| 2012-01-26 09:00:20 | BUILDING PLAN REVIEW |
| | PERMIT: 12010446 |
| | ADD: 2013 PONCE DE LEON AVE |
| | CONT: GLOBAL LINK SYSTEMS |
| | TEL: (954)448-8847 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COVER SHEET : |
| | |
| | 1A) THE PLANS INDICATE THEY ARE IN COMPLIANCE WITH THE |
| | STANDARD BUILDING CODE. THE STANDARD BUILDING CODE HAS |
| | NOT BEEN EXISTANCE SINCE THE 2001 FBC-B WAS ADOPTED. |
| | CURRENTLY THE 2007/09 FBC-B IS THE ADOPTED STATE-WIDE |
| | CODE. THE 2007/09 EXISTING BUILDING CODE FOR |
| | ALTERATIONS TO BUILDINGS THAT HAVE BEEN ALREADY CO'ED |
| | FOR ALTERATIONS AND CHANGE OF OCCUPANCY. |
| | |
| | 1B) THE SECOND ISSUE WITH THE COVER SHEET IS THE |
| | MINIMUM BUILDING TYPE VI. WHEN THE 2001 FBC-B WAS |
| | ADOPTED THE BUILDING TYPE VI IS NO LONGER IN EXISTANCE. |
| | THE 2004 FBC-B CODE COMMENTARY HAS CONSTRUCTION TYPE |
| | COMPARISION FIGURE 600, UNDER THE SBC BUILDING TYPE VI |
| | IS A TYPE VB UNDER THE 2004 FBC-B. THE 2007/09 FBC-B |
| | STILL LIST THE MINIMIUM BUILDING YPE AS TYPE VB. |
| | |
| | 1C) THE COVERSHEET ALSSO INDICATES TTHE TOTAL SQ FT OF |
| | THE BUILDING AS 5,987 SQ FT THE TOTAL OCCUPANT LOAD |
| | SHOULD BE 60 NOT 59 AS TAKEN IN UNDER THE OCCUPANT |
| | LOAD. |
| | 2007/09 FBC-B TABLE 1004.1.1. |
| | |
| | 2) SHEET A-2 THE RIGHT SIDE OF THE PAGE INDICATES 8 OF |
| | 15 WORK STATIONS THAT CREATE POSSIBLY A DEAD END |
| | CORRIDOR OVER 20'-0" LONG IF THE EXISTING OFFICE # 2 |
| | DOOR IS LOCKED. |
| | FBC-B 1017.3. |
| | |
| | 3) PLEASE REVIEW SHEET A4 THE REFLECTED CEILING PLAN, |
| | A5 LIFE SAFETY PLAN VERSES SHEET E2 FOR EXIT SIGNS AND |
| | EMERGENCY LIGHTS WITH BATTERY BACK-UP. THERE SEEMS TO |
| | BE A DICREPANCY IN THE PLANS. A4 & A5 APPEAR TO BE |
| | MISSING FIXTURES. 2007/09 FBC-B 1006.2 & 1006.3. |
| | |
| | 4) NEITHER SHEET A2 OR A5 PROVIDE INFORMATION AS TO |
| | COMPLIANCE OF FBC-B 906.1 LOCATION OF PORTABLE FIRE |
| | EXTINGUISHERS, A2 LEGEND DOES NOT EVEN HAVE A SYMBLE |
| | FOR FIRE EXTINGUISHERS. |
| | |
| | 5) SHEET A3 DETAIL TYP EXTERIOR WALL SECTION INDICATES |
| | INSTALL NEW R-19 INSULATION OVER EXISTING DECKING AS |
| | REQUIRED. THE CONFUSION IS NO ROOFING PERMIT IS PULLED |
| | FOR APPLYING INSULATION OVER THE ROOF DECK, THE PLANS |
| | SHOW A CROSS HATCHING UNDER THE DECK AS IF THIS |
| | INSULATION WOULD BE HUNG, THESE A RE BAR JOIST |
| | DEPICTED, HOW WILL THE INSULATION BE INSTALLED. 106.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) SHEET A3 ALSO INDICATES A DETAIL (K) OF A BREAK ROOM |
| | SINK THE DETAIL INDICATES A 34" HIGH TOP AND ACCESSIBLE |
| | SINK BUT FAILS TO PROVIDE COMPLIANCE FOR A FORWARD |
| | APPROACH AND CLEAR FLOOR SPACE.PLEASE SEE 2007/09 FBC-B |
| | 11-24. 1-7. |
| | |
| | 7) SHEET A3 DETAIL (K) DOES NOT INDICATE AT WHAT HEIGHT |
| | THE DRINKING FOUNTAIN HEIGHT (SPOUT) WILL BE INSTALLED |
| | . 2007/09 FBC-B 11-4.15.2. |
| | |
| | 8) THE PERMIT APPLICATION INDICATES THE VALUE OF THIS |
| | PROJECT TO BE $78,000 DOLLARS FBC-B11-4.1.6(2) |
| | (1)(2)(A) DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE |
| | EVENT OF DISPROPORTIONALITY. $78,000 X .20%= $ |
| | 15,600.00 IN UPGRADES TO BRING THE BUILDING IN |
| | CONFORMANCE TO CURRENT ACCESSIBILITY STANDARDS. THE |
| | MONIES ARE TO BE SPENT IN THIS ORDER: |
| | (I) AN ACCESSIBLE ENTRANCE, ENTRANCE AND EXTERIOR |
| | EGRESS NOT SHOWN STAIRS, RAMPS ETC? |
| | (II) AN ACCESSIBLE ROUTE TO ALTERED AREAS |
| | (III) AT LEAST ON ACCESSIBLE RESTROOM FOR EACH SEX OR A |
| | SINGLE UNISEX RESTROOM |
| | (IV) AN ACCESSIBLE TELEPHONE |
| | (V) ACCESSIBLE DRINKING FOUNTAIN |
| | (VI) PARKING STORAGE AND ALARMS |
| | PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE FOR |
| | THE LISTED ABOVE ACCESSIBILITY ITEMS AND DOLLAR AMOUNT |
| | SPENT. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |