Plan Review Details - Permit 12010446
Plan Review Stops For Permit 12010446
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-03-08 Cont ID  
Sent By jwitmer Date 2012-03-08 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2012-03-08 Time 16:13 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-27 Cont ID  
Sent By jwitmer Date 2012-02-23 Time 10:08 Rev Time 0.00
Received By jwitmer Date 2012-02-23 Time 09:30 Sent To  
Notes
2012-02-23 10:10:02BUILDING WILL STAMP PLANS ONCE ALL TRADES ARE PASSED.
 IT APPEARS THERE ARE STILL ISSUES WITH PLUMBING AND THE
 AMOUNT OF FIXTURES REQUIRED.
  
 FIRE HAS PULLED AN OLD PERMIT FROM FILE NET OUR RECORD
 RETENSION FILES THAT INDICATES THE LARGE AREA IN THE
 CENTER OF THE BUILDING WITH NO DETAIL IS AN EXISTING
 LAB. PLEASE
 PROVIDE DETAIL FOR THIS AREA, INCLUDE CHEMICALS TO BE
 STORED, AMOUNT OF CHEMICALS THAT ARE STORED, AND IN
 WHAT TYPE OF PROTECTION THEY ARE STORED, RATED
 CABINETS?
 THIS TYPE OF INFORMATION IS VITAL TO SEE IF THE EGRESS
 PATH FROM THE PROPOSED OFFICE SPACE THROUGH TO THE REAR
 EXIT IS STILL VIABLE?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-26 Cont ID  
Sent By jwitmer Date 2012-01-26 Time 09:00 Rev Time 1.50
Received By jwitmer Date 2012-01-25 Time 16:06 Sent To  
Notes
2012-01-26 09:00:20BUILDING PLAN REVIEW
 PERMIT: 12010446
 ADD: 2013 PONCE DE LEON AVE
 CONT: GLOBAL LINK SYSTEMS
 TEL: (954)448-8847
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COVER SHEET :
  
 1A) THE PLANS INDICATE THEY ARE IN COMPLIANCE WITH THE
 STANDARD BUILDING CODE. THE STANDARD BUILDING CODE HAS
 NOT BEEN EXISTANCE SINCE THE 2001 FBC-B WAS ADOPTED.
 CURRENTLY THE 2007/09 FBC-B IS THE ADOPTED STATE-WIDE
 CODE. THE 2007/09 EXISTING BUILDING CODE FOR
 ALTERATIONS TO BUILDINGS THAT HAVE BEEN ALREADY CO'ED
 FOR ALTERATIONS AND CHANGE OF OCCUPANCY.
  
 1B) THE SECOND ISSUE WITH THE COVER SHEET IS THE
 MINIMUM BUILDING TYPE VI. WHEN THE 2001 FBC-B WAS
 ADOPTED THE BUILDING TYPE VI IS NO LONGER IN EXISTANCE.
 THE 2004 FBC-B CODE COMMENTARY HAS CONSTRUCTION TYPE
 COMPARISION FIGURE 600, UNDER THE SBC BUILDING TYPE VI
 IS A TYPE VB UNDER THE 2004 FBC-B. THE 2007/09 FBC-B
 STILL LIST THE MINIMIUM BUILDING YPE AS TYPE VB.
  
 1C) THE COVERSHEET ALSSO INDICATES TTHE TOTAL SQ FT OF
 THE BUILDING AS 5,987 SQ FT THE TOTAL OCCUPANT LOAD
 SHOULD BE 60 NOT 59 AS TAKEN IN UNDER THE OCCUPANT
 LOAD.
 2007/09 FBC-B TABLE 1004.1.1.
  
 2) SHEET A-2 THE RIGHT SIDE OF THE PAGE INDICATES 8 OF
 15 WORK STATIONS THAT CREATE POSSIBLY A DEAD END
 CORRIDOR OVER 20'-0" LONG IF THE EXISTING OFFICE # 2
 DOOR IS LOCKED.
 FBC-B 1017.3.
  
 3) PLEASE REVIEW SHEET A4 THE REFLECTED CEILING PLAN,
 A5 LIFE SAFETY PLAN VERSES SHEET E2 FOR EXIT SIGNS AND
 EMERGENCY LIGHTS WITH BATTERY BACK-UP. THERE SEEMS TO
 BE A DICREPANCY IN THE PLANS. A4 & A5 APPEAR TO BE
 MISSING FIXTURES. 2007/09 FBC-B 1006.2 & 1006.3.
  
 4) NEITHER SHEET A2 OR A5 PROVIDE INFORMATION AS TO
 COMPLIANCE OF FBC-B 906.1 LOCATION OF PORTABLE FIRE
 EXTINGUISHERS, A2 LEGEND DOES NOT EVEN HAVE A SYMBLE
 FOR FIRE EXTINGUISHERS.
  
 5) SHEET A3 DETAIL TYP EXTERIOR WALL SECTION INDICATES
 INSTALL NEW R-19 INSULATION OVER EXISTING DECKING AS
 REQUIRED. THE CONFUSION IS NO ROOFING PERMIT IS PULLED
 FOR APPLYING INSULATION OVER THE ROOF DECK, THE PLANS
 SHOW A CROSS HATCHING UNDER THE DECK AS IF THIS
 INSULATION WOULD BE HUNG, THESE A RE BAR JOIST
 DEPICTED, HOW WILL THE INSULATION BE INSTALLED. 106.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A3 ALSO INDICATES A DETAIL (K) OF A BREAK ROOM
 SINK THE DETAIL INDICATES A 34" HIGH TOP AND ACCESSIBLE
 SINK BUT FAILS TO PROVIDE COMPLIANCE FOR A FORWARD
 APPROACH AND CLEAR FLOOR SPACE.PLEASE SEE 2007/09 FBC-B
 11-24. 1-7.
  
 7) SHEET A3 DETAIL (K) DOES NOT INDICATE AT WHAT HEIGHT
 THE DRINKING FOUNTAIN HEIGHT (SPOUT) WILL BE INSTALLED
 . 2007/09 FBC-B 11-4.15.2.
  
 8) THE PERMIT APPLICATION INDICATES THE VALUE OF THIS
 PROJECT TO BE $78,000 DOLLARS FBC-B11-4.1.6(2)
 (1)(2)(A) DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE
 EVENT OF DISPROPORTIONALITY. $78,000 X .20%= $
 15,600.00 IN UPGRADES TO BRING THE BUILDING IN
 CONFORMANCE TO CURRENT ACCESSIBILITY STANDARDS. THE
 MONIES ARE TO BE SPENT IN THIS ORDER:
 (I) AN ACCESSIBLE ENTRANCE, ENTRANCE AND EXTERIOR
 EGRESS NOT SHOWN STAIRS, RAMPS ETC?
 (II) AN ACCESSIBLE ROUTE TO ALTERED AREAS
 (III) AT LEAST ON ACCESSIBLE RESTROOM FOR EACH SEX OR A
 SINGLE UNISEX RESTROOM
 (IV) AN ACCESSIBLE TELEPHONE
 (V) ACCESSIBLE DRINKING FOUNTAIN
 (VI) PARKING STORAGE AND ALARMS
 PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE FOR
 THE LISTED ABOVE ACCESSIBILITY ITEMS AND DOLLAR AMOUNT
 SPENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-22 Cont ID  
Sent By rlecky Date 2012-02-22 Time 16:58 Rev Time 0.00
Received By rlecky Date 2012-02-22 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-25 Cont ID  
Sent By rlecky Date 2012-01-25 Time 17:47 Rev Time 0.00
Received By rlecky Date 2012-01-25 Time 17:31 Sent To  
Notes
2012-01-25 17:48:331201446
 2013 PONCE DE LEON AVENUE
 INTERIOR RENOVATION
  
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
  
 A SEPARATE PERMIT WITH PLANS WILL BE REQUIRED FOR VOICE
 AND DATA CIRCUITS
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-03-09 Cont ID  
Sent By wjolin Date 2012-03-09 Time 09:58 Rev Time 0.00
Received By wjolin Date 2012-03-09 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-02-24 Cont ID  
Sent By wjolin Date 2012-02-24 Time 12:19 Rev Time 0.00
Received By wjolin Date 2012-02-23 Time 12:32 Sent To B
Notes
2012-02-24 12:19:452013 PONCE DE LEON AVENUE
 PERMIT #12010446
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE LABORATORY CLASS (CLASS A, B, C OR D) PER
 NFPA 45 - FIRE PROTECTION FOR LABORATORIES USING
 CHEMICALS.
  
 PER NFPA 45, LABORATORY SPACES SHALL BE SEPARATED FROM
 NON-LABORATORY SPACES WITH A 1-HOUR FIRE RATING.
  
 THE EGRESS AND LIFE SAFETY REQUIREMENTS FOR
 NON-INSTRUCTIONAL LAB UNITS SHALL COMPLY WITH
 INDUSTRIAL OCCUPANCIES (CHAPTER 40) OF NFPA 101.
  
 INDICATE THE PRESENCE AND QUANTITIES OF ANY HAZARDOUS
 CHEMICALS, FLAMMABLE LIQUIDS, FLAMMABLE GASES, ETC.
  
 PROVIDE A LAYOUT OF THE LABORATORY EQUIPMENT (FUME
 HOODS, REFRIGERATORS, SPECIMEN STORAGE, CHEMICAL
 STORAGE, ETC).
  
 ENTRANCES TO LABORATORY UNITS, LABORATORY WORK AREAS
 AND STORAGE AREAS SHALL BE IDENTIFIED BY SIGNS TO WARN
 EMERGENCY RESPONSE PERSONNEL OF UNUSUAL OR SEVERE
 HAZARDS THAT ARE NOT DIRECTLY RELATED TO THE FIRE
 HAZARD OF CONTENTS.
  
 EXHAUST SYSTEMS USED FOR THE REMOVAL OF HAZARDOUS
 MATERIALS SHALL BE IDENTIFIED TO WARN PERSONNEL OF THE
 POSSIBLE HAZARDS.
  
 LABEL CONTAINERS AND CONTENT, INCLUDING PRECAUTIONARY
 INFORMATION, SHALL BE PROVIDED DIRECTLY ON ALL ORIGINAL
 AND SUBSEQUENT CONTAINERS OF HAZARDOUS CHEMICALS,
 EXCEPT THOSE BEING USED IN ONGOING EXPERIMENTS.
  
 EACH REFRIGERATOR, FREEZER, OR COOLER SHALL BE
 PROMINENTLY MARKED TO INDICATE WHETHER OR NOT IT MEETS
 THE REQUIREMENTS FOR SAFE STORAGE OF FLAMMABLE LIQUIDS.
  
 REFRIGERATORS, FREEZERS, AND OTHER COOLING EQUIPMENT
 USED TO STORE OR COOL FLAMMABLE LIQUIDS SHALL BE
 DESIGNED FOR SUCH USE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-01-27 Cont ID  
Sent By wjolin Date 2012-01-27 Time 11:33 Rev Time 0.00
Received By wjolin Date 2012-01-27 Time 11:03 Sent To  
Notes
2012-01-27 11:33:512013 PONCE DE LEON AVENUE
 PERMIT #12010446
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 DUCT SMOKE DETECTORS AND REMOTE TEST STATION ARE NEEDED
 FOR MECHANICAL AIRFLOWS GREATER THAN 2000 CFM.
  
 INDICATE THE USE OF THE LARGE SPACE CONTAINING THE
 EXISTING SAFETY SHOWER.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-09 Cont ID  
Sent By wjolin Date 2012-03-09 Time 09:58 Rev Time 0.00
Received By wjolin Date 2012-03-08 Time 13:30 Sent To  
Notes
2012-03-08 13:30:42INCOMING SENT TO JW DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-28 Cont ID  
Sent By hmoser Date 2012-02-28 Time 14:59 Rev Time 0.00
Received By hmoser Date 2012-02-16 Time 16:56 Sent To  
Notes
2012-02-16 16:56:50EXPEDITED

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-30 Cont ID  
Sent By hmoser Date 2012-01-30 Time 10:03 Rev Time 0.00
Received By hmoser Date 2012-01-20 Time 16:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-28 Cont ID  
Sent By hmoser Date 2012-02-28 Time 14:58 Rev Time 0.00
Received By hmoser Date 2012-02-28 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-30 Cont ID  
Sent By hmoser Date 2012-01-30 Time 10:02 Rev Time 0.00
Received By hmoser Date 2012-01-30 Time 09:00 Sent To  
Notes
2012-01-30 10:02:48PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3 2007
 FBC (M)
 2) PROVIDE A DETAIL ON THE PLANS BY THE ENGINEER ON THE
 CURB
 TO ROOF TIEDOWN AND UNIT TO CURB TIEDOWN PER SECTION
 301.12
 WIND RESISTANCE 2007 FBC (M) .
 3) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER
 CONTROLS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-27 Cont ID  
Sent By lwagner Date 2012-02-27 Time 13:23 Rev Time 0.00
Received By lwagner Date 2012-02-21 Time 11:15 Sent To  
Notes
2012-02-21 11:16:26OK WITH APPROVAL OF LETTER ON OCCUPANT LOAD

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-27 Cont ID  
Sent By lwagner Date 2012-01-27 Time 09:51 Rev Time 0.00
Received By lwagner Date 2012-01-26 Time 13:07 Sent To  
Notes
2012-01-27 09:51:14FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE REMOVAL OF THE PLUMBING FIXTURES AS SHOWN ON
 SHEET A-1 WOULD BRING THE FIXTURE COUNT BELOW THAT
 REQUIRED FOR AN OCCUPANT LOAD OF 60 AND OCCUPANCY TYPE
 OF BUSINESS.
 403.1 MINIMUM NUMBER OF FIXTURES. PLUMBING FIXTURES
 SHALL BE PROVIDED FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE 403.1. TYPES OF
 OCCUPANCIES NOT SHOWN IN TABLE 403.1 SHALL BE
 CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL. THE
 NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING. OCCUPANCY CLASSIFICATION SHALL
 BE DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 403.3 NUMBER OF OCCUPANTS OF EACH SEX. THE REQUIRED
 WATER CLOSETS, LAVATORIES, AND SHOWERS OR BATHTUBS
 SHALL BE DISTRIBUTED EQUALLY BETWEEN THE SEXES BASED ON
 THE PERCENTAGE OF EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD. THE OCCUPANT LOAD SHALL BE COMPOSED OF 50 PERCENT
 OF EACH SEX, UNLESS STATISTICAL DATA APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT DISTRIBUTION OF THE
 SEXES (SEE ALSO SECTION 403.1.1).
 2 RESTROOMS FOR WOMEN AND 2 RESTROOMS FOR MEN WILL BE
 REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-02-03 Cont ID  
Sent By lfranco Date 2012-02-03 Time 10:35 Rev Time 0.00
Received By lmartine Date 2012-02-03 Time 10:33 Sent To  
Notes
***NONE***