Plan Review Details - Permit 12010282
Plan Review Stops For Permit 12010282
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-05-17 Cont ID  
Sent By lmartine Date 2012-05-17 Time 16:43 Rev Time 0.00
Received By lmartine Date 2012-05-17 Time 16:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2012-05-01 Time 09:26 Sent To Z
Notes
2012-05-01 10:01:502007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 THE FOLLOWING ITEMS FROM THE FIRST TWO REVIEWS WERE NOT
 ADDRESSED:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. 2007 FBC ENERGY GLITCH AMENDMENTS
 N1100.2.2
  
 2) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 THAT
 WERE SUBMITTED FOR THE SH-600 AND SH-700 SINGLE HUNG
 WINDOWS AND THE FD-650 FRENCH DOORS HAVE INCOMPLETE
 INSTALLATION DRAWINGS. WHEN DOWNLOADING THEY HAVE TO BE
 SHRUNK TO FIT ON THE 8.5 " X 11" PAPER.
  
 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 106.3.3
  
 4) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF
 A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN
 INSTALLATION SCHEDULE FOR THE STORM PANELS. THE WINDOW
 AND DOOR SCHEDULE INDICATES THAT THE FIRST FLOOR
 WINDOWS AND FRENCH DOORS ARE NOT IMPACT RATED AND
 REQUIRE SHUTTERS.
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE RESPOND
 TO REVIEW COMMENTS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 10:49 Sent To  
Notes
2012-03-29 10:53:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 THE FOLLOWING ITEMS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED:
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR
 THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT
 AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN
 SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT
 APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE
 INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN
 DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11
 PAPER.
  
 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF
 A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN
 INSTALLATION SCHEDULE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-14 Cont ID  
Sent By rmcdouga Date 2012-02-14 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2012-02-07 Time 15:36 Sent To  
Notes
2012-02-10 10:07:212007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE ENERGY CALCULATION FORM DOES NOT CORRESPOND WITH
 THE PLANS. THE ENERGY CALC. FORM LISTS R-20 CEILING
 INSULATION, R-13 WALL INSULATION, R-0 SLAB FLOOR
 INSULATION AND R-13 RAISED FLOOR INSULATION. THE TWO
 STORY WALL SECTION ON PLAN SHEET A-5 HAS R-30 CEILING
 INSULATION, R-11 WALL INSULATION AND NO INSULATION IN
 THE RAISED FLOOR. PLEASE CORRECT.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 3) THE NEW FOOTINGS ARE REQUIRED TO BE TREATED FOR
 TERMITES. SHOW COMPLIANCE WITH FBC R320.
  
 4) ON THE FOUNDATION PLAN ON SHEET A-5, THE F1 FOOTER
 FOR THE NEW BEARING WALL IS INCORRECTLY SPECIFIED AS
 36" X 36" X 12" W/#5 @ 8" OC. IT SHOULD BE 24" X 12"
 CONC. FOOTER W/3 #5 BARS. PLEASE CORRECT.
  
 5) ON SHEET A-6 THE ROOF NOTES LOADING FOR THE NEW
 STRUCTURAL MEMBERS IS ILLEGIBLE. PLEASE CORRECT. CITY
 AMENDMENTS 106.1
  
 6) ON SHEET A-6 THE ADDED STRAP DETAIL IS FOR ATTACHING
 THE TRUSS TO A CONCRETE BEAM, HOWEVER, THIS STRUCTURE
 IS WOOD FRAME. PLEASE CORRECT. CITY AMENDMENTS 106.1
  
 7) PROVIDE COMPLETE DETAILS FOR THE NEW FIRE PLACE AND
 CHIMNEY SHOWN ON THE PLANS, INCLUDING STRUCTURAL
 DRAWINGS. CITY AMENDMENTS 106.1 & FBCR M1805
  
 8) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR
 SMOKE ALARMS AND CARBON MONOXIDE PROTECTION.
  
 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR
 THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT
 AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN
 SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT
 APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE
 INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN
 DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11
 PAPER.
  
 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF
 A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN
 INSTALLATION SCHEDULE.
  
 12) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-02-20 Cont ID  
Sent By rlecky Date 2013-02-20 Time 11:26 Rev Time 0.00
Received By rlecky Date 2013-02-20 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By rlecky Date 2012-03-27 Time 14:20 Rev Time 0.00
Received By rlecky Date 2012-03-27 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-30 Cont ID  
Sent By rlecky Date 2012-01-30 Time 14:59 Rev Time 0.00
Received By rlecky Date 2012-01-30 Time 12:50 Sent To  
Notes
2012-01-30 15:00:3412010182
 1805 FLORIDA AVE
 INTERIOR RENOVATION
  
 INDICATE LOCATION OF THE ELECTRICAL SERVICE. NEC 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 KITCHEN GFCI RECEPTACLE REQUIRED AT ISLAND COUNTER TOP.
 NEC 210.52
 ADDITIONAL RECEPTACLES REQUIRED FOR ANY WALL SPACE MORE
 THAN 2 FEET IN WIDTH I.E. KITCHEN AND LIVING ROOM. NEC
 210.52
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-01-26 Cont ID  
Sent By fmittner Date 2012-01-26 Time 14:50 Rev Time 0.00
Received By fmittner Date 2012-01-26 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-02-20 Cont ID  
Sent By rlecky Date 2013-02-20 Time 11:26 Rev Time 0.00
Received By rlecky Date 2013-02-14 Time 12:14 Sent To  
Notes
2013-02-15 12:14:57UNDER 5 K ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-05-17 Cont ID  
Sent By lmartine Date 2012-05-17 Time 16:43 Rev Time 0.00
Received By lmartine Date 2012-05-11 Time 12:06 Sent To  
Notes
2012-05-11 12:07:00GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 10:02 Rev Time 0.00
Received By rmcdouga Date 2012-04-20 Time 16:39 Sent To  
Notes
2012-04-20 16:40:01RM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2012-03-16 Time 08:57 Sent To  
Notes
2012-03-19 08:58:16IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-10 Cont ID  
Sent By rmcdouga Date 2012-02-10 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2012-01-17 Time 10:58 Sent To  
Notes
2012-01-17 10:58:14R--12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-05-01 Cont ID  
Sent By rmcdouga Date 2012-05-01 Time 09:02 Rev Time 0.00
Received By rmcdouga Date 2012-05-01 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 09:56 Sent To  
Notes
2012-03-29 10:49:09MECHANICAL REVIEW DENIED
  
 THE PREVIOUS REVIEW COMMENTS HAVE NOT BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-02-08 Cont ID  
Sent By rmcdouga Date 2012-02-08 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2012-02-08 Time 15:38 Sent To  
Notes
2012-02-09 07:14:262007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 2) FBCR M1602.4 REQUIRES THROUGH THE WALL TRANSFER
 GRILLES TO USE 50 SQUARE INCHES OF GRILL AREA TO 100
 CFMS FOR SIZING WITH AN UNRESTRICTED 1 INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE. THE FIRST FLOOR OFFICE HAS 292 CFMS AND ONLY
 100 SQUARE INCHES OF GRILL AREA. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 09:04 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-08 Cont ID  
Sent By rmcdouga Date 2012-02-08 Time 11:58 Rev Time 0.00
Received By rmcdouga Date 2012-02-08 Time 11:58 Sent To  
Notes
2012-02-08 13:19:182007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE FIRST FLOOR BATHROOM IS NOT VENTED PROPERLY. A
 SOIL STACK CAN NOT BE USED AS A STACK VENT. A DRY VENT
 CONNECTION TO THE HORIZONTAL WET VENT IS REQUIRED. SEE
 FBCR P3108.1
  
 2) ONLY THE FIXTURES WITHIN TWO BATHROOM GROUPS ON THE
 SAME FLOOR ARE PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT PER FBCR P3108.1. THE PLANS SHOW THE WASHING
 MACHINE DRY VENT BEING USED AS A HORIZONTAL WET VENT
 FOR BATHROOM FIXTURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-23 Cont ID  
Sent By fmittner Date 2012-03-23 Time 11:53 Rev Time 0.00
Received By fmittner Date 2012-03-20 Time 16:26 Sent To  
Notes
2012-03-20 16:26:41GIVEN TO FM

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-26 Cont ID  
Sent By fmittner Date 2012-01-26 Time 14:50 Rev Time 0.00
Received By fmittner Date 2012-01-26 Time 14:50 Sent To  
Notes
2012-01-26 14:51:21REQUIRES SURVEY.