| 2012-01-04 11:10:27 | UNDER 5 K MECHANICAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-01-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2012-01-05 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2012-01-05 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2012-01-05 10:22:51 | PLANS DENIED | | | 1) PROVIDE A DETAIL ON THE PLANS HOW THE DUCT OVER THE | | | NAIL TABLES MEET THE REQUIREMENTS OF | | | TABLE 403.3 FOOT NOTE (I) 2007 FBC(M) | | | 2) REFER TO SECTION 506.3.12.3 TERMINATION LOCATION | | | 2007 FBC(M) | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|
|
|