Plan Review Details - Permit 12010207
Plan Review Stops For Permit 12010207
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-04-23 Cont ID  
Sent By jgomez Date 2012-04-23 Time 16:16 Rev Time 0.00
Received By jgomez Date 2012-04-23 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-07 Cont ID  
Sent By jgomez Date 2012-04-05 Time 15:22 Rev Time 0.00
Received By jgomez Date 2012-04-05 Time 15:19 Sent To  
Notes
2012-04-05 15:25:15BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- THIS PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH A
 BASE FLOOD ELEVATION OF 7'-0". SURVEY STATES HOUSE
 FINISH FLOOR 7.5' AND GARAGE 6.6'. SINCE GARAGE FLOOR
 IS BELOW 7.5', THEN FLOOD DAMAGE -RESISTANT MATERIALS
 NEED TO BE USED IN GARAGE WALLS. FLOOD VENTS WILL BE
 REQUIRED. SEE FEMA FLOOD DAMAGE-RESISTANT MATERIALS
 REQUIREMENTS AND PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH THIS REQUIREMENTS. SEC. 94-546 OF CITY FLOOD
 MANAGEMENT POLICY.
  
 2- SURVEY SUBMITTED: A) REVISE FLOOD ZONE SPECIFIED.
 BUILDING IS LOCATED ON FLOOD ZONE "A5" NOT "A6".
 B) PROVIDE SURVEYS WITH ORIGINAL SIGNATURE (NOT COPY)
 AS REQUIRED BY CHAPTER 472 FLORIDA STATUTES.
  
 3- REVISE ENERGY CALCULATIONS: PAGE 2 OF 5 SPECIFIES
 COMPOSITION SHINGLES ON THE ROOF. PLANS SHOW METAL
 ROOFING. REVISE AS REQUIRED AND OWNER/AGENT TO SIGN AND
 DATE BOTTOM OF FORM.
  
 4- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R10
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY NOTE #8 ON PAGE 2 OF 30 OF FLORIDA
 PRODUCT APPROVAL SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 14:19 Rev Time 0.00
Received By jgomez Date 2012-02-06 Time 10:16 Sent To  
Notes
2012-02-06 14:36:51RESIDENTIAL (R3) ADDITION/RENOVATION BUILDING REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- THIS PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH A
 BASE FLOOD ELEVATION OF 7'-0". NEW CONSTRUCTION NEEDS
 TO HAVE A FINISH FLOOR ELEVATION AT LEAST 6" ABOVE THE
 BASE FLOOD ELEVATION. IN ADDITION, IF THE EXISTING
 HOUSE FINISH FLOOR ELEVATION IS LESS THAN 7'-6", THEN
 THE HOUSE NEEDS TO BE RAISED TO MEET THE MINIMUM FINISH
 FLOOR ELEVATION REQUIRED BY SEC. 94-546(B)(1) OF THE
 CITY FLOOD MANAGEMENT POLICY. PLEASE PROVIDE SURVEY
 SHOWING THE EXISTING FINISH FLOOR ELEVATION.
  
 2- PLEASE BRING REVISED PLANS TO THE PALM BEACH COUNTY
 BUILDING (2300 N. JOG RD. TEL. (561)233-5120) TO VERIFY
 IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PLEASE PROVIDE ENERGY CALCULATIONS AS REQUIRED BY
 SEC. N1100.3
  
 4- PLEASE PROVIDE PRODUCT APPROVALS (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) SLIDING GLASS DOORS. NOA 09-0826.10 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA.
 B) WINDOW MULLIONS. NOA 10-0819.05 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE ALSO. PROVIDE CURRENT NOA.
 C) CONCRETE TILE AS SHOWN ON PLANS. PRODUCT APPROVAL
 FL12076-R1 SUBMITTED IS FOR METAL ROOFING.
 D) IF USING FOAM FOR CONCRETE TILE, THEN PROVIDE
 PRODUCT APPROVAL. SEE LISTED FOAM ON CONCRETE TILE
 PRODUCT APPROVAL.
 E) FLAT ROOF FOR ROOF ABOVE FLORIDA ROOM AND COVERED
 PATIO. CONCRETE TILE CAN'T BE INSTALLED ON LOW ROOF
 SLOP. SEE TILE PRODUCT APPROVAL FOR MINIMUM ROOF SLOPE.
 AND, PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. IF PRODUCT APPROVAL
 REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS, THEN,
 PROVIDE SIGNED AND SEALED CALCULATIONS.
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PLEASE PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE CONNECTOR.
 THIS APPLIES TO STRUCTURAL CONNECTORS ONLY.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL TO THIS OFFICE. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
  
 6- SHEET #1:
 A) WIND DESIGN INFORMATION: (1) CLARIFY WHY INTERNAL
 PRESSURE COEFFICIENT IS NOT APPLICABLE. (2) CLARIFY WHY
 SHEAR WALL ARE NOT REQUIRED.
 B) COMPONENTS AND CLADDING PRESSURES TABLE NEEDS TO BE
 REVISED. NEED CALCULATIONS THAT CORRESPOND TO EXPOSURE
 "C". CALCULATIONS SHOWN ARE FOR EXPOSURE "B". ENGINEER
 TO PROVIDE THE CALCULATIONS AS REQUIRED BY SEC. 106.1.2
 CITY AMENDMENTS TO FBC.
 C) DIMENSIONS SHOWN ON THE SITE PLAN ARE TOO SMALL.
 THEY ARE NOT LEGIBLE. REVISE AS REQUIRED.
 D) TYPICAL INFILL WALL SECTION: (1) NEED TO PROVIDE 2
 LAYERS OF APPROVED WATER-RESISTANT BARRIER MATERIAL AS
 REQUIRED BY SEC. R703.6.3. SPECIFY THE 2 LAYERS ON THE
 WALL SECTION. (2) WALL SECTION IS SHOWING THE STUCCO
 FINISH BELOW FINISH GRADE. THIS IS NOT ALLOWED. NEED 6"
 MIN. CLEARANCE FROM FINISH GRADE TO STUCCO. REVISE AS
 REQUIRED. SEC. R704.
  
 7- SHEET #2:
 A) WINDOWS 24SH AND 34SH SPECIFIED FOR THE BEDROOMS
 DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF SEC. R310.
 THEY DON'T PROVIDE THE MINIMUM CLEAR HEIGHT OPENING
 REQUIRED. REVISE AS REQUIRED.
 B) DOOR LEADING FROM THE GARAGE TO THE FLORIDA ROOM IS
 NOT ALLOWED. REVISE AS REQUIRED. SEC. R309.1.
  
 8- SHEET #3:
 A) PROPOSED ROOF PLAN: PROVIDE COMPLETE TRUSS ANCHOR
 SCHEDULE. SPECIFY ALL CONNECTORS FOR ROOF TRUSSES, AND
 2X ROOF JOISTS, AND FOR NEW ENTRY ROOF FRAMING MEMBERS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3.
 B) PROVIDE COMPLETE GABLE END DETAIL SHOWING COMPLIANCE
 WITH SEC. R609.4.
 C) SPECIFY ATTIC ACCESS SIZE AND LOCATION FOR NEW
 ADDITION AS REQUIRED BY SEC. R807.
  
 9- SHEET #4: TYPICAL ONE STORY WALL SECTION: STUCCO
 FINISH IS SHOWN BELOW FINISH GRADE. REVISE AS REQUIRED.
 NEED 6" MIN. CLEARANCE. SEC. R704.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-26 Cont ID  
Sent By rlecky Date 2012-03-26 Time 11:02 Rev Time 0.00
Received By rlecky Date 2012-03-26 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-01-20 Cont ID  
Sent By rlecky Date 2012-01-20 Time 11:40 Rev Time 0.00
Received By rlecky Date 2012-01-20 Time 11:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-23 Cont ID  
Sent By jgomez Date 2012-04-23 Time 16:16 Rev Time 0.00
Received By jgomez Date 2012-04-23 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-10 Cont ID  
Sent By jgomez Date 2012-04-09 Time 08:55 Rev Time 0.00
Received By jgomez Date 2012-03-19 Time 10:36 Sent To  
Notes
2012-04-10 08:55:34LAST REVIEW DONE BY ZONING ON 4/9/12. JG.
2012-03-21 10:37:27SENT TO R7 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-09 Cont ID  
Sent By ajones Date 2012-02-09 Time 16:48 Rev Time 0.00
Received By ajones Date 2012-01-11 Time 09:40 Sent To  
Notes
2012-01-13 09:40:12SENT TO SHELF R16 FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-04-06 Cont ID  
Sent By jgomez Date 2012-04-06 Time 16:54 Rev Time 0.00
Received By jgomez Date 2012-04-06 Time 16:54 Sent To  
Notes
2012-04-06 16:56:03$1093.12 PAID. TRACKING NO MU-2012-004831-0000.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 13:05 Rev Time 0.00
Received By jgomez Date 2012-02-06 Time 13:05 Sent To  
Notes
2012-02-06 13:06:45PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE. THEN, BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-04-23 Cont ID  
Sent By jgomez Date 2012-04-23 Time 17:25 Rev Time 0.00
Received By jgomez Date 2012-04-23 Time 17:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-04-07 Cont ID  
Sent By jgomez Date 2012-04-07 Time 14:08 Rev Time 0.00
Received By jgomez Date 2012-04-07 Time 13:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 14:13 Rev Time 0.00
Received By jgomez Date 2012-02-06 Time 14:12 Sent To  
Notes
2012-02-06 14:19:03RESIDENTIAL (R3) ADDITION/RENOVATION MECHANICAL REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- MECHANICAL CONTRACTOR SIGNED THE PERMIT APPLICATION,
 BUT THERE ARE NOT DRAWINGS SHOWING A/C WORK. PLEASE
 PROVIDE A/C DRAWING AND A/C EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY SEC. N1107.AB.1.
 ***NOTE: A/C CONTRACTOR MAY DRAW PLANS. PLEASE PROVIDE
 CONTRACTOR'S NAME, LICENSE NUMBER AND SIGN THE
 DRAWINGS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (5610805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 14:02 Rev Time 0.00
Received By jgomez Date 2012-02-06 Time 14:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-04-09 Cont ID  
Sent By ajones Date 2012-04-09 Time 10:40 Rev Time 0.00
Received By ajones Date 2012-04-09 Time 10:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-02-09 Cont ID  
Sent By lfranco Date 2012-02-09 Time 16:40 Rev Time 0.00
Received By ajones Date 2012-02-09 Time 16:40 Sent To  
Notes
2012-02-09 16:47:222-9-12- PRIOR TO THE ISSUANCE OF A CO, THE APPLICANT
 MUST PROVIDE PLANS THAT SHOW THAT THE PROPERTY COMPLIES
 WITH THE LANDSCAPE CODE, BECASUE THE VALUE OF THE JOB
 EXCEEDS THE VALUE OF THE HOME, ACCORDING TO RECORDS IN
 THE PROPERTY APPRAISALS OFFICE. THE REGULATIONS REQUIRE
 THE FOLLOWING:
  
 SECTION 94-442 (2)(A) REQUIRES AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE AND AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE.
  
 ANGELLA VANN
 561-822-1441
 [email protected]