Plan Review Details - Permit 12010238
Plan Review Stops For Permit 12010238
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-01-19 Cont ID  
Sent By jwitmer Date 2012-01-19 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2012-01-19 Time 11:39 Sent To  
Notes
2012-01-19 14:16:27BUILDING PROVISO:
  
 1) SHEET A1.0 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS,
 FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR
 ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDENTIFICATION
 SHALL BE ABOVE ANY DECORATIVE CEILING AND IN CONCEALED
 SPACES. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS:
 "FIRE AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 2) SHEET A3.0 BREAKROOM ELEVATION C MICROWAVE/ 11-4.27
 CONTROLS AND OPERATING MECHANISMS.
 11-4.27.2 CLEAR FLOOR SPACE. CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 THAT ALLOWS A FORWARD
 OR A PARALLEL APPROACH BY A PERSON USING A WHEELCHAIR
 SHALL BE PROVIDED AT CONTROLS, DISPENSERS, RECEPTACLES
 AND OTHER OPERABLE EQUIPMENT.
  
 11-4.27.3 HEIGHT. THE HIGHEST OPERABLE PART OF
 CONTROLS, DISPENSERS, RECEPTACLES, AND OTHER OPERABLE
 EQUIPMENT SHALL BE PLACED WITHIN AT LEAST ONE OF THE
 REACH RANGES SPECIFIED IN SECTIONS 11-4.2.5 AND
 11-4.2.6. ELECTRICAL AND COMMUNICATIONS SYSTEM
 RECEPTACLES ON WALLS SHALL BE MOUNTED NO LESS THAN 15
 INCHES (380 MM) ABOVE THE FLOOR.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-01-19 Cont ID  
Sent By rlecky Date 2012-01-19 Time 16:03 Rev Time 0.00
Received By rlecky Date 2012-01-19 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-23 Cont ID  
Sent By wjolin Date 2012-01-23 Time 11:57 Rev Time 0.00
Received By wjolin Date 2012-01-23 Time 11:22 Sent To  
Notes
2012-01-23 11:57:49225 CLEMATIS STREET - SUITE #202
 PERMIT #12010238
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET FP-1 NOT SUBMITTED.
  
 PROVIDE ADDITIONAL PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 SHEET A1.0: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET FA1.01: UPDATE THE STANDARDS LIST TO REFERENCE
 THE 2007 EDITION OF NFPA 72.
  
 SHEET FA1.01: ONLY TWO HORN-TYPE NOTIFICATION
 APPLIANCES LOCATED IN TENANT SPACE; RECOMMEND CHANGING
 THE STROBE-ONLY DEVICE TO HORN-STROBE DEVICE IN BREAK
 ROOM TO HELP MEET THE MINIMUM AUDIBILITY REQUIREMENTS
 OF NFPA 72.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-07 Cont ID  
Sent By hmoser Date 2012-02-07 Time 08:35 Rev Time 0.00
Received By hmoser Date 2012-01-31 Time 13:04 Sent To  
Notes
2012-01-31 13:04:44INCOMING SENT TO MECHANICAL BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By hmoser Date 2012-01-24 Time 14:02 Rev Time 0.00
Received By hmoser Date 2012-01-12 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By hmoser Date 2012-02-07 Time 08:35 Rev Time 0.00
Received By hmoser Date 2012-02-07 Time 06:59 Sent To  
Notes
2012-02-07 08:35:32PASS PROVISO
 1) HAVE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 CONDENSER STAND AT 1ST INSPECTION.
 2 REFER TO SECTION 13-409.AB.33 SHUTOFF CONTROLS
 2007 ENERGY CODE NEED MOTORIZED DAMPER FOR FRESH AIR.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-24 Cont ID  
Sent By hmoser Date 2012-01-24 Time 14:01 Rev Time 0.00
Received By hmoser Date 2012-01-24 Time 13:29 Sent To  
Notes
2012-01-24 14:00:59PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 FBC (M) 2007
 2) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER
 CONTROLS. 2007 ENERGY CODE.
 3) PROVIDE A DETAIL ON THE MINI SPLIT CONDENSER TIE
 DOWN PER SECTION 301.12 WIND RESISTANCE
 2007 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-01-18 Cont ID  
Sent By lwagner Date 2012-01-18 Time 12:29 Rev Time 0.00
Received By lwagner Date 2012-01-18 Time 10:40 Sent To  
Notes
2012-01-18 11:05:01****PROVISO****
 314.2.1 CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING
 COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN
 OUTLET TO AN APPROVED PLACE OF
 DISPOSAL. CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR
 OTHER AREAS SO AS TO CAUSE A NUISANCE.
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-01-18 Cont ID  
Sent By aaponte Date 2012-01-18 Time 10:16 Rev Time 0.00
Received By aaponte Date 2012-01-18 Time 10:13 Sent To  
Notes
2012-01-18 10:17:16INTERIOR WORK ONLY FOR OFFICE SPACE.