| 2012-01-12 13:52:45 | 901 45TH STREET - MAINTENANCE BUILDING |
| | PERMIT #12010058 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PER FLORIDA STATUTES, FIRE SPRINKLER DRAWINGS AND |
| | HYDRAULIC CALCULATIONS ARE REQUIRED TO BE SIGNED AND |
| | SEALED BY A PROFESSIONAL ENGINEER FOR THE DESIGN OR |
| | ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. |
| | |
| | SPRINKLER DESIGN SHALL CONFORM TO THE REQUIREMENTS OF |
| | THE 2007 EDITION OF NFPA 13 AS OF JANUARY 1, 2012. |
| | |
| | SUBMIT HYDRAULIC CALCULATIONS FOR REVIEW AND PROVIDE |
| | HYDRAULIC DESIGN PLACARD ON RISER. |
| | |
| | PROVIDE WATER SUPPLY INFORMATION (FIRE PUMP TEST OR |
| | HYDRANT FLOW TEST, ETC.). |
| | |
| | INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS |
| | FLOOR. |
| | |
| | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | THE 4-INCH STANDPIPE RISER ON THE EAST SIDE OF THE |
| | BUILDING APPEARS TO BE SUPPLYING THE SPRINKLER SYSTEM; |
| | HOWEVER, THERE ARE SPRINKLERS LOCATED BOTH UPSTREAM AND |
| | DOWNSTREAM OF THE FLOOR CONTROL ASSEMBLY. PLEASE |
| | EXPLAIN. |
| | |
| | TWO STORAGE ROOMS ON SHEET 2 DO NOT INDICATE THE |
| | FINISHED CEILING TO BE RUN TIGHT TO THE BOTTOM OF THE |
| | WOOD CEILING JOISTS. SPRINKLERS WILL BE REQUIRED IN THE |
| | COMBUSTIBLE CONCEALED SPACE IF THE CEILING IS LOCATED |
| | MORE THAN 6-INCHES BELOW THE JOISTS. VERIFY CEILING |
| | ELEVATION IN RELATION TO THE JOISTS. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |