Plan Review Details - Permit 11120506
Plan Review Stops For Permit 11120506
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2011-12-20 Cont ID  
Sent By jnguyen Date 2011-12-20 Time 16:36 Rev Time 0.00
Received By jnguyen Date 2011-12-20 Time 15:37 Sent To  
Notes
2011-12-20 16:35:59I DETERMINED THAT THE APPROXIMATE LOCATION FOR THIS
 PUMP STATION & DIVIDE STRUCTURE WILL BE LOCATED AT 771
 @ N AUSTRALIAN AVE (UNOFFICIAL ADDRESSES NOT USED FOR
 MAILING PURPOSES).
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 PUBLIC UTILITIES DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]
2011-12-20 12:03:13NEED ADDRESS FROM JOHN BECAUSE OF VARIOUS LOCATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-13 Cont ID  
Sent By jwitmer Date 2012-04-13 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2012-04-13 Time 15:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-01-05 Cont ID  
Sent By jwitmer Date 2012-01-05 Time 10:36 Rev Time 1.50
Received By jwitmer Date 2012-01-05 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-05-16 Cont ID  
Sent By jleahy Date 2012-05-16 Time 14:08 Rev Time 0.00
Received By jleahy Date 2012-05-16 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-04-17 Cont ID  
Sent By jleahy Date 2012-04-17 Time 14:25 Rev Time 0.00
Received By jleahy Date 2012-04-16 Time 14:24 Sent To  
Notes
2012-04-17 14:25:39SEE ELECTRICAL NOTES ALL THROUGH "E" PAGES JL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-06 Cont ID  
Sent By rlecky Date 2012-01-06 Time 11:31 Rev Time 0.00
Received By rlecky Date 2012-01-06 Time 09:13 Sent To  
Notes
2012-01-06 11:32:2111120506
 771 N AUSTRALIAN AVE
 WPB PUMP STATION
  
 GROUND-FAULT PROTECTION OF EQUIPMENT (GFPE) IS REQUIRED
 FOR THE SERVICE. NEC 230.95
 PROVIDE A LABELING SCHEDULE FOR THE WARNING AND SAFETY
 SIGNAGE REQUIRED FOR THE ELECTRICAL EQUIPMENT. NEC
 110.22, 110.16, 701.9
 INDICATE THE SIZE OF THE PORTABLE GENERATOR FEEDERS TO
 THE TRANSFER SWITCH. NEC 450.13
 HOW IS THE LOAD ON THE PORTABLE GENERATOR TO BE
 MANAGED? NEC 702.5
 THE SIZE OF THE MAIN BREAKER FOR PANEL BOARDS ?A? AND
 ?B? HAS NOT BEEN SPECIFIED.
 THE FAULT CURRENT CAPABILITY FOR THE THREE 100 AMP
 PANELS HAS NOT BEEN SPECIFIED.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2012-05-04 Cont ID  
Sent By mgonzale Date 2012-05-04 Time   Rev Time 1.00
Received By mgonzale Date 2012-05-04 Time   Sent To  
Notes
2012-05-04 12:33:55PLAN REVISIONS ARE ACCEPTABLE.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-04-12 Cont ID  
Sent By mgonzale Date 2012-04-12 Time   Rev Time 1.00
Received By mgonzale Date 2012-04-12 Time   Sent To  
Notes
2012-04-12 15:26:38COMMENTS HAVE BEEN RESPONDED TOO AND ADDRESSED ON
 PLANS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-02-07 Cont ID  
Sent By mgonzale Date 2012-02-07 Time   Rev Time 0.50
Received By mgonzale Date 2012-02-07 Time   Sent To  
Notes
2012-02-07 19:10:31PLEASE RESPOND TO COMMENTS IN WRITING:
  
 SHEET C3-2 "GATES AND WALL SECTIONS"
 THE SECTION NUMBER ON EACH SECTION TITLE SHOULD REFLECT
 THE SHEET NUMBER WHERE
 SECTION WAS TAKEN FROM. HAVING SAID THIS, THE CALL OUT
 OF C3-2 ON EACH SECTION TITLE
 SHOULD BE SHOULD BE C3-1.
 (NOTE: SEE AS AN EXAMPLE, THE STRUCTURAL SHEETS, THOSE
 WHERE DONE CORRECTLY)
  
 SHEET C5-1 "CIVIL DETAILS"
 THE SECTION NUMBER ON EACH SECTION TITLE SHOULD REFLECT
 THE SHEET NUMBER WHERE
 SECTION WAS TAKEN FROM. HAVING SAID THIS, THE CALL OUT
 OF C5-1 ON EACH SECTION TITLE
 SHOULD BE SHOULD BE REFERENCED TO C1-2 AND C1-3.
 (NOTE: SEE AS AN EXAMPLE, THE STRUCTURAL SHEETS, THOSE
 WHERE DONE CORRECTLY)
  
 SHEET C3-1 "DIVIDE STRUCTURE SECTIONS"
 THIS SHEET SHOWS ON DETAIL 1 A GATE OPENING OF 11' HIGH
 (SHOWN AS 11' OPENING)
 SHEET C3-2 ON SECTION OR DETAIL 6 "MULTIPLE DISC SLIDE
 GATE NO. 2 FULLY RAISED" SHOWS
 A CLEAR OPENING OF 6' AND NOT 11' ON SECTION OR DETAIL
 4 IT SHOWS 9'.
 IT SEEMS A LITTLE CONFUSING WITHOUT A BETTER
 DESCRIPTION FOR EACH MODE OF OPERATION OF THE DISKS.
  
 MANUEL JULIAN GONZALEZ
 DSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-05-21 Cont ID  
Sent By wjolin Date 2012-05-21 Time 11:00 Rev Time 0.00
Received By wjolin Date 2012-05-21 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-10 Cont ID  
Sent By wjolin Date 2012-04-10 Time 13:15 Rev Time 0.00
Received By wjolin Date 2012-04-10 Time 13:14 Sent To  
Notes
2012-04-10 13:14:58771 NORTH AUSTRALIAN AVENUE
 PERMIT #11120506
 REVIEW COMMENTS - FIRE DEPARTMENT
 BID SET
  
 ALL PREVIOUS REVIEW COMMENTS HAVE BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-09 Cont ID  
Sent By wjolin Date 2012-01-09 Time 09:34 Rev Time 0.00
Received By wjolin Date 2012-01-09 Time 08:57 Sent To  
Notes
2012-01-09 09:34:14771 NORTH AUSTRALIAN AVENUE
 PERMIT #11120506
 REVIEW COMMENTS - FIRE DEPARTMENT
 90% CONSTRUCTION DOCUMENTS
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE FENCE OR STRUCTURE AND BE AT LEAST
 SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE ADDITIONAL INFORMATION REGARDING THE PORTABLE
 GENERATOR.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-05-22 Cont ID  
Sent By jwitmer Date 2012-05-22 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2012-04-30 Time 09:21 Sent To  
Notes
2012-05-01 09:52:24SENT TO C2 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-25 Cont ID  
Sent By lmartine Date 2012-04-25 Time 16:26 Rev Time 0.00
Received By lmartine Date 2012-03-28 Time 12:56 Sent To  
Notes
2012-03-29 13:03:09C--2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-08 Cont ID  
Sent By shill Date 2012-02-08 Time 14:14 Rev Time 0.00
Received By shill Date 2011-12-20 Time 10:44 Sent To  
Notes
2011-12-21 10:51:11C16

Review Stop Z ZONING
Rev No 3 Status P Date 2012-05-15 Cont ID  
Sent By jroach Date 2012-05-15 Time 20:47 Rev Time 0.00
Received By jroach Date 2012-05-07 Time 16:31 Sent To  
Notes
2012-05-15 20:47:58PROVISO
  
 PRIOR TO ISSUANCE OF A CERTIFICATE OF COMPLETION, A
 LANDSCAPE PLAN SHALL BE SUBMITTED TO THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING & ZONING DIVISION. ONCE
 AN ACCEPTABLE LANDSCAPE PLAN HAS BEEN DEVELOPED, AS
 DETERMINED BY THE PLANNING & ZONING DIVISION, SUCH
 LANDSCAPING SHALL BE INSTALLED (UNDER SEPARATE PERMIT),
 WITHIN THREE (3) MONTHS OF COMPLETION OF THE PROJECT
 AUTHORIZED HEREIN.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-04-25 Cont ID  
Sent By jroach Date 2012-04-25 Time 09:52 Rev Time 0.00
Received By jroach Date 2012-04-17 Time 16:25 Sent To  
Notes
2012-04-25 09:52:38PROVISO
  
 PRIOR TO ISSUANCE OF A CERTIFICATE OF COMPLETION, A
 LANDSCAPE PLAN SHALL BE SUBMITTED TO THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING & ZONING DIVISION. ONCE
 AN ACCEPTABLE LANDSCAPE PLAN HAS BEEN DEVELOPED, AS
 DETERMINED BY THE PLANNING & ZONING DIVISION, SUCH
 LANDSCAPING SHALL BE INSTALLED (UNDER SEPARATE PERMIT),
 WITHIN THREE (3) MONTHS OF COMPLETION OF THE PROJECT
 AUTHORIZED HEREIN.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  
2012-04-17 16:25:46JOHN HAS PLANS

Review Stop Z ZONING
Rev No 1 Status F Date 2012-02-03 Cont ID  
Sent By jroach Date 2012-02-03 Time 08:58 Rev Time 0.00
Received By jroach Date 2012-01-13 Time 08:53 Sent To  
Notes
2012-02-03 08:58:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.01.2011
 PERMIT NO.: 11120506
 ADDRESS: AUSTRALIAN AVENUE
 CONTRACTOR/CONTACT: JEREMY COVEY
 TELEPHONE NO.: 561.494.1112
 SCOPE OF REVIEW: WATER SUPPLY PUMP STATION.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE PROPOSED PULL-OFF AREA SHOULD BE
 MINIMALISTIC?THE DRIVEWAY SHOULD BE PLACED AT GRADE,
 ELIMINATE THE D-CURB AND CONSIDER THE USE OF AN
 ALTERNATIVE PAVING MATERIAL THAT WOULD BE MORE
 AESTHETIC (I.E. PAVERS, TURF BLOCK, ETC.).
  
 2. HAS APPROVAL BEEN GRANTED FROM PALM BEACH COUNTY FOR
 ACCESS TO AUSTRALIAN AVENUE?
  
 3. SIGNIFICANT LANDSCAPING SHOULD BE INSTALLED IN THE
 AREA OF THE PUMP STATION AND DIVIDE STRUCTURE (NORTH,
 SOUTH, AND BOTH SIDES OF AUSTRALIAN AVENUE) TO VISUALLY
 SCREEN THE STRUCTURE FROM THE ADJACENT TRAFFIC.
  
 4. EFFORTS SHOULD BE MADE TO VISUALLY REDUCE THE IMPACT
 OF THE STRUCTURE ON THE ADJACENT TRAFFIC BY REDUCING
 THE AMOUNT OF VISIBLE MECHANICAL EQUIPMENT AS MUCH AS
 POSSIBLE (I.E. REDUCE THE HEIGHT OF THE GATE OPEN/CLOSE
 MECHANISM, ETC.).
  
 5. MECHANICAL EQUIPMENT, INCLUDING THE AREA FOR THE
 GENERATOR, ELECTRICAL PANELS, ETC. SHALL BE SCREENED
 WITH AN OPAQUE MATERIAL. THE MATERIAL SHALL CONSIST OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY,
 OR COMPARABLY DURABLE WOOD AND STEEL. THE SCREEN SHALL
 BE LANDSCAPED WITH SHRUBS AND/OR HEDGES PLANTED AT
 TWO-FOOT INTERVALS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  