Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-24 Cont ID  
Sent By jwitmer Date 2012-01-24 Time 16:06 Rev Time 0.00
Received By jwitmer Date 2012-01-24 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-12-29 Cont ID  
Sent By jwitmer Date 2011-12-29 Time 13:16 Rev Time 0.00
Received By jwitmer Date 2011-12-29 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-03 Cont ID  
Sent By wjolin Date 2012-01-03 Time 13:43 Rev Time 0.00
Received By wjolin Date 2012-01-03 Time 13:36 Sent To  
Notes
2012-01-03 13:42:521401 FORUM WAY
 PERMIT #11120530
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE (IF NOT EXISTING) VISUAL FIRE ALARM
 NOTIFICATION APPLIANCES IN ALL RENOVATED RESTROOM
 SPACES.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATIONS OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-03 Cont ID  
Sent By lwagner Date 2012-02-03 Time 13:50 Rev Time 0.00
Received By lwagner Date 2012-01-24 Time 09:05 Sent To  
Notes
2012-01-24 09:06:13B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By rmcdouga Date 2012-01-24 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2011-12-22 Time 09:38 Sent To  
Notes
2011-12-22 09:39:10INCOMING SENT TO B10. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-03 Cont ID  
Sent By lwagner Date 2012-02-03 Time 13:50 Rev Time 0.00
Received By lwagner Date 2012-02-03 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-12-28 Cont ID  
Sent By lwagner Date 2011-12-28 Time 08:00 Rev Time 0.00
Received By lwagner Date 2011-12-27 Time 14:23 Sent To  
Notes
2011-12-28 08:00:48FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. BY REMOVING A WATER CLOSET IN EACH RESTROOM THE
 FIXTURE COUNT FOR THE FLOOR MAY BE LESS THAN REQUIRED.
 PLEASE SHOW THE CALCULATIONS FOR THE REQUIRED FIXTURES.
 FBC PLUMBING TABLE 403.1 - FOR BUSINESS OCCUPANCY FOUR
 WC/ URINALS = 100 OCCUPANTS.
  
 2. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 PLUMBING RISER DIAGRAM REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-01-20 Cont ID  
Sent By lfranco Date 2012-01-20 Time 14:19 Rev Time 0.00
Received By lfranco Date 2012-01-20 Time 14:18 Sent To  
Notes
2012-01-20 14:21:46PLANNING: ***** ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE. ****