Plan Review Details - Permit 12010162
Plan Review Stops For Permit 12010162
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-31 Cont ID  
Sent By jgomez Date 2012-01-31 Time 08:58 Rev Time 0.00
Received By jgomez Date 2012-01-31 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-24 Cont ID  
Sent By jgomez Date 2012-01-24 Time 17:24 Rev Time 0.00
Received By jgomez Date 2012-01-24 Time 17:24 Sent To  
Notes
2012-01-24 17:37:50RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- MISSING BASIC INFORMATION. ARCHITECT TO SPECIFY ALL
 THE DESIGN CRITERIA AND CODE USED FOR THE DESIGN OF THE
 ROOF ADDITION. SPECIFY THE BUILDING CODE, WIND SPEED,
 BUILDING EXPOSURE, DESIGN PRESSURES AND DEAD AND LIVE
 LOADS AS REQUIRED BY SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING
 IS LOCATED ON EXPOSURE "C". TAKE THIS INTO
 CONSIDERATION FOR THE DESIGN OF THE ADDITION.
  
  
 2- ARCHITECT TO PROVIDE ALL HIS INFORMATION ON THE
 TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA
 STATUTES. INFORMATION WAS NOT PROVIDED ON THE PLANS
 SUBMITTED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES NOA 11-0411.02 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE WEBSITE AND
 DOWNLOAD CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON THE
 PLANS AND DETAILS. PLEASE, PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR TO
 SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC.
  
 5- ARCHITECT TO SPECIFY HOW IS THE 4X10 BEAM ATTACHED
 TO EXISTING WALL. SEC. R301.2.1.4.3.
  
 7- DETAIL B & C: ARCHITECT TO CLARIFY WHY USING 1/4" X
 4" MASONRY ANCHORS INTO EXISTING WOOD STUDS. PROVIDE
 COMPLETE ENGINEERING ANALYSIS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC.
  
 8- PROVIDE ROOF SHEATHING COMPLETE NAILING
 SPECIFICATIONS TO SHOW COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 9- OWNER/BUILDER TO APPLY FOR THE ROOFING PERMIT. OWNER
 MAY SIGN THE PERMIT APPLICATION ON THE ROOFING
 CONTRACTOR LINE TO GET THE ROOFING PERMIT.
  
 IF YOU HAVE ANY QUESTION, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-01-20 Cont ID  
Sent By fmittner Date 2012-01-20 Time 14:26 Rev Time 0.00
Received By fmittner Date 2012-01-20 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-31 Cont ID  
Sent By jgomez Date 2012-01-31 Time 08:57 Rev Time 0.00
Received By jgomez Date 2012-01-31 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By jgomez Date 2012-01-24 Time 17:38 Rev Time 0.00
Received By jgomez Date 2012-01-10 Time 16:37 Sent To  
Notes
2012-01-12 13:25:24R01
  
2012-01-10 16:38:47<5K BUILDING.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-01-20 Cont ID  
Sent By fmittner Date 2012-01-20 Time 14:26 Rev Time 0.00
Received By fmittner Date 2012-01-20 Time 14:26 Sent To  
Notes
2012-01-20 14:27:51EXTENSION OF ROOF LINE SHALL NOT PROJECT FURTHER INTO
 FRONT SETBACK THAN EXISTING LINE. QUESTIONS CONTACT
 FRIEDERIKE 822-1457.