Plan Review Details - Permit 12010206
Plan Review Stops For Permit 12010206
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By jgomez Date 2012-02-07 Time 10:36 Rev Time 0.00
Received By jgomez Date 2012-02-07 Time 10:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-01 Cont ID  
Sent By jgomez Date 2012-02-01 Time 13:38 Rev Time 0.00
Received By jgomez Date 2012-02-01 Time 11:14 Sent To  
Notes
2012-02-01 14:25:58RESIDENTIAL (R3) RENOVATION/ALTERATION BUILDING REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE SET OF PLANS AND SPECIFICATIONS TO
 SHOW ALL WORK TO BE PERFORMED AS SPECIFIED ON THE
 DESCRIPTION OF PROJECT SHOWN ON THE CONSTRUCTION
 AGREEMENT SUBMITTED. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 A) SHOW DEMOLITION AND REBUILDING OF WALLS.
 B) SHOW HALF CONCRETE WALL AND FRAME OUT FOR OFFICE
 AREA.
 C) SHOW ATTIC PULL DOWN STAIRS LOCATION, FRAMING
 DETAILS, ETC. AND, PROVIDE ENGINEERING SHOWING THAT
 EXISTING ROOF SYSTEM IS CAPABLE OF SUPPORTING
 ADDITIONAL LOAD (STORAGE). SHOW COMPLIANCE WITH TABLE
 R301.5 FOR ATTIC WITH STORAGE LIVE LOAD. SEE FOOTNOTES
 ALSO.
 D) SHOW DEMOLITION AND REBUILDING OF MASTER BATH.
 E0 SHOW WINDOW REPAIRS/SPECIFICATIONS.
 F) SHOW ROOF REPAIRS/SPECIFICATIONS.
  
 2- THIS PROPERTY IS LOCATED ON FLOOD ZONE A5. IF THE
 WORK EXCEEDS 50% OF THE VALUE OF THE STRUCTURE, THIS
 VALUE IS CUMULATIVE ON THE LIFE OF THE STRUCTURE. THEN,
 THE ALL HOUSE NEEDS TO COMPLY WITH THE CITY FLOOD
 MANAGEMENT POLICY. THIS IS ANOTHER REASON WHY THE PLANS
 SHOWING THE SPECIFIC WORK TO BE PERFORMED IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-01-30 Cont ID  
Sent By rlecky Date 2012-01-30 Time 10:07 Rev Time 0.00
Received By rlecky Date 2012-01-30 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-20 Cont ID  
Sent By rlecky Date 2012-01-20 Time 11:21 Rev Time 0.00
Received By rlecky Date 2012-01-20 Time 10:18 Sent To  
Notes
2012-01-20 11:21:5912010206
 122 WORTH CT. N.
 BATH REMODEL
  
 SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED.
 ADDITIONAL INFORMATION MAY BE NEEDED. PLEASE PROVIDE
 THE FOLLOWING:
  
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 PROVIDE A PANEL SCHEDULE AND SUMMARY LOAD CALCULATION.
 SHOW THE SERVICE LOCATION, FEEDER SIZE AND EXISTING
 MAIN BREAKER. INCLUDE A FLOOR PLAN SHOWING THE LOCATION
 OF ALL NEW AND EXISTING OUTLETS INCLUDING LIGHTING. NEC
 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 VERIFY THE BATHROOM RECEPTACLES ARE GFCI PROTECTED. NEC
 210.8
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.52
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-07 Cont ID  
Sent By jgomez Date 2012-02-07 Time 10:37 Rev Time 0.00
Received By jgomez Date 2012-02-07 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-01 Cont ID  
Sent By jgomez Date 2012-02-01 Time 14:30 Rev Time 0.00
Received By jgomez Date 2012-01-11 Time 09:00 Sent To  
Notes
2012-01-25 11:48:12ELECTRIC REVISION ROUTED TO RL
2012-01-13 09:00:18SENT TO R15 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By jgomez Date 2012-02-07 Time 10:36 Rev Time 0.00
Received By jgomez Date 2012-02-07 Time 10:36 Sent To  
Notes
2012-02-09 16:40:58SCOPE OF WORK NEW SHOWER AS SHOWN ON PLUMBING RISER
 DIAGRAM. JG.

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-01 Cont ID  
Sent By jgomez Date 2012-02-01 Time 14:26 Rev Time 0.00
Received By jgomez Date 2012-02-01 Time 14:26 Sent To  
Notes
2012-02-01 14:30:35RESIDENTIAL RENOVATION/ALTERATION PLUMBING REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CLARIFY IF REPLACING EXISTING PLUMBING FIXTURES OR
 IF RELOCATING AND ADDING NEW PLUMBING FIXTURES.
 INFORMATION SUBMITTED DOESN'T PROVIDE THIS
 CLARIFICATION. PROVIDE PLUMBING RISER DIAGRAM IF DOING
 OTHER THAN JUST REPLACING EXISTING PLUMBING FIXTURES.
 SEC. 106.3.5.4(9) CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status N Date 2012-01-18 Cont ID  
Sent By eschneid Date 2012-01-18 Time 18:09 Rev Time 0.25
Received By eschneid Date 2012-01-18 Time 18:09 Sent To  
Notes
2012-01-18 18:11:59WORK VALUE LESS THAN 50% OF STRUCTURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved