Plan Review Details - Permit 12010283
Plan Review Stops For Permit 12010283
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2013-06-20 Cont ID  
Sent By rmcdouga Date 2013-06-20 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2013-06-18 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2013-02-01 Cont ID  
Sent By rmcdouga Date 2013-02-01 Time 08:42 Rev Time 0.00
Received By rmcdouga Date 2013-02-01 Time 08:42 Sent To  
Notes
2013-02-01 08:56:362007 FBC W/2009 REVISIONS
 CHANGE OF OCCUPANCY
  
 DENIED BY BUILDING
  
 I AM IN RECEIPT OF THE LETTER FROM GABRIEL GOSLINE AND
 THE RESPONSES FROM JOHN AVERKAMP. I AGREE THAT THE
 GARAGE CAN BE CONVERTED INTO AN APARTMENT AS LONG AS IT
 MEETS THE REQUIREMENTS OF THE BUILDING CODE. THE GARAGE
 WAS APPARENTLY CONVERTED INTO AN APARTMENT WITHOUT THE
 PROPER PERMITS AND INSPECTIONS SOMETIME IN THE PAST.
 SINCE THE CONVERSION WAS DONE WITHOUT THE PROPER
 PERMITS AND INSPECTIONS, THERE ARE TWO OPTIONS. IT CAN
 BE CONVERTED BACK TO A GARAGE OR IT CAN BE PERMITTED AS
 A CHANGE OF OCCUPANCY FROM A GARAGE TO AN APARTMENT.
 THE DETACHED GARAGE IS A GROUP U OCCUPANCY AND THE
 APARTMENT IS A GROUP R-3 OCCUPANCY. IF YOU WISH TO HAVE
 THE APARTMENT, THEN THE FOLLOWING COMMENTS WILL NEED TO
 BE ADDRESSED.
  
 1) THIS STRUCTURE WAS ORIGINALLY CONSTRUCTED AS A
 GARAGE. THERE IS NO EVIDENCE THAT THIS STRUCTURE WAS
 LEGALLY CONVERTED TO AN APARTMENT AS INDICATED ON THE
 PLANS. UNLESS YOU CAN PROVIDE PROOF THAT THE CHANGE
 FROM GARAGE TO APARTMENT WAS PREVIOUSLY PERMITTED,
 INSPECTED AND APPROVED BY THE BUILDING DEPARTMENT, THIS
 WILL BE CONSIDERED A CHANGE OF OCCUPANCY FROM AN
 EXISTING GARAGE TO A RESIDENCE. FBC EXISTING BUILDING
 SECTION 406.
  
 2) FBC EXISTING BUILDING SECTION 907.2 WIND LOADS,
 REQUIRES STRUCTURES SUBJECT TO A CHANGE OF OCCUPANCY
 WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY RESULTS IN
 HIGHER WIND IMPORTANCE FACTORS BASED ON THE FLORIDA
 BUILDING CODE, BUILDING TABLE 1604.5, SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND LOAD
 PROVISIONS OF THE FBC. PROVIDE TWO SETS OF A SIGNED AND
 SEALED WIND LOAD ANALYSIS OF THE STRUCTURE.
  
 3) COMPLIED.
  
 4) PROVIDE TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE EXISTING STRUCTURE AND THE DISTANCE TO PROPERTY
 LINES AND OTHER STRUCTURES LOCATED ON THE SAME PARCEL.
 FBC R302
  
 5) THE PLANS WILL BE REQUIRED TO BE TAKEN TO PALM BEACH
 COUNTY FOR AN IMPACT FEE REVIEW.
  
 PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH
 REVIEW COMMENT WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2012-10-05 Cont ID  
Sent By rmcdouga Date 2012-10-05 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2012-10-05 Time 13:29 Sent To  
Notes
2012-10-05 15:59:452007 FBC W/2009 REVISIONS
 CHANGE OF OCCUPANCY
  
 DENIED BY BUILDING
  
 I AM IN RECEIPT OF THE LETTER FROM GABRIEL GOSLINE AND
 THE RESPONSES FROM JOHN AVERKAMP. I AGREE THAT THE
 GARAGE CAN BE CONVERTED INTO AN APARTMENT AS LONG AS IT
 MEETS THE REQUIREMENTS OF THE BUILDING CODE. THE GARAGE
 WAS APPARENTLY CONVERTED INTO AN APARTMENT WITHOUT THE
 PROPER PERMITS AND INSPECTIONS SOMETIME IN THE PAST.
 SINCE THE CONVERSION WAS DONE WITHOUT THE PROPER
 PERMITS AND INSPECTIONS, THERE ARE TWO OPTIONS. IT CAN
 BE CONVERTED BACK TO A GARAGE OR IT CAN BE PERMITTED AS
 A CHANGE OF OCCUPANCY FROM A GARAGE TO AN APARTMENT.
 THE DETACHED GARAGE IS A GROUP U OCCUPANCY AND THE
 APARTMENT IS A GROUP R-3 OCCUPANCY. IF YOU WISH TO HAVE
 THE APARTMENT, THEN THE FOLLOWING COMMENTS WILL NEED TO
 BE ADDRESSED.
  
 1) THIS STRUCTURE WAS ORIGINALLY CONSTRUCTED AS A
 GARAGE. THERE IS NO EVIDENCE THAT THIS STRUCTURE WAS
 LEGALLY CONVERTED TO AN APARTMENT AS INDICATED ON THE
 PLANS. UNLESS YOU CAN PROVIDE PROOF THAT THE CHANGE
 FROM GARAGE TO APARTMENT WAS PREVIOUSLY PERMITTED,
 INSPECTED AND APPROVED BY THE BUILDING DEPARTMENT, THIS
 WILL BE CONSIDERED A CHANGE OF OCCUPANCY FROM AN
 EXISTING GARAGE TO A RESIDENCE. FBC EXISTING BUILDING
 SECTION 406.
  
 2) FBC EXISTING BUILDING SECTION 907.2 WIND LOADS,
 REQUIRES STRUCTURES SUBJECT TO A CHANGE OF OCCUPANCY
 WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY RESULTS IN
 HIGHER WIND IMPORTANCE FACTORS BASED ON THE FLORIDA
 BUILDING CODE, BUILDING TABLE 1604.5, SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND LOAD
 PROVISIONS OF THE FBC. PROVIDE TWO SETS OF A SIGNED AND
 SEALED WIND LOAD ANALYSIS OF THE STRUCTURE.
  
 3) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY THE 2007 FBC ENERGY GLITCH AMENDMENTS SECTION
 N1100.0.7 FOR THE PROPOSED APARTMENT.
  
 4) PROVIDE TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE EXISTING STRUCTURE AND THE DISTANCE TO PROPERTY
 LINES AND OTHER STRUCTURES LOCATED ON THE SAME PARCEL.
 FBC R302
  
 5) THE PLANS WILL BE REQUIRED TO BE TAKEN TO PALM BEACH
 COUNTY FOR AN IMPACT FEE REVIEW.
  
 PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW EACH
 REVIEW COMMENT WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-04-30 Cont ID  
Sent By rmcdouga Date 2012-04-30 Time 16:15 Rev Time 0.00
Received By rmcdouga Date 2012-04-30 Time 16:15 Sent To Z
Notes
2012-04-30 15:44:56COMMENTS FROM FIRST TWO REVIEWS HAVE NOT BEEN
 ADDRESSED. PLEASE RESPOND TO COMMENTS.
  
 2007 FBC W/2009 REVISIONS
 CHANGE OF OCCUPANCY
  
 DENIED BY BUILDING
  
 1) THE DESCRIPTION OF WORK ON THE APPLICATION IS TO
 RENEW EXTERIOR ONLY AND LISTS THE VALUE OF THE WORK AS
 $2000.00. THE PLANS THAT WERE SUBMITTED SHOW A COMPLETE
 REMODEL WITH A BATHROOM AND KITCHEN. THE PERMIT VALUE
 FOR THE AMOUNT OF WORK SHOWN ON THE PLANS IS MUCH MORE
 THAN $2000.00. CITY AMENDMENTS 108.3. PLEASE CLARIFY.
  
 2) THIS STRUCTURE WAS ORIGINALLY CONSTRUCTED AS A
 GARAGE. THERE IS NO EVIDENCE THAT THIS STRUCTURE WAS
 LEGALLY CONVERTED TO AN APARTMENT AS INDICATED ON THE
 PLANS. UNLESS YOU CAN PROVIDE PROOF THAT THE CHANGE
 FROM GARAGE TO APARTMENT WAS PREVIOUSLY PERMITTED,
 INSPECTED AND APPROVED BY THE BUILDING DEPARTMENT, THIS
 WILL BE CONSIDERED A CHANGE OF OCCUPANCY FROM AN
 EXISTING GARAGE TO A RESIDENCE. FBC EXISTING BUILDING
 SECTION 406.
  
 3) CITY AMENDMENTS 108.3 FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, ARCHITECTURAL
 AND DESIGN FEES, OVERHEAD AND PROFIT. PLEASE ADJUST
 VALUE TO REFLECT SCOPE OF WORK.
  
 4) FBC EXISTING BUILDING SECTION 907.2 WIND LOADS,
 REQUIRES STRUCTURES SUBJECT TO A CHANGE OF OCCUPANCY
 WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY RESULTS IN
 HIGHER WIND IMPORTANCE FACTORS BASED ON THE FLORIDA
 BUILDING CODE, BUILDING TABLE 1604.5, SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND LOAD
 PROVISIONS OF THE FBC. PROVIDE TWO SETS OF A SIGNED AND
 SEALED WIND LOAD ANALYSIS OF THE STRUCTURE.
  
 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY THE 2007 FBC ENERGY GLITCH AMENDMENTS SECTION
 N1100.0.7 FOR THE PROPOSED APARTMENT.
  
 6) THE NEW BATHROOM IS REQUIRED TO HAVE A DOOR THAT HAS
 A 29 INCH CLEAR OPENING PER FBC 11-4.22.2.
  
 7) PROVIDE TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE EXISTING STRUCTURE AND THE DISTANCE TO PROPERTY
 LINES AND OTHER STRUCTURES LOCATED ON THE SAME PARCEL.
 FBC R302
  
 8) SHOW COMPLIANCE WITH FBC R303.3 FOR REQUIRED
 BATHROOM MECHANICAL VENTILATION.
  
 9) SHOW COMPLIANCE WITH FBC R303.8 FOR REQUIRED HEATING
 FACILITIES.
  
 10) FBC R703.6.3 WHICH REQUIRES A BOND BREAK BETWEEN
 THE WATER RESISTIVE BARRIER AND THE STUCCO ON THE
 EXTERIOR WALLS.
  
 11) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. FBC R301.2.1.2
  
 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR NEW
 EXTERIOR FRENCH DOORS, STORM PANELS, TRUSS ANCHORS,
 STRAPS AND CONNECTORS AS REQUIRED BY DCA RULE 9N-3.
 (THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 FRENCH DOORS AND SINGLE HUNG WINDOWS DO NOT HAVE
 COMPLETE DRAWINGS. PLEASE SHRINK THE DRAWINGS TO FIT ON
 THE 8.5" X 11" PAPER.)
  
 13) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD PER CITY AMENDMENTS
 106.3.3.
  
 14) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW
 EACH REVIEW COMMENT WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 11:12 Sent To  
Notes
2012-03-29 11:14:00DENIED BY BUILDING
  
 1) THE COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-08 Cont ID  
Sent By rmcdouga Date 2012-02-08 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2012-02-08 Time 06:38 Sent To  
Notes
2012-02-08 08:11:302007 FBC W/2009 REVISIONS
 CHANGE OF OCCUPANCY
  
 DENIED BY BUILDING
  
 1) THE DESCRIPTION OF WORK ON THE APPLICATION IS TO
 RENEW EXTERIOR ONLY AND LISTS THE VALUE OF THE WORK AS
 $2000.00. THE PLANS THAT WERE SUBMITTED SHOW A COMPLETE
 REMODEL WITH A BATHROOM AND KITCHEN. THE PERMIT VALUE
 FOR THE AMOUNT OF WORK SHOWN ON THE PLANS IS MUCH MORE
 THAN $2000.00. CITY AMENDMENTS 108.3. PLEASE CLARIFY.
  
 2) THIS STRUCTURE WAS ORIGINALLY CONSTRUCTED AS A
 GARAGE. THERE IS NO EVIDENCE THAT THIS STRUCTURE WAS
 LEGALLY CONVERTED TO AN APARTMENT AS INDICATED ON THE
 PLANS. UNLESS YOU CAN PROVIDE PROOF THAT THE CHANGE
 FROM GARAGE TO APARTMENT WAS PREVIOUSLY PERMITTED,
 INSPECTED AND APPROVED BY THE BUILDING DEPARTMENT, THIS
 WILL BE CONSIDERED A CHANGE OF OCCUPANCY FROM AN
 EXISTING GARAGE TO A RESIDENCE. FBC EXISTING BUILDING
 SECTION 406.
  
 3) CITY AMENDMENTS 108.3 FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, ARCHITECTURAL
 AND DESIGN FEES, OVERHEAD AND PROFIT. PLEASE ADJUST
 VALUE TO REFLECT SCOPE OF WORK.
  
 4) FBC EXISTING BUILDING SECTION 907.2 WIND LOADS,
 REQUIRES STRUCTURES SUBJECT TO A CHANGE OF OCCUPANCY
 WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY RESULTS IN
 HIGHER WIND IMPORTANCE FACTORS BASED ON THE FLORIDA
 BUILDING CODE, BUILDING TABLE 1604.5, SHALL BE ANALYZED
 AND SHALL COMPLY WITH THE APPLICABLE WIND LOAD
 PROVISIONS OF THE FBC. PROVIDE TWO SETS OF A SIGNED AND
 SEALED WIND LOAD ANALYSIS OF THE STRUCTURE.
  
 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY THE 2007 FBC ENERGY GLITCH AMENDMENTS SECTION
 N1100.0.7 FOR THE PROPOSED APARTMENT.
  
 6) THE NEW BATHROOM IS REQUIRED TO HAVE A DOOR THAT HAS
 A 29 INCH CLEAR OPENING PER FBC 11-4.22.2.
  
 7) PROVIDE TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE EXISTING STRUCTURE AND THE DISTANCE TO PROPERTY
 LINES AND OTHER STRUCTURES LOCATED ON THE SAME PARCEL.
 FBC R302
  
 8) SHOW COMPLIANCE WITH FBC R303.3 FOR REQUIRED
 BATHROOM MECHANICAL VENTILATION.
  
 9) SHOW COMPLIANCE WITH FBC R303.8 FOR REQUIRED HEATING
 FACILITIES.
  
 10) FBC R703.6.3 WHICH REQUIRES A BOND BREAK BETWEEN
 THE WATER RESISTIVE BARRIER AND THE STUCCO ON THE
 EXTERIOR WALLS.
  
 11) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. FBC R301.2.1.2
  
 12) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR NEW
 EXTERIOR FRENCH DOORS, STORM PANELS, TRUSS ANCHORS,
 STRAPS AND CONNECTORS AS REQUIRED BY DCA RULE 9N-3.
  
 13) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD PER CITY AMENDMENTS
 106.3.3.
  
 14) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW
 EACH REVIEW COMMENT WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-06-18 Cont ID  
Sent By rmcdouga Date 2013-06-18 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2013-06-18 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By rlecky Date 2012-03-27 Time 14:34 Rev Time 0.00
Received By rlecky Date 2012-03-27 Time 14:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-30 Cont ID  
Sent By rlecky Date 2012-01-30 Time 15:32 Rev Time 0.00
Received By rlecky Date 2012-01-30 Time 15:06 Sent To  
Notes
2012-01-30 16:01:1612010283
 1805 FLORIDA AVE
 INTERIOR RENOVATION OF BACK COTTAGE
  
 INDICATE LOCATION OF THE ELECTRICAL SERVICE AND MAIN
 DISCONNECT. NEC 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE I.E. KITCHEN. NEC
 210.52
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.52
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-06-19 Cont ID  
Sent By fmittner Date 2013-06-19 Time 14:42 Rev Time 0.00
Received By fmittner Date 2013-06-19 Time 14:42 Sent To B
Notes
2013-06-19 14:43:12APPROVED WITH THE CONDITION THAT THE WINDOW ON SOUTH
 ELEVATION TO BE CHANGED TO A VERTICAL ORIENTATION. FM
 LEFT MESSAGE WITH PROPERTY OWNER 6-19-13.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-01-26 Cont ID  
Sent By fmittner Date 2012-01-26 Time 14:52 Rev Time 0.00
Received By fmittner Date 2012-01-26 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2013-07-09 Cont ID  
Sent By rmcdouga Date 2013-07-09 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2013-06-07 Time 10:58 Sent To  
Notes
2013-06-10 10:58:59SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-02-01 Cont ID  
Sent By rmcdouga Date 2013-02-01 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2013-01-28 Time 08:36 Sent To  
Notes
2013-01-28 08:36:50TO RM

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-02-01 Cont ID  
Sent By rmcdouga Date 2013-02-01 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2012-09-17 Time 15:47 Sent To  
Notes
2012-09-17 15:47:47SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-05-09 Cont ID  
Sent By rmcdouga Date 2012-05-09 Time 09:34 Rev Time 0.00
Received By rmcdouga Date 2012-04-20 Time 16:34 Sent To  
Notes
2012-04-20 16:34:57RM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2012-03-16 Time 09:02 Sent To  
Notes
2012-03-19 09:03:27IN ZONING BOX, WITH #12010282

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-08 Cont ID  
Sent By rmcdouga Date 2012-02-08 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2012-01-17 Time 11:00 Sent To  
Notes
2012-01-17 11:01:04THIS APPLICATION IS RIDING WITH #12010282

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-07-09 Cont ID  
Sent By rmcdouga Date 2013-07-09 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2013-07-09 Time 15:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 11:14 Sent To  
Notes
2012-03-29 11:15:09AN IMPACT FEE REVIEW WILL BE REQUIRED BY PALM BEACH
 COUNTY.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-02-07 Cont ID  
Sent By rmcdouga Date 2012-02-07 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2012-02-07 Time 16:47 Sent To  
Notes
2012-02-07 16:49:04AN IMPACT FEE REVIEW WILL BE REQUIRED BY PALM BEACH
 COUNTY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2013-02-01 Cont ID  
Sent By rmcdouga Date 2013-02-01 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2013-02-01 Time 09:47 Sent To  
Notes
2013-02-01 09:48:39PERMIT IS NOT REQUIRED FOR A WINDOW UNIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-02-07 Cont ID  
Sent By rmcdouga Date 2012-02-07 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2012-02-07 Time 16:41 Sent To  
Notes
2012-02-07 16:47:34NO MECHANICAL PLANS SUBMITTED AND NO MECHANICAL PERMIT
 APPLIED FOR.

Review Stop P PLUMBING
Rev No 5 Status P Date 2013-06-18 Cont ID  
Sent By rmcdouga Date 2013-06-18 Time 16:58 Rev Time 0.00
Received By rmcdouga Date 2013-06-18 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2012-10-05 Cont ID  
Sent By rmcdouga Date 2012-10-05 Time 13:28 Rev Time 0.00
Received By rmcdouga Date 2012-10-05 Time 13:28 Sent To  
Notes
2012-10-05 13:29:33PLANS HAVE BEEN REDLINED TO SHOW COMPLIANCE WITH FBCR
 P3108.2.1.

Review Stop P PLUMBING
Rev No 3 Status F Date 2012-04-30 Cont ID  
Sent By rmcdouga Date 2012-04-30 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2012-04-30 Time 16:13 Sent To  
Notes
2012-04-30 16:14:43THE COMMENTS FROM THE FIRST TWO REVIEWS HAVE NOT BEEN
 ADDRESSED. SEE BELOW.
  
 2007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE BATH ROOM FIXTURES ARE NOT PROPERLY VENTED. PER
 FBCR P3108.2.1, NOT MORE THAN ONE WET-VENTED FIXTURE
 DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED
 FIXTURE DRAIN CONNECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 11:03 Sent To  
Notes
2012-03-29 11:05:17PLUMBING DENIED
  
 COMMENTS FROM THE FIRST REVIEW WERE NOT ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-07 Cont ID  
Sent By rmcdouga Date 2012-02-07 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2012-02-07 Time 16:19 Sent To  
Notes
2012-02-07 16:32:242007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE BATH ROOM FIXTURES ARE NOT PROPERLY VENTED. PER
 FBC R3108.2, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN CONNECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2013-06-19 Cont ID  
Sent By fmittner Date 2013-06-19 Time 14:44 Rev Time 0.00
Received By fmittner Date 2013-06-19 Time 14:44 Sent To  
Notes
2013-06-19 14:44:58UNIT APPROVED IN COTTAGE BECAUSE OF CONVERSION OF
 DUPLEX IN FRONT BUILDING TO SINGLE FAMILY. SAME DENSITY
 ON SITE. PER DOUG WISE/ANGELLA VANN.

Review Stop Z ZONING
Rev No 3 Status P Date 2012-05-07 Cont ID  
Sent By fmittner Date 2012-05-07 Time 15:55 Rev Time 0.00
Received By fmittner Date 2012-05-07 Time 15:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-23 Cont ID  
Sent By fmittner Date 2012-03-23 Time 11:54 Rev Time 0.00
Received By fmittner Date 2012-03-23 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-26 Cont ID  
Sent By fmittner Date 2012-01-26 Time 14:52 Rev Time 0.00
Received By fmittner Date 2012-01-26 Time 14:52 Sent To  
Notes
2012-01-26 14:52:40SUBMITTAL REQUIRES SURVEY.