Plan Review Details - Permit 11120597
| Plan Review Stops For Permit 11120597 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2011-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2011-12-27 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2011-12-27 09:40:49 | UNDER 5 K MECHANICAL |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-12-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2011-12-27 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2011-12-27 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2011-12-27 16:23:50 | DENIED | | | | | | SKETCH SUBMITTED PROPOSES CLEARANCE REDUTION FOR | | | COMBUSTIBLE MATERIALS. ACCORDING TO THE DRAWING, THE | | | PROPOSED CLEARANCE BETWEEN THE GREASE EXHAUST DUCT AND | | | THE HVAC DUCT WOULD BE 3 INCHES WITH TWO SHEETS OF | | | GALVANIZED STEEL ENCAPSULATING 1 INCH OF MINERAL WOOL | | | BATT INSULATION. ACCORDING TO FBC-M TABLE 308.6, THE | | | MINIMUM REQUIRED CLEARANCE WHEN USING SUCH AN ASSEMBLY | | | IS 6 INCHES. THEREFORE, THIS CLEARANCE REDUCTION METHOD | | | IS NOT CODE COMPLIANT. | | | | | | FOR ALTERNATIVE CLEARANCE REDUCTION METHODS, SEE FBC-M | | | SECTION 308.5. THIS SECTION ALLOWS THE USE OF LISTED | | | AND RATED ASSEMBLIES TO BE USED FOR CLEARANCE REDUCTION | | | AND THE REQUIRED CLEARANCE SHALL BE IN ACCORDANCE WITH | | | THE PRODUCT LISTING. SOME OF THESE PRODUCTS, COMMONLY | | | REFERRED TO AS "FIRE WRAP" ALLOW FOR SIGNIFICANT | | | CLEARANCE REDUCTION. SOME ARE AS LITTLE AS ZERO | | | CLEARANCE REQUIRED TO COMBUSTIBLE MATERIALS. BE SURE TO | | | CHECK THE PRODUCT LISTING FOR ACTUAL CLARANCE REDUCTION | | | PROPERTIES. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |