Plan Review Details - Permit 12010285
Plan Review Stops For Permit 12010285
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-15 Cont ID  
Sent By hmoser Date 2012-02-15 Time 14:24 Rev Time 0.00
Received By hmoser Date 2012-02-07 Time 08:51 Sent To  
Notes
2012-02-07 08:52:10INCOMING SENT TO MECHANICAL BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By hmoser Date 2012-01-24 Time 13:19 Rev Time 0.00
Received By hmoser Date 2012-01-17 Time 13:38 Sent To  
Notes
2012-01-17 13:38:26INCOMING SENT TO MECHANICAL BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-15 Cont ID  
Sent By hmoser Date 2012-02-15 Time 14:24 Rev Time 0.00
Received By hmoser Date 2012-02-15 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-24 Cont ID  
Sent By hmoser Date 2012-01-24 Time 13:19 Rev Time 0.00
Received By hmoser Date 2012-01-24 Time 13:12 Sent To  
Notes
2012-01-24 13:19:38PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 2007 FBC (M) .
 2) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER
 CONTROL 2007 ENERGY CODE.
 3) PROVIDE A DETAIL FROM A ENGINEER ON CONDENSER TO
 SLAB TIE DOWN.
 PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]