Plan Review Details - Permit 12010484
Plan Review Stops For Permit 12010484
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-06-11 Cont ID  
Sent By shill Date 2012-06-11 Time 10:22 Rev Time 0.00
Received By shill Date 2012-06-11 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-05-01 Cont ID  
Sent By shill Date 2012-05-01 Time 08:56 Rev Time 0.00
Received By shill Date 2012-05-01 Time 08:56 Sent To  
Notes
2012-05-01 09:04:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 IMPROVEMENT. WIND DESIGN CRITERIA, ALONG WITH SIGNATURE
 AND SEAL (IF APPLICABLE) FOR INDIDUAL LICENSED TO
 DESIGN THIS SCOPE OF WORK, FS471, 481, 489.
  
 2ND REVIEW - COMMENT NOT ADDRESSED COMPLETELY. A DETAIL
 WAS PROVIDED BUT WIND DESIGN CRITERIA (MINIMUM OF
 140MPH EXPOSURE C), DESIGNER INFORMATION NOT ON PLAN.
  
 3RD REVIEW - PLAN DOES NOT INCLUDE THE WIND DESIGN
 CRITERIA, WALL INSULATION DOES NOT MEET MINIMUMS
 REQUIRED BY ENERGY CALCS. THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE PLAN IS TO PROVIDE NAME AND
 SIGNATURE.
  
 2-4. OK.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR, FAC9N-3.
  
 2ND REVIEW, PRODUCT APPROVAL SUBMITTED IS EXPIRED.
 PROVIDE CURRENT PRODUCT APPROVAL FOR SLIDING GLASS DOOR
 AND FOR THE SHUTTERS.
  
 3RD REVIEW, PRODUCT APPROVAL SUBMITTED IS FOR WALL
 PANELS/SIDING. PROVIDE THE PRODUCT APPROVAL FOR THE
 SLIDING GLASS DOOR, FAC9N-3.
  
 6. OK.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-22 Cont ID  
Sent By shill Date 2012-02-22 Time 15:35 Rev Time 0.00
Received By shill Date 2012-02-22 Time 15:35 Sent To  
Notes
2012-02-22 16:01:28****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 IMPROVEMENT. WIND DESIGN CRITERIA, ALONG WITH SIGNATURE
 AND SEAL (IF APPLICABLE) FOR INDIDUAL LICENSED TO
 DESIGN THIS SCOPE OF WORK, FS471, 481, 489.
  
 2ND REVIEW - COMMENT NOT ADDRESSED COMPLETELY. A DETAIL
 WAS PROVIDED BUT WIND DESIGN CRITERIA, DESIGNER
 INFORMATION NOT ON PLAN.
  
 2. OK.
  
 3. A LIVING ROOM IS PROPOSED, BUT NO INFORMATION
 PROVIDED REGARDING DRYWALL INSTALLATION, PLEASE CLARIFY
 SCOPE.
  
 2ND REVIEW, NOTE SAYS NO DRYWALL. NO INSULATION EITHER?
 HOW WILL THIS PROPOSED IMPROVEMENT COMPLY WITH THE
 ENERGY CODE FBC CHAPTER 13? PLEASE REVISE PLAN TO
 INCLUDE INSULATION AS REQUIRED.
  
 4. ENERGY CALCS REQUIRED, FBC 13-103.
  
 2ND REVIEW, SEE FBC 13-600, IT DOES NOT APPEAR THAT
 THIS ADDITION WOULD BE EXEMPT. PLEASE SUBMIT ENERGY
 CALCS AND REVISE PLAN TO SHOW APPLICABLE DETAILS.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR, FAC9N-3.
  
 2ND REVIEW, PRODUCT APPROVAL SUBMITTED IS EXPIRED.
 PROVIDE CURRENT PRODUCT APPROVAL FOR SLIDING GLASS DOOR
 AND FOR THE SHUTTERS.
  
 6. OK.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-06 Cont ID  
Sent By shill Date 2012-02-06 Time 10:43 Rev Time 0.00
Received By shill Date 2012-02-06 Time 10:43 Sent To  
Notes
2012-02-06 10:46:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 IMPROVEMENT. WIND DESIGN CRITERIA, ALONG WITH SIGNATURE
 AND SEAL (IF APPLICABLE) FOR INDIDUAL LICENSED TO
 DESIGN THIS SCOPE OF WORK, FS471, 481, 489.
  
 2. IMPACT FEE ASSESSMENT REQUIRED BY PALM BEACH COUNTY,
 233-5025 FOR MORE INFORMATION.
  
 3. A LIVING ROOM IS PROPOSED, BUT NO INFORMATION
 PROVIDED REGARDING DRYWALL INSTALLATION, PLEASE CLARIFY
 SCOPE.
  
 4. ENERGY CALCS REQUIRED, FBC 13-103.
  
 5. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE SLIDING GLASS DOOR, FAC9N-3.
  
 6. MINIMUM PLAN REVIEW CRITERIA, PROVIDE ELEVATION OF
 EXISTING, PROPOSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-15 Cont ID  
Sent By rlecky Date 2012-02-15 Time 09:52 Rev Time 0.00
Received By rlecky Date 2012-02-15 Time 09:03 Sent To  
Notes
2012-02-15 10:06:19ADD RECEPTACLES, SWITCH AND LIGHT AS NOTED ON PLAN. NEC
 210.52
  
  
 ROBERT LECKY
 ELECTRIC PLAN REVIEWER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-02 Cont ID  
Sent By rlecky Date 2012-02-02 Time 12:05 Rev Time 0.00
Received By rlecky Date 2012-02-02 Time 12:03 Sent To B
Notes
2012-02-02 12:05:03PLEASE PROVIDE AN ELECTRICAL PLAN SHOWING COMPLIANCE
 WITH THE REQUIREMENTS OF THE CODE FOR RECEPTACLES,
 LIGHTING, GFCIS, AFCIS, SMOKE ALARMS, CARBON MONOXIDE
 DETECTORS, LOCATION OF THE ELECTRICAL PANEL AND
 SERVICE, ETC. NEC 215.5
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-06-11 Cont ID  
Sent By shill Date 2012-06-11 Time 10:22 Rev Time 0.00
Received By shill Date 2012-05-24 Time 10:46 Sent To  
Notes
2012-05-29 10:48:13INCOMING SENT TO S HILL DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-05-01 Cont ID  
Sent By shill Date 2012-05-01 Time 09:04 Rev Time 0.00
Received By shill Date 2012-04-25 Time 14:52 Sent To  
Notes
2012-04-25 14:52:47TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-22 Cont ID  
Sent By shill Date 2012-02-22 Time 16:01 Rev Time 0.00
Received By shill Date 2012-02-15 Time 07:38 Sent To  
Notes
2012-02-15 07:39:15SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-06 Cont ID  
Sent By shill Date 2012-02-06 Time 10:46 Rev Time 0.00
Received By shill Date 2012-01-24 Time 08:25 Sent To  
Notes
2012-02-02 12:26:50SENT TO BUILDING <5K
2012-01-25 08:25:53INCOMING SENT TO ZONING BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-05-01 Cont ID  
Sent By shill Date 2012-05-01 Time 09:06 Rev Time 0.00
Received By shill Date 2012-05-01 Time 09:05 Sent To  
Notes
2012-05-01 09:06:20MU 12-2071
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-02-07 Cont ID  
Sent By shill Date 2012-02-07 Time 14:50 Rev Time 0.00
Received By shill Date 2012-02-07 Time 14:50 Sent To  
Notes
2012-02-07 14:50:57IMPACT FEE ASSESSMENT REQUIRED, 233-5025 FOR MORE
 INFORMATION.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-02-01 Cont ID  
Sent By ajones Date 2012-02-01 Time 16:37 Rev Time 0.00
Received By ajones Date 2012-02-01 Time 16:37 Sent To E
Notes
***NONE***