Plan Review Details - Permit 11120520
Plan Review Stops For Permit 11120520
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-12-28 Cont ID  
Sent By wjolin Date 2011-12-28 Time 11:40 Rev Time 0.00
Received By wjolin Date 2011-12-28 Time 11:29 Sent To M
Notes
2011-12-28 11:40:273220 COMMERCE PLACE
 PERMIT #11120520
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE
 EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM
 OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE
 SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL
 CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC 904.11.1.
  
 PROVIDE A TYPE K PORTABLE FIRE EXTINGUISHER WITH PROPER
 SIGNAGE.
  
 CONFIRM ELECTRICAL POWER TO APPLIANCE WILL BE SHUT OFF
 WITH THE ACTIVATION OF THE KITCHEN HOOD SUPPRESSION
 SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-28 Cont ID  
Sent By hmoser Date 2011-12-28 Time 15:05 Rev Time 0.00
Received By hmoser Date 2011-12-20 Time 07:41 Sent To  
Notes
2011-12-21 07:42:31SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-12-28 Cont ID  
Sent By hmoser Date 2011-12-28 Time 15:05 Rev Time 0.00
Received By hmoser Date 2011-12-28 Time 15:04 Sent To  
Notes
***NONE***