 305.1.
  
 2) FOR UNIT # 228 THIS IS CONSIDERED A CHANGE OF
 OCCUPANCY FROM A R2 RESIDENTIAL UNIT TO EITHER B OR E
 DEPENDING ON THE AGE OF THE STUDENTS. THIS REVIEW WILL
 BE ASSUMED AS A BUSINESS OCCUPANCY. PLEASE NOTE THE 2ND
 & 3RD FLOORS WERE BUILT TO THE FAIR HOUSING STANDARDS
 SINCE THESE UNITS WERE DESIGNED AS A R2 OCCUPANCY.
 PLEASE REVIEW THE 2007/09 EXISTING BUILDING CODE 912.8
 ACCESSIBILITY , EXISTING BUILDINGS OR PORTIONS THEREOF
 THAT UNDER GO A CHANGE OF OCCUPANCY CLASSIFICATION
 SHALL COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2A) THE 2007/09 FBC-B CHAPTER 11-4.1.6(2) THIS SECTION
 INDICATES THAT WHEN ALTERATIONS ARE DONE 20 % OF THE
 COST OF THE ALTERATIONS OVER AND ABOVE THE CONTRACT
 VALUE NEED TO GO TO ACCESSIBILITY TO BRING THE
 BUILDING( UNIT) INTO CODE COMPLIANCE WITH THE
 ACCESSIBILITY CODE. THE CODE INDICATES HOW THESE FUNDS
 ARE TO BE ALLOWCATED.
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 2B) A ACCESSIBLE ENTRANCE IS REQUIRED MISSING THE
 REQUIRED 18" ON THE INTERIOR SIDE OF THE ENTRY DOOR.
 2007/09 FBC-B 11-4.13.6.
  
 2C) THE SAME REQUIREMENT IS MISSING ON THE IT CLOSET
  
 3) THE NEXT AREA IN QUESTION IS AT THE RESSTROOM AREA.
 THE PLANS INDICATE A NEW WALL BEING PLACED BETWEEN THE
 TUB AND WATER CLOSET PLEASE PROVIDE A WALL DETAIL
 INDICATING THE LOCATION OF THE NEW WALL INREGARDS TO
 THE TUB AND THE DISTANCE AWAY FROM THE FINISHED WALL TO
 THE CENTERLINE OF THE WATER CLOSET, IT APPEARS THE
 CENTERLINE DISTANCE WILL NOT BE CLOSE TO THE REQUIRED
 18 INCHES. 2007/09 FBC-B 11-4.11-4.16.2/ 11-4.16.3 &
 FIGURE 11-28.
  
 PLEASE PROVIDE AN ITEMIZED LIST WHERE THESE FUNDS WILL
 BE USED IN MAKING THESE TENAT SPACES CLOSER TO CODE
 COMPLIANCE FOR ACCESSIBIITY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-06 Cont ID  
Sent By jwitmer Date 2012-02-06 Time 14:31 Rev Time 0.70
Received By jwitmer Date 2012-02-06 Time 14:31 Sent To  
Notes
2012-02-06 14:32:30BUILDING PLAN REVIEW
 PERMIT: 12020021
 ADD: 477 S ROSEMARY # 318
 CONT: STRATICON LLC
 TEL: (954)927-1845
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PLANS SHEET A-1 INDICATE THIS TENANT BUILD OUT
 TO BE A CLASSROOM. PLEASE PROVIDE THE AGES OF THE
 OCCUPANTS AND ACTIVITY. FBC-B EDUCATIONAL OCCUPANCY ARE
 OCCUPANTS THAT ARE SIX OR MORE PEOPLE GATHERED TOGRTHER
 THROUGH THE 12TH GRADE. STUDENTS OVER THE 12TH GRADE
 THE OCCUPANCY TYPE IS CONSIDERED A BUSINESS OCCUPANCY.
 FBC-B 304.1 & 305.1.
  
 2) FOR UNIT # 228 THIS IS CONSIDERED A CHANGE OF
 OCCUPANCY FROM A R2 RESIDENTIAL UNIT TO EITHER B OR E
 DEPENDING ON THE AGE OF THE STUDENTS. THIS REVIEW WILL
 BE ASSUMED AS A BUSINESS OCCUPANCY. PLEASE NOTE THE 2ND
 & 3RD FLOORS WERE BUILT TO THE FAIR HOUSING STANDARDS
 SINCE THESE UNITS WERE DESIGNED AS A R2 OCCUPANCY.
 PLEASE REVIEW THE 2007/09 EXISTING BUILDING CODE 912.8
 ACCESSIBILITY , EXISTING BUILDINGS OR PORTIONS THEREOF
 THAT UNDER GO A CHANGE OF OCCUPANCY CLASSIFICATION
 SHALL COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2A) THE 2007/09 FBC-B CHAPTER 11-4.1.6(2) THIS SECTION
 INDICATES THAT WHEN ALTERATIONS ARE DONE 20 % OF THE
 COST OF THE ALTERATIONS OVER AND ABOVE THE CONTRACT
 VALUE NEED TO GO TO ACCESSIBILITY TO BRING THE
 BUILDING( UNIT) INTO CODE COMPLIANCE WITH THE
 ACCESSIBILITY CODE. THE CODE INDICATES HOW THESE FUNDS
 ARE TO BE ALLOWCATED.
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 2B) A ACCESSIBLE ENTRANCE IS REQUIRED MISSING THE
 REQUIRED 18" ON THE INTERIOR SIDE OF THE ENTRY DOOR.
 2007/09 FBC-B 11-4.13.6.
  
 2C) THE SAME REQUIREMENT IS MISSING ON THE IT CLOSET
  
 3) THE NEXT AREA IN QUESTION IS AT THE RESSTROOM AREA.
 THE PLANS INDICATE A NEW WALL BEING PLACED BETWEEN THE
 TUB AND WATER CLOSET PLEASE PROVIDE A WALL DETAIL
 INDICATING THE LOCATION OF THE NEW WALL INREGARDS TO
 THE TUB AND THE DISTANCE AWAY FROM THE FINISHED WALL TO
 THE CENTERLINE OF THE WATER CLOSET, IT APPEARS THE
 CENTERLINE DISTANCE WILL NOT BE CLOSE TO THE REQUIRED
 18 INCHES. 2007/09 FBC-B 11-4.11-4.16.2/ 11-4.16.3 &
 FIGURE 11-28.
  
 PLEASE PROVIDE AN ITEMIZED LIST WHERE THESE FUNDS WILL
 BE USED IN MAKING THESE TENAT SPACES CLOSER TO CODE
 COMPLIANCE FOR ACCESSIBIITY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By rlecky Date 2012-02-09 Time 09:33 Rev Time 0.00
Received By rlecky Date 2012-02-08 Time 17:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-02-03 Cont ID  
Sent By rlecky Date 2012-02-03 Time 15:23 Rev Time 0.00
Received By rlecky Date 2012-02-03 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-02-27 Cont ID  
Sent By wjolin Date 2012-02-27 Time 13:04 Rev Time 0.00
Received By wjolin Date 2012-02-27 Time 13:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By wjolin Date 2012-02-09 Time 11:58 Rev Time 0.00
Received By wjolin Date 2012-02-09 Time 11:57 Sent To M
Notes
2012-02-09 11:58:13477 SOUTH ROSEMARY AVENUE - SUITE #318
 PERMIT #12020021
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: **THIS PLAN IS BEING REVIEWED AS A CHANGE OF
 OCCUPANCY FROM RESIDENTIAL TO BUSINESS OCCUPANCY.
  
 PROVISO - SUBMIT REVISED PLANS
  
 SHEET M1.1 - DUCTWORK IS PASSING THROUGH A FIRE-RATED
 WALL FROM SUITE 316 TO SUITE 318. PROVIDE FIRE DAMPERS.
  
 FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE/SMOKE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 THE RESIDENTIAL STYLE FIRE SPRINKLERS WILL NEED TO BE
 REPLACED WITH COMMERCIAL STYLE SPRINKLERS. SPRINKLERS
 WILL NEED TO ADDED TO ANY SMALL CLOSETS AND RESTROOMS
 PER NFPA 13.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-07 Cont ID  
Sent By wjolin Date 2012-02-07 Time 12:28 Rev Time 0.00
Received By wjolin Date 2012-02-07 Time 12:28 Sent To Z
Notes
2012-02-07 12:28:28477 SOUTH ROSEMARY AVENUE - SUITE #318
 PERMIT #12020021
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 CONFIRM THE OCCUPANCY OF THIS SPACE WILL BE EDUCATIONAL
 AND NOT BUSINESS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 FIRE ALARM NOTIFICATION APPLIANCES WILL BE NEEDED IN
 THE CLASSROOM AND HC RESTROOM.
  
 THE RESIDENTIAL STYLE FIRE SPRINKLERS WILL NEED TO BE
 REPLACED WITH COMMERCIAL STYLE SPRINKLERS. SPRINKLERS
 WILL NEED TO ADDED TO ANY SMALL CLOSETS AND RESTROOMS
 PER NFPA 13.
  
 INDICATE IF THE EXISTING COOKING APPLIANCES WILL BE
 USED OR REMOVED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-02-09 Time   Rev Time 0.00
Received By lmartine Date 2012-02-08 Time 16:02 Sent To  
Notes
2012-02-08 16:03:13EXPEDITED
 2ND RUN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-08 Cont ID  
Sent By lmartine Date 2012-02-08 Time 16:01 Rev Time 0.00
Received By lmartine Date 2012-02-01 Time 17:02 Sent To  
Notes
2012-02-01 17:03:05EXPEDITED
 B--6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By rregueir Date 2012-02-09 Time 14:59 Rev Time 0.00
Received By rregueir Date 2012-02-09 Time 14:59 Sent To  
Notes
2012-02-09 14:59:21***PROVISO***
  
 1. PLAN CLAIMS EXTERIOR WINDOW OPENINGS OF 40 SQ. FT.
 FOR NATURAL VENTILATION. THE SIZE OF THE OPENABLE
 WINDOW AREA SHALL BE VERIFIED IN THE FIELD. FBC-M
 SECTION 402.
  
 2. TWO NEW 14X10 DUCTS ARE SHOWN PENETRATING AN
 EXISTING TENANT SEPARATION WALL. FIRE DAMPERS ARE
 REQUIRED AT THESE PENETRATIONS PER FBC-M 607.5.3 AND
 SHALL BE SHOWN ON THE PLANS PER FBC-M 607.8. REVISION
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-02-06 Cont ID  
Sent By hmoser Date 2012-02-06 Time 13:17 Rev Time 0.00
Received By hmoser Date 2012-02-06 Time 13:16 Sent To  
Notes
2012-02-06 13:22:00PLANS DENIED
 1) PROVIDE CAN OR GRILL SIZE ON THE PLANS.
 2) CHANGE OF OCCUPANCY REQUIRED.
 3) REMOVE STOVE OR SEPARATE PERMITS WILL BE REQUIRED
 FOR
 HOOD AND FIRE SUPPRESSION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By lwagner Date 2012-02-09 Time 11:10 Rev Time 0.00
Received By lwagner Date 2012-02-09 Time 11:08 Sent To  
Notes
2012-02-09 11:10:38***PROVISO***
 1. CAP OFF DRAIN AND WATER LINES FOR CONCEALED TUB.
  
 2. DEPENDING UPON THE 20 % OF THE COST OF THE
 ALTERATIONS OVER AND ABOVE THE CONTRACT VALUE NEED TO
 GO TO ACCESSIBILITY TO BRING THE BUILDING( UNIT) INTO
 CODE COMPLIANCE WITH THE ACCESSIBILITY CODE, THE
 KITCHEN SINK TOP MAY NEED TO BE LOWERED TO 34" ABOVE
 FINISHED FLOOR.
  
 NOTE
 1. THE REQUIRED DRINKING FOUNTAIN IS LOCATED IN
 HALLWAY.

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-07 Cont ID  
Sent By lwagner Date 2012-02-07 Time 10:20 Rev Time 0.00
Received By lwagner Date 2012-02-07 Time 10:18 Sent To  
Notes
2012-02-07 10:20:10FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. A DRINKING FOUNTAIN WILL BE REQUIRED PER 403.1
 MINIMUM NUMBER OF FIXTURES. SEE TABLE 403.1 FOR FIXTURE
 REQUIREMENTS FOR TYPES OF OCCUPANCIES.
  
 2. DEPENDING UPON THE 20 % OF THE COST OF THE
 ALTERATIONS OVER AND ABOVE THE CONTRACT VALUE NEED TO
 GO TO ACCESSIBILITY TO BRING THE BUILDING( UNIT) INTO
 CODE COMPLIANCE WITH THE ACCESSIBILITY CODE, THE
 KITCHEN SINK TOP MAY NEED TO BE LOWERED TO 34" ABOVE
 FINISHED FLOOR.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop Z ZONING
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By eschneid Date 2012-02-09 Time 08:37 Rev Time 0.25
Received By eschneid Date 2012-02-09 Time 08:36 Sent To  
Notes
2012-02-09 08:37:26PASSED W/PROVISO
  
 THE UNITS MAY NOT BE USED AS CLASSROOMS UNTIL SUCH TIME
 AS THE CITY COMMISSION APPROVES THE AMENDMENT TO THE
 CITYPLACE DRI TO ALLOW EDUCATIONAL USE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-02-08 Cont ID  
Sent By lmartine Date 2012-02-08 Time 16:02 Rev Time 0.00
Received By lmartine Date 2012-02-08 Time 16:01 Sent To  
Notes
2012-02-08 16:02:34SEE ERIC'S COMMENTS ON #120120020