| 2011-12-29 11:44:23 | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES |
| | IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF |
| | RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL |
| | REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) PROVIDE FIRE STOP SYSTEM AT TIME OF FRAMING |
| | INSPECTION. |
| | FBC-B 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. |
| | THROUGH PENETRATIONS SHALL BE |
| | PROTECTED BY AN APPROVED PENETRATION FIRESTOP SYSTEM |
| | INSTALLED AS TESTED IN ACCORDANCE |
| | WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH |
| | (2.49 PA) OF WATER AND SHALL HAVE AN F RATING OF NOT |
| | LESS THAN THE REQUIRED FIRE-RESISTANCE |
| | RATING OF THE WALL PENETRATED. |
| | |
| | 2) FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR |
| | ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS |
| | SHALL BE EFFECTIVELY AND PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. |
| | SUCH IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING AND IN CONCEALED SPACES. SUGGESTED |
| | WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE AND SMOKE |
| | BARRIER - PROTECT ALL OPENINGS." |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |