Plan Review Details - Permit 11120607
Plan Review Stops For Permit 11120607
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-01-23 Cont ID  
Sent By rlecky Date 2012-01-23 Time 09:35 Rev Time 0.00
Received By rlecky Date 2012-01-23 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-01-06 Cont ID  
Sent By rlecky Date 2012-01-06 Time 10:18 Rev Time 0.00
Received By rlecky Date 2012-01-05 Time 15:37 Sent To  
Notes
2012-01-05 15:42:45SEE FD COMMENTS.
 TO MECHANICAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-01-17 Cont ID  
Sent By wjolin Date 2012-01-17 Time 12:40 Rev Time 0.00
Received By wjolin Date 2012-01-17 Time 12:18 Sent To M
Notes
2012-01-17 12:32:03601 CLEARWATER PARK
 PERMIT #11120607
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 72, SMOKE DETECTORS SHALL NOT BE INSTALLED IN
 UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS THEY ARE
 INSTALLED TO ACTIVATE SMOKE RELIEF EQUIPMENT.
  
 THERE IS AN EXISTING FIRE SHUTTER (WITH FUSIBLE LINK?)
 ON THE FIRST FLOOR ADJACENT TO THE STAIR. PROVIDE SMOKE
 DETECTORS ON EACH SIDE OF THE SHUTTER TO ACTIVATE THE
 SHUTTER. FIRE SHUTTER SHALL ALSO DROP UPON ACTIVATION
 OF OTHER FIRE ALARM DEVICES.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-12-28 Cont ID  
Sent By wjolin Date 2011-12-28 Time 14:41 Rev Time 0.00
Received By wjolin Date 2011-12-28 Time 14:16 Sent To E
Notes
2011-12-28 14:41:44601 CLEARWATER PARK
 PERMIT #11120607
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM SHEETS 1 & 2 ARE THE SAME SHEET. SUBMIT FIRE
 ALARM LAYOUT FOR SECOND FLOOR.
  
 THERE IS AN EXISTING FIRE SHUTTER (WITH FUSIBLE LINK?)
 ON THE FIRST FLOOR ADJACENT TO THE STAIR. PROVIDE SMOKE
 DETECTORS ON EACH SIDE OF THE SHUTTER TO ACTIVATE THE
 SHUTTER. FIRE SHUTTER SHALL ALSO DROP UPON ACTIVATION
 OF OTHER FIRE ALARM DEVICES.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-23 Cont ID  
Sent By rlecky Date 2012-01-23 Time 09:36 Rev Time 0.00
Received By rlecky Date 2012-01-10 Time 12:47 Sent To  
Notes
2012-01-10 12:47:42TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2012-01-06 Cont ID  
Sent By hmoser Date 2012-01-06 Time 09:58 Rev Time 0.00
Received By hmoser Date 2011-12-27 Time 10:08 Sent To  
Notes
2011-12-27 10:09:11IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-01-23 Cont ID  
Sent By hmoser Date 2012-01-23 Time 08:57 Rev Time 0.00
Received By hmoser Date 2012-01-23 Time 08:57 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-01-06 Cont ID  
Sent By hmoser Date 2012-01-06 Time 09:44 Rev Time 0.00
Received By hmoser Date 2012-01-06 Time 09:27 Sent To  
Notes
2012-01-06 09:43:38PASS PROVISO
 IF THE LAYOUT OF THE FIRST AND SECOND FLOOR ARE NOT THE
 SAME REVISIONS WILL BE REQUIRED .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected].