Plan Review Details - Permit 12010550
Plan Review Stops For Permit 12010550
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-21 Cont ID  
Sent By rmcdouga Date 2012-03-21 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2012-03-20 Time 15:43 Sent To  
Notes
2012-03-21 09:07:55PROVIDE PRODUCT APPROVALS FOR GLASS BLOCK TO FIELD
 INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-16 Cont ID  
Sent By rmcdouga Date 2012-02-16 Time 13:23 Rev Time 0.00
Received By rmcdouga Date 2012-02-15 Time 13:44 Sent To  
Notes
2012-02-15 16:53:162007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND
 THE PLANS SPECIFY CATEGORY B. PLEASE CORRECT. FBCR
 301.2.1.4.3
  
 2) REVISE THE PRESSURES IN THE WINDOW AND DOOR SCHEDULE
 ON A-2 TO CONFORM WITH EXPOSURE C. FBCR 301.2.1
  
 3) SHOW COMPLIANCE WITH FBCR 320 FOR TERMITE PROTECTION
 ON THE PLANS.
  
 4) PROVIDE A WINDOW BUCK FASTENING DETAIL IN COMPLIANCE
 WITH FBC R613.6.
  
 5) THE SECTION DETAIL FOR SECTION 61 ON S1 IS NOT
 PROVIDED. PLEASE CORRECT. CITY AMENDMENTS 106.1.1
  
 6) THE FOOTING FOR THE MASONRY WALL AT THE EXPANDED
 COVERED PATIO IS INCORRECTLY LABELED AS F1 ON SHEET
 S-1. IT SHOULD BE FOOTER F-3. PLEASE CORRECT. FBC
 R403.1.1
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 106.3.3
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS AND THE ROOFING MATERIAL AS
 REQUIRED BY DCA RULE 9N-3.
  
 9) THE TRANSOM WINDOW LABELED #001 AND THE PICTURE
 WINDOW LABELED #016 ARE LARGER THAN THE MAXIMUM SIZE
 ALLOWED BY THE FIXED GLASS PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE FIXED WINDOWS. PLEASE SUBMIT THE
 APPROPRIATE PRODUCT APPROVALS AS REQUIRED BY DCA RULE
 9N-3. IF THESE ARE SMALLER WINDOWS THAT ARE MULLED
 TOGETHER PLEASE PROVIDE THIS INFORMATION ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-21 Cont ID  
Sent By rmcdouga Date 2012-03-21 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2012-03-21 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-01-31 Cont ID  
Sent By rlecky Date 2012-01-31 Time 12:20 Rev Time 0.00
Received By rlecky Date 2012-01-31 Time 10:28 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2012-03-20 Cont ID  
Sent By rmcdouga Date 2012-03-20 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2012-03-20 Time 13:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2012-02-15 Cont ID  
Sent By rmcdouga Date 2012-02-15 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2012-02-15 Time 11:43 Sent To  
Notes
2012-02-15 12:02:472007 FBC W/2009 REVISIONS
  
 GAS REVIEW DENIED
  
 1) THE PLANS APPEAR TO SHOW A LARGER GAS STOVE AND
 RELOCATED DRYER THAT COULD BE GAS. IN ORDER TO
 DETERMINE THAT THE GAS SUPPLY SYSTEM IS ADEQUATE,
 PLEASE SUBMIT TWO SETS OF A GAS ISOMETRIC RISER DIAGRAM
 FOR THE PROJECT. SPECIFY THE PIPE MATERIAL, SIZE AND
 LENGTHS, THE REQUIRED BTUS OF EACH APPLIANCE, THE TYPE
 OF GAS (LP OR NATURAL), THE SYSTEM PRESSURE, SPECIFY
 THE TOTAL DISTANCE FROM THE POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND THE SIZING TABLE
 THAT WAS USED TO DESIGN THE SYSTEM. FBC CHAPTER 24.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-21 Cont ID  
Sent By rmcdouga Date 2012-03-21 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2012-03-14 Time 13:18 Sent To  
Notes
2012-03-16 13:18:51GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-08 Cont ID  
Sent By shill Date 2012-03-08 Time 13:24 Rev Time 0.00
Received By shill Date 2012-01-26 Time 12:32 Sent To  
Notes
2012-01-26 12:32:33INCOMING SENT TO R-1. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-03-20 Cont ID  
Sent By rmcdouga Date 2012-03-20 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2012-03-20 Time 15:34 Sent To  
Notes
2012-03-20 15:35:38PLANS STAMPED BY COUNTY / NO IMPACT FEES DUE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-02-15 Cont ID  
Sent By rmcdouga Date 2012-02-15 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2012-02-15 Time 13:42 Sent To  
Notes
2012-02-15 13:43:52DUE TO THE ADDITION OF LIVING SPACE, AN IMPACT FEE
 REVIEW BY PALM BEACH COUNTY WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-03-20 Cont ID  
Sent By rmcdouga Date 2012-03-20 Time 15:35 Rev Time 0.00
Received By rmcdouga Date 2012-03-20 Time 15:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-02-15 Cont ID  
Sent By rmcdouga Date 2012-02-15 Time 13:42 Rev Time 0.00
Received By rmcdouga Date 2012-02-15 Time 12:05 Sent To  
Notes
2012-02-15 13:41:592007 FBC W/2009 REVISIONS
  
 MECHANICAL REVIEW DENIED
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS FOR THE PROJECT.
 SHOW DUCT LAYOUT AND DROP LOCATIONS, SPECIFY DUCT
 SIZES, SPECIFY GRILL SIZES AND CFMS. SHOW RETURN
 LOCATIONS AND SIZES. CITY AMENDMENTS 106.3.5.4
  
 2) PROVIDE AN EQUIPMENT SCHEDULE WITH THE MODEL NUMBERS
 ON THE PLANS. AMENDMENTS 106.3.5.4
  
 3) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 4) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY 2007 FBC ENERGY GLITCH AMENDMENTS SECTION N1100.
  
 5) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-03-20 Cont ID  
Sent By rmcdouga Date 2012-03-20 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2012-03-20 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-15 Cont ID  
Sent By rmcdouga Date 2012-02-15 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2012-02-15 Time 10:43 Sent To  
Notes
2012-02-15 11:43:362007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF DWV ISOMETRIC RISER DIAGRAM
 DRAWINGS FOR THE PROJECT. CITY AMENDMENTS 106.3.5.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2012-03-08 Cont ID  
Sent By lfranco Date 2012-03-08 Time 13:26 Rev Time 0.00
Received By shill Date 2012-03-08 Time 13:27 Sent To  
Notes
2012-03-08 13:26:27OK PER AV (SEE SIGNATURE ON PLAN)
  