Plan Review Stops For Permit 11120528
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-01-05 Cont ID  
Sent By jwitmer Date 2012-01-05 Time 09:43 Rev Time 0.50
Received By jwitmer Date 2012-01-05 Time 09:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-03 Cont ID  
Sent By wjolin Date 2012-01-03 Time 13:48 Rev Time 0.00
Received By wjolin Date 2012-01-03 Time 13:46 Sent To  
Notes
2012-01-03 13:48:261645 PALM BEACH LAKES BOULEVARD
 PERMIT #11120528
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE (IF NOT EXISTING) VISUAL FIRE ALARM
 NOTIFICATION APPLIANCES IN ALL RENOVATED RESTROOM
 SPACES.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATIONS OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-03 Cont ID  
Sent By lwagner Date 2012-02-03 Time 10:37 Rev Time 0.00
Received By lwagner Date 2012-01-23 Time 09:46 Sent To  
Notes
2012-02-03 09:46:56GAVE TO LARRY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By rmcdouga Date 2012-01-20 Time 09:03 Rev Time 0.00
Received By lmartine Date 2011-12-22 Time 09:35 Sent To  
Notes
2011-12-22 09:37:02INCOMING SENT TO B9. JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-03 Cont ID  
Sent By lwagner Date 2012-02-03 Time 10:37 Rev Time 0.00
Received By lwagner Date 2012-02-03 Time 10:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-03 Cont ID  
Sent By lwagner Date 2012-01-03 Time 12:30 Rev Time 0.00
Received By lwagner Date 2011-12-29 Time 07:51 Sent To  
Notes
2012-01-03 11:11:43FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. BY REMOVING A WATER CLOSET IN EACH RESTROOM THE
 FIXTURE COUNT FOR THE FLOOR MAY BE LESS THAN REQUIRED.
 PLEASE SHOW THE CALCULATIONS FOR THE REQUIRED FIXTURES.
 FBC PLUMBING TABLE 403.1 - FOR BUSINESS OCCUPANCY FOUR
 WC/ URINALS = 100 OCCUPANTS.
  
 2. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 PLUMBING RISER DIAGRAM REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop Z ZONING
Rev No 1 Status N Date 2012-01-20 Cont ID  
Sent By lfranco Date 2012-01-20 Time 14:23 Rev Time 0.00
Received By lfranco Date 2012-01-20 Time 14:23 Sent To  
Notes
2012-01-20 14:23:19PLANNING: ***** ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE. ****