| Plan Review Stops For Permit 12010550 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-03-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-21 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-20 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2012-03-21 09:07:55 | PROVIDE PRODUCT APPROVALS FOR GLASS BLOCK TO FIELD | | | INSPECTOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-02-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-16 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-15 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2012-02-15 16:53:16 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND | | | THE PLANS SPECIFY CATEGORY B. PLEASE CORRECT. FBCR | | | 301.2.1.4.3 | | | | | | 2) REVISE THE PRESSURES IN THE WINDOW AND DOOR SCHEDULE | | | ON A-2 TO CONFORM WITH EXPOSURE C. FBCR 301.2.1 | | | | | | 3) SHOW COMPLIANCE WITH FBCR 320 FOR TERMITE PROTECTION | | | ON THE PLANS. | | | | | | 4) PROVIDE A WINDOW BUCK FASTENING DETAIL IN COMPLIANCE | | | WITH FBC R613.6. | | | | | | 5) THE SECTION DETAIL FOR SECTION 61 ON S1 IS NOT | | | PROVIDED. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 | | | | | | 6) THE FOOTING FOR THE MASONRY WALL AT THE EXPANDED | | | COVERED PATIO IS INCORRECTLY LABELED AS F1 ON SHEET | | | S-1. IT SHOULD BE FOOTER F-3. PLEASE CORRECT. FBC | | | R403.1.1 | | | | | | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | | AMENDMENTS 106.3.3 | | | | | | 8) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL MULLIONS AND THE ROOFING MATERIAL AS | | | REQUIRED BY DCA RULE 9N-3. | | | | | | 9) THE TRANSOM WINDOW LABELED #001 AND THE PICTURE | | | WINDOW LABELED #016 ARE LARGER THAN THE MAXIMUM SIZE | | | ALLOWED BY THE FIXED GLASS PRODUCT APPROVAL THAT WAS | | | SUBMITTED FOR THE FIXED WINDOWS. PLEASE SUBMIT THE | | | APPROPRIATE PRODUCT APPROVALS AS REQUIRED BY DCA RULE | | | 9N-3. IF THESE ARE SMALLER WINDOWS THAT ARE MULLED | | | TOGETHER PLEASE PROVIDE THIS INFORMATION ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-03-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-21 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-21 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-01-31 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-01-31 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-01-31 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2012-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-20 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-20 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2012-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-15 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-15 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2012-02-15 12:02:47 | 2007 FBC W/2009 REVISIONS | | | | | | GAS REVIEW DENIED | | | | | | 1) THE PLANS APPEAR TO SHOW A LARGER GAS STOVE AND | | | RELOCATED DRYER THAT COULD BE GAS. IN ORDER TO | | | DETERMINE THAT THE GAS SUPPLY SYSTEM IS ADEQUATE, | | | PLEASE SUBMIT TWO SETS OF A GAS ISOMETRIC RISER DIAGRAM | | | FOR THE PROJECT. SPECIFY THE PIPE MATERIAL, SIZE AND | | | LENGTHS, THE REQUIRED BTUS OF EACH APPLIANCE, THE TYPE | | | OF GAS (LP OR NATURAL), THE SYSTEM PRESSURE, SPECIFY | | | THE TOTAL DISTANCE FROM THE POINT OF DELIVERY TO THE | | | MOST REMOTE OUTLET IN THE BUILDING AND THE SIZING TABLE | | | THAT WAS USED TO DESIGN THE SYSTEM. FBC CHAPTER 24. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-03-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-21 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-14 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2012-03-16 13:18:51 | GAVE TO ROBBIE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-03-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-03-08 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-01-26 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2012-01-26 12:32:33 | INCOMING SENT TO R-1. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2012-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-20 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-20 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2012-03-20 15:35:38 | PLANS STAMPED BY COUNTY / NO IMPACT FEES DUE |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-15 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-15 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2012-02-15 13:43:52 | DUE TO THE ADDITION OF LIVING SPACE, AN IMPACT FEE | | | REVIEW BY PALM BEACH COUNTY WILL BE REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2012-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-20 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-20 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-15 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-15 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2012-02-15 13:41:59 | 2007 FBC W/2009 REVISIONS | | | | | | MECHANICAL REVIEW DENIED | | | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS FOR THE PROJECT. | | | SHOW DUCT LAYOUT AND DROP LOCATIONS, SPECIFY DUCT | | | SIZES, SPECIFY GRILL SIZES AND CFMS. SHOW RETURN | | | LOCATIONS AND SIZES. CITY AMENDMENTS 106.3.5.4 | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE WITH THE MODEL NUMBERS | | | ON THE PLANS. AMENDMENTS 106.3.5.4 | | | | | | 3) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR. | | | | | | 4) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY 2007 FBC ENERGY GLITCH AMENDMENTS SECTION N1100. | | | | | | 5) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-03-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-20 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-20 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-15 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-15 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2012-02-15 11:43:36 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO SETS OF DWV ISOMETRIC RISER DIAGRAM | | | DRAWINGS FOR THE PROJECT. CITY AMENDMENTS 106.3.5.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2012-03-08 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2012-03-08 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-03-08 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2012-03-08 13:26:27 | OK PER AV (SEE SIGNATURE ON PLAN) | | | |
|
|