| 2012-01-05 12:11:15 | BUILDING PLAN REVIEW |
| | PERMIT: 11120632 |
| | ADD: 7426 S DIXIE HWY |
| | CONT: LANTANA CONSTRUCTION |
| | TEL: (561)642-0870 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) THE DESIGNER OF RECORD INDICATES THIS AREA TO BE |
| | NEW TAE KWON DO CENTER, INSTRUCTION AREA, BUT ACTUALLY |
| | LISTING THE OCCUPANCY TYPE, THE AGE OF THE CLIENTS MAY |
| | BE A FACTOR OF HOW THE TENANT SPACE SHOULD BE LABELED |
| | FOR OCCUPANCY. FOR THIS REVIEW THE BUILDING REVIEW WILL |
| | REVIEW AS A BUSINESS OCCUPANCY, FBC-B 304.1 LIST |
| | TRAINING AND SKILLS DEVELOPMENT NOT WITHIN A SCHOOL OR |
| | ACADEMIC PROGRAM AS A BUSINESS OCCUPANCY. |
| | |
| | 1B) OUR RECORDS DO NOT INDICATE THE LAST USAGE FOR THIS |
| | SPACE, IS IT A CHANGE OF OCCUPANCY? IF SO THE 2007/09 |
| | FLORIDA EXISTING BUILDING CODE CHAPTER 9 SECTION |
| | 901.1.3.1 SHALL APPLY. FL EXST BLDG CODE 901.3.1 |
| | PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION . WHERE A |
| | PORTION OF AN EXISTING BUILDING IS CHANGED TO A NEW |
| | OCCUPANCY CLASSIFICATION, SECTION 912 OF THE EXISTING |
| | BLDG CODE SHALL APPLY. |
| | |
| | 2) IF A CHANGE OF OCCUPANCY HAS OCCURED, THEN THE EXST |
| | BLDG CODE SECTION 912.8 REFERS YOU BACK TO CHAPTER 11 |
| | OF THE FLORIDA BUILDING CODE- BUILDING. |
| | PLEASE SEE 11-4.1.6(2) DUTY TO PROVIDE ACCESSIBLE |
| | FEATURE IN THE EVENT OF DISPROPORTIONALITY. 11-4.1.6 |
| | (2)(A) |
| | (I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE TO ALL ALTERED AREAS (DRESSING |
| | ROOM) |
| | (III) AT LEAST ONE SCCESSIBLE RESTROOM FOR EACH SEX OR |
| | A SINGLE UNISEX RESTROOM. |
| | PLEASE PROVIDE HOW AN ADDITIONAL $ 1560 DOLLARS WILL BE |
| | SPENT BRINGING THIS TENANT SPACE CLOSER TO CODE |
| | COMPLIANCE, A WRITTEN LETTER ON THE CONTRACTOR LETTER |
| | HEAD WILL THEN BE ATTACHED TO THE PLANS AS PART OF THE |
| | PERMANENT RECORDS. |
| | |
| | 3) THE NEW COUNTER IS INDICATED TO HAVE A HEIGHT OF 42" |
| | PLEASE REVIEW 11-7 SRVICE COUNTERS |
| | |
| | 4) THE ELECTRIC SHEET # 4 INDICATES THE REAR DOOR AS A |
| | EGRESS DOOR. PLEASE BE AWARE THAT 2007/ 09 FBC-B 1024.3 |
| | EXIT DISCHARGE LOCATION SHALL BE LOCATED AT LEAST 10 |
| | FEET FROM ADJACENT PROPERTY LINES AND FROM OTHER |
| | BUILDINGS. THE OTHER FRONT DOOR DOES MEET 1/2 OF THE |
| | DIAGONAL OF THE SPACE FOR THE MEANS OF A 2ND EGRESS. |
| | |
| | 5) FLOOR PLAN A01 FINISH NOTES # 3 INDICATE HUMIDOR TO |
| | HAVE T & G CEILING. PLANS DO NOT INDICATE THE USE OF A |
| | HUMIDOR? 106.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) SHEET # 1 INDICATES IN THE TWO OFFICES THAT TEMPERED |
| | GLASS IS OPTIONAL TEMPERED GLASS IS REQUIRED BY SECTION |
| | FBC-B 2406.3(6) WHEN WITHIN 24 INCHES OF THE ARC OF THE |
| | SWING OF THE DOOR. CONSIDERED A HAZARDOUS LOCATION. |
| | |
| | 7) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| | SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |