Plan Review Details - Permit 12010122
Plan Review Stops For Permit 12010122
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-01 Cont ID  
Sent By jwitmer Date 2012-03-01 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2012-03-01 Time 13:31 Sent To  
Notes
2012-03-01 13:34:17PLEASE NOTE WINDOW PERMIT --080145 EXPIERES 3/15/2012
 WITHOUT LETTER OF EXTENSION. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-17 Cont ID  
Sent By jwitmer Date 2012-01-17 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2012-01-17 Time 09:24 Sent To  
Notes
2012-01-17 16:08:10BUILDING PLAN REVIEW
 PERMIT: 12010122
 ADD: 429 BELVEDERE RD
 CONT: C & S EXPERTISE INC.
 TEL: (561)436-5355
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION RQUIRED. THE PERMIT
 APPLICATION UNDER THE HEADING DESCRIBE PROJECT IN
 DETAIL, INDICATES DEMO OF INTERIOR CONCRETE FLOOR.
 PLEASE PROVIDE WHERE THIS CONDITION EXIST. UNDER THE
 EXPIRED PERMIT 09110339 PLAN REVIEW COMMENTS INDICATE
 THE REPLACEMENT OR REPAIR OF 2X10 FLOOR JOIST, 3X8 GLUE
 LAMS AND STEEL COLUMNS? SHEET 2.1 ALSO INDICATES
 FRAMING OF FLOOR JOIST , GLUE-LAMS AND STEEL COLUMNS,
 IS THE WORK DEPICTED PART OF THE WORK TO BE COVERED
 UNDER THIS PERMIT OR SHOULD THE WORK DEPICTED STRUCKNOT
 PART OF THIS PERMIT?
  
 2) PLANS 2.1 PROVIDE OCCUPANCY SEPERATION BETWEEN THE
 FIRST FLOOR AND SECOND FLOOR SINCE THE FIRST FLOOR IS
 CONSIDERED BUSINESS AND THE SECOND AS RESIDENTIAL.
 2007/09 FBC-B TABLE 503. PLEASE PROVIDE FIRE RATED
 ASSEMBLIES FOR THROUGH PENETRATIONS. 712.4.1.1.
  
 3) SHEET 1.1 INDICATES WIDER WINDOW OPENINGS WITH NEW
 CELL INFILL, PLANS ALSO INDICATE ALSO LOCATED ON THIS
 SHEET IS A NOTE FOR 2X BUCKS PER MANUFACTURERS
 REQUIREMENTS, NO FASTENING INFORMATION SHILE ON SHEET
 2.1 DETAIL 3 THE DETAIL INDICATES THE USE OF 1X4 PT
 BUCKS ATTACHED WITH CASE HARDENED NAILS AT 24" OC, BUT
 NO SIZE IS PROVIDED FOR THE CASE HARDENED NAIL.
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)((B) WINDOWS & MULLIONS
  
  
 6) SHEET 1.1 BATHROOM WINDOW MAY OR MAY NOT NEED TO
 MEET THE REQUIREMENTS OF 2007/09 FBC-B 2406.3

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-04-09 Cont ID  
Sent By rlecky Date 2012-04-09 Time 16:45 Rev Time 0.00
Received By rlecky Date 2012-04-09 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-02-29 Cont ID  
Sent By rlecky Date 2012-02-29 Time 13:33 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 10:11 Sent To  
Notes
2012-02-29 13:34:5412010122
 429 BELVEDERE ROAD
 RESIDENTIAL LOFT RENOVATION
  
 INDICATE SIZE OF FEEDERS TO 150 AMPERE PANELBOARD.
 IS THE ELECTRIC SERVICE EXISTING OR NEW? VERIFY THE
 ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND GROUPED IN
 ONE LOCATION. NEC 230.2, 230.71
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 UNIT ENTRANCE. NEC 210.52
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING IN HOMES WITH GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE. 2007
 FBC R313
  
  
 ROBERT LECKY
 ELECTRIC PLAN REVIEWER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By rlecky Date 2012-01-09 Time 14:50 Rev Time 0.00
Received By rlecky Date 2012-01-09 Time 14:48 Sent To  
Notes
2012-01-09 14:54:54ELECTRIC PLAN AND PERMIT REQUIRED. SHOW EXISTING AND
 NEW. PROVIDE AN ELECTRICAL RISER PLAN. LOCATE ALL PANEL
 BOARDS AND MAIN DISCONNECTS ON THE PLAN. NEC 215.5.
  
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-03-05 Cont ID  
Sent By wjolin Date 2012-03-05 Time 08:46 Rev Time 0.00
Received By wjolin Date 2012-03-05 Time 08:42 Sent To  
Notes
2012-03-05 08:48:18429 BELVEDERE ROAD
 PERMIT #12010122
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE CARBON MONOXIDE DETECTORS OUTSIDE OF ANY
 BEDROOMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-18 Cont ID  
Sent By wjolin Date 2012-01-18 Time 14:13 Rev Time 0.00
Received By wjolin Date 2012-01-18 Time 13:42 Sent To  
Notes
2012-01-18 14:13:22429 BELVEDERE ROAD
 PERMIT #12010122
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-18 Cont ID  
Sent By lmartine Date 2012-04-18 Time 15:30 Rev Time 0.00
Received By lmartine Date 2012-04-06 Time 15:06 Sent To  
Notes
2012-04-06 15:07:03TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-22 Cont ID  
Sent By hmoser Date 2012-03-22 Time 11:49 Rev Time 0.00
Received By hmoser Date 2012-02-21 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-25 Cont ID  
Sent By hmoser Date 2012-01-25 Time 12:43 Rev Time  
Received By hmoser Date 2012-01-06 Time   Sent To  
Notes
2012-01-09 08:08:24B04

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2012-04-18 Cont ID  
Sent By hmoser Date 2012-04-18 Time 15:08 Rev Time 0.00
Received By hmoser Date 2012-04-18 Time 15:08 Sent To  
Notes
2012-04-18 15:11:31SEPARATE PLANS AND PERMIT REQUIRED BY AIRCONDITIONING
 CONTRACTOR
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-04-18 Cont ID  
Sent By hmoser Date 2012-03-22 Time 11:48 Rev Time 0.00
Received By hmoser Date 2012-03-22 Time 11:09 Sent To  
Notes
2012-03-22 11:48:41PLANS DENIED
 1) PROVIDE MORE INFORMATION ON THE EQUIPMENT SCHEDULE
 CONDENSER MODEL NUMBER AND INFORMATION ON THE
 AIR HANDLER UNIT. SECTION 301.5 FBC (M) 2007
 2) PROVIDE HEAT LOADS AND ENERGY CALCULATIONS FOR THE
 ADDITION.
 3) ON THE DETAIL FOR THE CONDENSER STAND TO ROOF WHAT
 SIZE BOLTS
 ARE USED . SECTION 301.12 WIND RESISTANCE.2007 FBC (M)
 4) PROVIDE PRODUCT APPROVALS ON THE CONDENSER STAND
 WITH THE
 PLANS SECTION 106.3.3 FBC 2007
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-01-25 Cont ID  
Sent By hmoser Date 2012-01-25 Time 12:43 Rev Time 0.00
Received By hmoser Date 2012-01-25 Time 12:32 Sent To  
Notes
2012-01-25 12:42:46NO MECHANICAL PLANS SUBMITTED. SEPARATE APPLICATION AND
 PLANS WILL BE SUBMITTED
 BY MECHANICAL CONTRACTOR.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-29 Cont ID  
Sent By lwagner Date 2012-02-29 Time 09:57 Rev Time 0.00
Received By lwagner Date 2012-02-29 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-10 Cont ID  
Sent By lwagner Date 2012-01-10 Time 09:16 Rev Time 0.00
Received By lwagner Date 2012-01-10 Time 08:59 Sent To  
Notes
2012-01-10 09:15:47NO PLUMBING DRAWINGS ON PLAN AT THIS TIME. TO OBTAIN A
 PLUMBING PERMIT AN APPLICATION, DRAWINGS, AND FEES WILL
 BE REQUIRED.

Review Stop Z ZONING
Rev No 3 Status F Date 2012-04-19 Cont ID  
Sent By jroach Date 2012-04-19 Time 16:05 Rev Time 0.00
Received By jroach Date 2012-04-19 Time 16:04 Sent To  
Notes
2013-01-18 14:52:33THE OWNER OF THE PROPERTY HAS OUTSTANDING LIENS THAT
 ARE DUE TO THE CITY. THE PERMIT MAY NOT BE ISSUED UNTIL
 ALL OUTSTADING DEBTS ARE RESOLVED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1448.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-08 Cont ID  
Sent By jroach Date 2012-03-08 Time 10:55 Rev Time 0.00
Received By jroach Date 2012-03-08 Time 09:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-01-19 Cont ID  
Sent By jroach Date 2012-01-19 Time 11:35 Rev Time 0.00
Received By jroach Date 2012-01-19 Time 09:48 Sent To  
Notes
***NONE***