Plan Review Details - Permit 12010375
Plan Review Stops For Permit 12010375
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-06 Cont ID  
Sent By hmoser Date 2012-02-06 Time 11:01 Rev Time 0.00
Received By hmoser Date 2012-02-02 Time 16:52 Sent To  
Notes
2012-02-03 16:52:32SENT TO HAROLD'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By hmoser Date 2012-01-24 Time 11:50 Rev Time 0.00
Received By hmoser Date 2012-01-18 Time 15:16 Sent To  
Notes
2012-01-18 15:15:57TO MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-06 Cont ID  
Sent By hmoser Date 2012-02-06 Time 11:01 Rev Time 0.00
Received By hmoser Date 2012-02-06 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-24 Cont ID  
Sent By hmoser Date 2012-01-24 Time 11:45 Rev Time 0.00
Received By hmoser Date 2012-01-24 Time 10:55 Sent To  
Notes
2012-01-24 11:50:16PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 2007 FBC (M)
 2) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER
 CONTROLS 2007 ENERGY CODE.
 3) PROVIDE DUCT SIZE ON ALL DUCT WORK.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]