Plan Review Details - Permit 12010011
Plan Review Stops For Permit 12010011
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-03-08 Cont ID  
Sent By jwitmer Date 2012-03-08 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2012-03-08 Time 11:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-10 Cont ID  
Sent By jwitmer Date 2012-02-10 Time 07:53 Rev Time 0.50
Received By jwitmer Date 2012-02-10 Time 07:15 Sent To  
Notes
2012-02-10 07:58:15BUILDING PLAN REVIEW
 PERMIT:12010011
 ADD: 535 E LAKEWOOD RD
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE CONTRACTOR OF RECORD IF DOING THEIR OWN DESIGN
 (DRAFTING) ARE TO TAKE OWNERSHIP OF THE PLANS PRINT
 THEIR NAME, SIGN THEIR NAME AND PROVIDE THEIR LICENSE
 NUMBER ON THE PLANS BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
 FBC-B 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 2) 2007/09 FBC-B 106.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
  
 A) 106.3.5 (3)MINIMUM BUILDING TYPE
  
 B) BUILDING SPRINKLERED OR NON-SPRINKLERED
  
 C) IT APPEARS THERE ARE EITHER SEPERATE TENANTS OR
 OCCUPANCY SEPERATION ISSUES NOT INDICATED ON THE PLANS
 (TABLE 508.3.3)/ 708.1. SEPERATED USE OR NON SEPERATED
 508.3.1.3 OR 508.3.2.
  
 106.3.5(2) OCCUPANCY GROUP ( OCCUPANCY SEPERATION
 ISSUES) AND SPECIAL OCCUPANCY REQUIREMENTS SHALL BE
 DETERMINED. THE PBC PROPERTY APPRAISERS OFFICE
 INDICATES THE FOLLOWING SQ FT AREAS:
 1590 S F OFFICE
 1054 S F GARAGE
 4760 S F WAREHOUSE
  
 D) 106.3.5 (6) LIFE SAFETY OCCUPANT LOADS/ EGRESS
 CAPACITY
  
 E) CHANGE IN CEILING/ ROOF ASSEMBLIES? SHOW OCCUPANCY
 SEPERATION WALL DETAIL AND HOUR RATING!!!!!
  
 F) COMPLIED.
  
 G) PLANS FAIL TO PROVIDE DETAILS FOR ACCESSIBILITY TO
 RESTROOMS AND BREAK ROOM AREAS?PLEASE REVIEW 2007/09
 FBC-B CHAPTER 11-4.1.6(2)(A) 20 % DISPROPORTIONATE
 COST. PLEASE SHOW THE LAYOUT OF THE RESTROOMS SINCE THE
 WALL FINISHES WERE REMOVED!!!!!!!!! DEMO PERMIT
 11120176.
  
 3) PLEASE REVIEW 2007/09 EXISTING BUILDING CODE CHAPTER
 7 FOR LEVEL 2 ALTERATIONS OR IS THIS A LEVEL I
 ALTERATION:
  
 3A) 704.5 EGRESS DOORS.
  
 3B) 706.1. ACCESSIBILITY CHAPTER 11 OF THE FBC-B.
  
 3C) POSSIBLY: 711.1 MINIMUM REQUIREMENTS ENERGY CODE.
  
 4) SUBMITTED DOOR SPEC MASONITE DOOR, PLANS DO NOT
 INDICATE WHERE THIS DOOR IS LOCATED, INTERIOR .
 EXTERIOR , FIRE RATED DOOR THESE ARE ALL UNKNOWNS?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-10 Cont ID  
Sent By jwitmer Date 2012-01-10 Time 13:19 Rev Time 0.77
Received By jwitmer Date 2012-01-10 Time 13:05 Sent To  
Notes
2012-01-10 15:30:00BUILDING PLAN REVIEW
 PERMIT:12010011
 ADD: 535 E LAKEWOOD RD
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE CONTRACTOR OF RECORD IF DOING THEIR OWN DESIGN
 (DRAFTING) ARE TO TAKE OWNERSHIP OF THE PLANS PRINT
 THEIR NAME, SIGN THEIR NAME AND PROVIDE THEIR LICENSE
 NUMBER ON THE PLANS BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
  
 2) 2007/09 FBC-B 106.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
  
 A) 106.3.5 (3)MINIMUM BUILDING TYPE
  
 B) BUILDING SPRINKLERED OR NON-SPRINKLERED
  
 C) IT APPEARS THERE ARE EITHER SEPERATE TENANTS OR
 OCCUPANCY SEPERATION ISSUES NOT INDICATED ON THE PLANS
 (TABLE 508.3.3)/ 708.1. SEPERATED USE OR NON SEPERATED
 508.3.1.3 OR 508.3.2.
  
 106.3.5(2) OCCUPANCY GROUP AND SPECIAL OCCUPANCY
 REQUIREMENTS SHALL BE DETERMINED. THE PBC PROPERTY
 APPRAISERS OFFICE INDICATES THE FOLLOWING SQ FT AREAS:
 1590 S F OFFICE
 1054 S F GARAGE
 4760 S F WAREHOUSE
  
 D) 106.3.5 (6) LIFE SAFETY OCCUPANT LOADS/ EGRESS
 CAPACITY
  
 E) CHANGE IN CEILING/ ROOF ASSEMBLIES?
  
 F) PLANS FAIL TO PROVIDE DETAIL OF 2X4 SPACING, IF THEY
 GO TO A DROPPED CEILING OR TO THE ROOF DECK ABOVE?
  
 G) PLANS FAIL TO PROVIDE DETAILS FOR ACCESSIBILITY TO
 RESTROOMS AND BREAK ROOM AREAS?PLEASE REVIEW 2007/09
 FBC-B CHAPTER 11-4.1.6(2)(A) 20 % DISPROPORTIONATE
 COST.
  
 3) PLEASE REVIEW 2007/09 EXISTING BUILDING CODE CHAPTER
 7 FOR LEVEL 2 ALTERATIONS:
  
 3A) 704.5 EGRESS DOORS.
  
 3B) 706.1. ACCESSIBILITY CHAPTER 11 OF THE FBC-B.
  
 3C) POSSIBLY: 711.1 MINIMUM REQUIREMENTS ENERGY CODE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2012-03-12 Cont ID  
Sent By rlecky Date 2012-03-12 Time 09:29 Rev Time 0.00
Received By rlecky Date 2012-03-12 Time 09:17 Sent To  
Notes
2012-03-12 09:29:51INTERIOR ELECTRIC EXISTS.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2012-02-10 Cont ID  
Sent By rlecky Date 2012-02-10 Time 15:10 Rev Time 0.00
Received By rlecky Date 2012-02-10 Time 15:10 Sent To  
Notes
2012-02-10 15:14:08SEPERATE PERMIT AND PLANS REQUIRED FOR ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-05 Cont ID  
Sent By rlecky Date 2012-01-05 Time 15:53 Rev Time 0.00
Received By rlecky Date 2012-01-05 Time 15:47 Sent To  
Notes
2012-01-05 15:50:58REQUIRES AN ELECTRICAL PERMIT AND PLAN INCLUDING
 LOCATION AND SIZE OF EXISTING SERVICE, PANEL BOARDS,
 PANEL SCHEDULE WITH NEW AND EXISTING CIRCUITS
 IDENTIFIED. PLAN SHALL BE SIGNED BY THE DESIGNER OR
 RECORD. NEC 215.5
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-03-09 Cont ID  
Sent By wjolin Date 2012-03-09 Time 13:30 Rev Time 0.00
Received By wjolin Date 2012-03-09 Time 13:27 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-02-14 Cont ID  
Sent By wjolin Date 2012-02-14 Time 09:02 Rev Time 0.00
Received By wjolin Date 2012-02-14 Time 08:22 Sent To  
Notes
2012-02-14 09:02:31535 EAST LAKEWOOD ROAD
 PERMIT #12010011
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLEASE PROVIDE ALL THE RESPONSE LETTER INFORMATION ON
 THE PLANS (ADDRESS, CONSTRUCTION MATERIALS, ETC.).
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-01-11 Cont ID  
Sent By wjolin Date 2012-01-11 Time 14:28 Rev Time 0.00
Received By wjolin Date 2012-01-11 Time 14:06 Sent To  
Notes
2012-01-11 14:28:20535 EAST LAKEWOOD ROAD
 PERMIT #12010011
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON THE PLANS.
  
 INDICATE THE REASON FOR REPLACING THE WALLS.
  
 INDICATE IF WALLS BEING ADDED OR RELOCATED FROM
 PREVIOUS LOCATIONS.
  
 PLANS INDICATE A BUILDING #1 AND BUILDING #2. NO PLANS
 WERE SUBMITTED FOR BUILDING #2 (WAREHOUSE). INDICATE IF
 WORK IS BEING PERFORMED IN THIS SPACE.
  
 PLANS DO NOT INDICATE WALL MATERIALS, STUD SPACING,
 WALL FINISH ETC.
  
 A THOROUGH PLAN REVIEW CANNOT BE COMPLETED AT THIS TIME
 DUE TO LACK OF INFORMATION PRESENTED ON THE PLANS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-12 Cont ID  
Sent By rlecky Date 2012-03-12 Time 09:45 Rev Time 0.00
Received By rlecky Date 2012-02-24 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-14 Cont ID  
Sent By wjolin Date 2012-02-14 Time 09:03 Rev Time 0.00
Received By wjolin Date 2012-02-07 Time 13:08 Sent To  
Notes
2012-02-08 13:10:08INCOMING SENT TO B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-03 Cont ID  
Sent By shill Date 2012-02-03 Time 09:07 Rev Time 0.00
Received By shill Date 2012-01-03 Time 15:40 Sent To  
Notes
2012-01-03 15:42:58B 13

Review Stop Z ZONING
Rev No 1 Status N Date 2012-01-13 Cont ID  
Sent By eschneid Date 2012-01-13 Time 14:03 Rev Time 0.25
Received By eschneid Date 2012-01-13 Time 14:03 Sent To  
Notes
2012-01-13 14:03:43DOES NOT TRIGGER 50% VALUE.