| 2012-01-05 13:21:36 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE W/ 2009 REVISIONS. |
| | |
| | |
| | 1- FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE |
| | OF NOA 08-0410.09 SUBMITTED. PAGE 35 OF NOA SUBMITTED |
| | IS GOOD FOR 60PSF. CORNER AND PERIMETER AREAS DESIGN |
| | PRESSURES ARE HIGHER. NEED THE CALCULATIONS TO COMPLY |
| | WITH THE DESIGN PRESSURES AS REQUIRED BY SEC. |
| | R301.2.1.4.3. |
| | |
| | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 |
| | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDOING |
| | TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON |
| | EXPOUSRE "C". |
| | |
| | 2- SPECIFY HOW IS THE CONCRETE TILE GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1.4.3. IF USING SCREWS, THEN |
| | SPECIFY NUMBER OF SCREWS. IF USING FOAM, THEN PROVIDE |
| | PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3. SEE TILE |
| | NOA FOR LISTED FOAMS. |
| | |
| | 3- A) DESCRIPTION ON PERMIT APPLICATION DOESN'T SPECIFY |
| | SKYLIGHTS. SPECIFY/CLARIFY IF INSTALLING NEW SKYLIGHTS |
| | OR REPLACING EXISTING SKYLIGHTS AND SPECIFY HOW MANY. |
| | |
| | B) SPECIFY HOW MUCH SQUARE FEET IS FOR CONCRETE TILE, |
| | HOW MUCH SQUARE FEET IS FOR FLAT ROOF AND HOW MANY |
| | SKYLIGHTS ARE TO BE INSTALLED TO VERIFY TOTAL VALUE. |
| | SEC. 108.3 CITY AMENDMENTS. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC. |
| | VALUE TO INCLUDE ALL SCOPE OF WORK INCLUDING CONCRETE |
| | TILE ROOF, FLAT ROOF AND SKYLIGHTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL: |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |