| Plan Review Stops For Permit 12010282 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2012-05-17 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-05-17 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-05-17 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2012-05-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-01 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-01 |
Time |
09:26 |
Sent To |
Z |
|
| Notes |
| 2012-05-01 10:01:50 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | THE FOLLOWING ITEMS FROM THE FIRST TWO REVIEWS WERE NOT | | | ADDRESSED: | | | | | | 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. 2007 FBC ENERGY GLITCH AMENDMENTS | | | N1100.2.2 | | | | | | 2) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 THAT | | | WERE SUBMITTED FOR THE SH-600 AND SH-700 SINGLE HUNG | | | WINDOWS AND THE FD-650 FRENCH DOORS HAVE INCOMPLETE | | | INSTALLATION DRAWINGS. WHEN DOWNLOADING THEY HAVE TO BE | | | SHRUNK TO FIT ON THE 8.5 " X 11" PAPER. | | | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 106.3.3 | | | | | | 4) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT | | | PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF | | | A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN | | | INSTALLATION SCHEDULE FOR THE STORM PANELS. THE WINDOW | | | AND DOOR SCHEDULE INDICATES THAT THE FIRST FLOOR | | | WINDOWS AND FRENCH DOORS ARE NOT IMPACT RATED AND | | | REQUIRE SHUTTERS. | | | | | | 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE RESPOND | | | TO REVIEW COMMENTS IN WRITING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-29 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-29 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2012-03-29 10:53:39 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | THE FOLLOWING ITEMS FROM THE FIRST REVIEW WERE NOT | | | ADDRESSED: | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. | | | | | | 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR | | | THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT | | | AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN | | | SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT | | | APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE | | | INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN | | | DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11 | | | PAPER. | | | | | | 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT | | | PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF | | | A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN | | | INSTALLATION SCHEDULE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-02-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-14 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-07 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2012-02-10 10:07:21 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENERGY CALCULATION FORM DOES NOT CORRESPOND WITH | | | THE PLANS. THE ENERGY CALC. FORM LISTS R-20 CEILING | | | INSULATION, R-13 WALL INSULATION, R-0 SLAB FLOOR | | | INSULATION AND R-13 RAISED FLOOR INSULATION. THE TWO | | | STORY WALL SECTION ON PLAN SHEET A-5 HAS R-30 CEILING | | | INSULATION, R-11 WALL INSULATION AND NO INSULATION IN | | | THE RAISED FLOOR. PLEASE CORRECT. | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. | | | | | | 3) THE NEW FOOTINGS ARE REQUIRED TO BE TREATED FOR | | | TERMITES. SHOW COMPLIANCE WITH FBC R320. | | | | | | 4) ON THE FOUNDATION PLAN ON SHEET A-5, THE F1 FOOTER | | | FOR THE NEW BEARING WALL IS INCORRECTLY SPECIFIED AS | | | 36" X 36" X 12" W/#5 @ 8" OC. IT SHOULD BE 24" X 12" | | | CONC. FOOTER W/3 #5 BARS. PLEASE CORRECT. | | | | | | 5) ON SHEET A-6 THE ROOF NOTES LOADING FOR THE NEW | | | STRUCTURAL MEMBERS IS ILLEGIBLE. PLEASE CORRECT. CITY | | | AMENDMENTS 106.1 | | | | | | 6) ON SHEET A-6 THE ADDED STRAP DETAIL IS FOR ATTACHING | | | THE TRUSS TO A CONCRETE BEAM, HOWEVER, THIS STRUCTURE | | | IS WOOD FRAME. PLEASE CORRECT. CITY AMENDMENTS 106.1 | | | | | | 7) PROVIDE COMPLETE DETAILS FOR THE NEW FIRE PLACE AND | | | CHIMNEY SHOWN ON THE PLANS, INCLUDING STRUCTURAL | | | DRAWINGS. CITY AMENDMENTS 106.1 & FBCR M1805 | | | | | | 8) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR | | | SMOKE ALARMS AND CARBON MONOXIDE PROTECTION. | | | | | | 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR | | | THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT | | | AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN | | | SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT | | | APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE | | | INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN | | | DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11 | | | PAPER. | | | | | | 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT | | | PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF | | | A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN | | | INSTALLATION SCHEDULE. | | | | | | 12) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW | | | EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2013-02-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2013-02-20 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2013-02-20 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-03-27 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-03-27 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-03-27 |
Time |
14:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-01-30 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-01-30 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-01-30 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2012-01-30 15:00:34 | 12010182 | | | 1805 FLORIDA AVE | | | INTERIOR RENOVATION | | | | | | INDICATE LOCATION OF THE ELECTRICAL SERVICE. NEC 215.5 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | | RESISTANT. NEC 406.11 | | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | | 210.12 | | | BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND NEC 250.94 | | | KITCHEN GFCI RECEPTACLE REQUIRED AT ISLAND COUNTER TOP. | | | NEC 210.52 | | | ADDITIONAL RECEPTACLES REQUIRED FOR ANY WALL SPACE MORE | | | THAN 2 FEET IN WIDTH I.E. KITCHEN AND LIVING ROOM. NEC | | | 210.52 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-01-26 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-01-26 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-01-26 |
Time |
14:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2013-02-20 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2013-02-20 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2013-02-14 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2013-02-15 12:14:57 | UNDER 5 K ELECTRIC |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2012-05-17 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2012-05-17 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2012-05-11 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2012-05-11 12:07:00 | GAVE TO ROBBIE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-05-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-01 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-04-20 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-29 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-16 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2012-03-19 08:58:16 | IN ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-10 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-17 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2012-05-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-01 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-01 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2012-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-29 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-29 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2012-03-29 10:49:09 | MECHANICAL REVIEW DENIED | | | | | | THE PREVIOUS REVIEW COMMENTS HAVE NOT BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-02-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-08 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-08 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2012-02-09 07:14:26 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. | | | | | | 2) FBCR M1602.4 REQUIRES THROUGH THE WALL TRANSFER | | | GRILLES TO USE 50 SQUARE INCHES OF GRILL AREA TO 100 | | | CFMS FOR SIZING WITH AN UNRESTRICTED 1 INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR | | | BALANCE. THE FIRST FLOOR OFFICE HAS 292 CFMS AND ONLY | | | 100 SQUARE INCHES OF GRILL AREA. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-03-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-03-29 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-29 |
Time |
09:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-02-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-08 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-08 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2012-02-08 13:19:18 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE FIRST FLOOR BATHROOM IS NOT VENTED PROPERLY. A | | | SOIL STACK CAN NOT BE USED AS A STACK VENT. A DRY VENT | | | CONNECTION TO THE HORIZONTAL WET VENT IS REQUIRED. SEE | | | FBCR P3108.1 | | | | | | 2) ONLY THE FIXTURES WITHIN TWO BATHROOM GROUPS ON THE | | | SAME FLOOR ARE PERMITTED TO BE VENTED BY A HORIZONTAL | | | WET VENT PER FBCR P3108.1. THE PLANS SHOW THE WASHING | | | MACHINE DRY VENT BEING USED AS A HORIZONTAL WET VENT | | | FOR BATHROOM FIXTURES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-03-23 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-03-23 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-03-20 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2012-03-20 16:26:41 | GIVEN TO FM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-01-26 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-01-26 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-01-26 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2012-01-26 14:51:21 | REQUIRES SURVEY. |
|
|