Plan Review Details - Permit 12010607
Plan Review Stops For Permit 12010607
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-29 Cont ID  
Sent By shill Date 2012-02-29 Time 09:34 Rev Time 0.00
Received By shill Date 2012-02-29 Time 09:34 Sent To  
Notes
2012-02-29 09:34:53PROVISO - DOOR NOT TO ENCROACH INTO THE PUBLIC ROW WHEN
 IN THE OPEN POSITION FBC 3202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-01 Cont ID  
Sent By shill Date 2012-02-01 Time 11:21 Rev Time 0.00
Received By shill Date 2012-02-01 Time 11:21 Sent To  
Notes
2012-02-01 11:24:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. A DOOR IS TO BE REPLACED WITH A FIXED WINDOW.
 PROVIDE A LIFE SAFETY PLAN SHOWING HOW EXITING IS
 AFFECTED. THIS SHOULD INCLUDE OCCUPANCY CLASSIFICATION,
 OCCUPANT LOAD, ROOM DESIGNATIONS, TRAVEL DISTANCE, ETC.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-02-29 Cont ID  
Sent By wjolin Date 2012-02-29 Time 10:35 Rev Time 0.00
Received By wjolin Date 2012-02-29 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-03 Cont ID  
Sent By wjolin Date 2012-02-03 Time 11:44 Rev Time 0.00
Received By wjolin Date 2012-02-03 Time 11:40 Sent To Z
Notes
2012-02-03 11:44:36417 25TH STREET
 PERMIT #12010607
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 IF AN EXIT DOOR IS BEING REPLACED WITH A WINDOW, A
 FLOOR PLAN NEEDS TO BE SUBMITTED INDICATING THE LIFE
 SAFETY FEATURES OF THE BUILDING (EXIT DOORS, EXIT
 SIGNS, DEAD-ENDS ETC.).
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-29 Cont ID  
Sent By shill Date 2012-02-29 Time 11:10 Rev Time  
Received By lmartine Date 2012-01-31 Time 16:43 Sent To  
Notes
2012-02-01 11:25:112/1/12 TO FIRE
2012-01-31 16:43:45SH DESK
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-02-29 Cont ID  
Sent By astelly Date 2012-02-29 Time 10:47 Rev Time 0.00
Received By astelly Date 2012-02-29 Time 10:47 Sent To  
Notes
2012-02-29 10:57:23AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W/ PROVISO
  
 PILASTER BASES CANNOT ENCROACH MORE THAN 4" BEYOND THE
 PROPERTY LINE IN ACCORDANCE WITH THE1949 BUILDING PER
 SEC. 4601(4)(E).
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-02-08 Cont ID  
Sent By astelly Date 2012-02-08 Time 16:14 Rev Time 0.00
Received By astelly Date 2012-02-08 Time 16:14 Sent To  
Notes
2012-02-08 16:20:51AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE SUBMIT A SURVEY SHOWING THE SIZE AND LOCATION OF
 THE PILASTER BASES.
 DOORS MAY NOT SWING INTO THE RIGHT-OF-WAY. IF THE
 FACADE OF THE BUILDING IS ON THE PROPERTY LINE, A NICHE
 WILL HAVE TO BE CREATED IN ORDER TO CONTAIN THE SWING
 WITHIN THE LIMITS OF THE PROPERTY.
 YOUR SUBMISSION MAY GENERATE ADDITIONAL COMMENTS.
  