2012-01-09 12:54:421601 BELVEDERE ROAD
 PERMIT #12010034
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE
 EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM
 OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE
 SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL
 CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC 904.11.1.
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  