| 2011-12-27 15:57:41 | BUILDING PLAN REVIEW |
| | PERMIT:11100408/ (REV) 11120496 |
| | ADD: 601 CLEARWATER PARK |
| | CONT: TURNER CONSTRUCTION CO. |
| | TEL: (786)348-6741 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ON THE PREVIOUS APPROVED PLANS SHEET A.100 NOTE 24 |
| | WAS FOR KNOX BOX AT FRONT ENTRY. THE REVISION # 2 DATED |
| | 12/19/2011 IS FOR A NEW STOREFRONT AND DOOR ASSEMBLY. |
| | 1A) PLEASE PROVIDE THE WIND DESIGN CRITERIA:1609.6.2 |
| | WIND DESIGN PROCEDURES |
| | 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 5) 1603.1.4 (5) PRESSURES POSITIVE & NEGATIVE FOR |
| | COMPONENTS & CLADDING. |
| | |
| | 1B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 1C) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, |
| | |
| | 2) SHEET A.100 ONE OF THE ITEMS THAT WAS AGREED UPON |
| | BETWEEN THE CLIENT, FIRE AND BUILDING DEPARTMENT WAS NO |
| | COMBUSTIBLE IN THE LOBBY. IT WAS ALSO SPECIFIED THAT |
| | THEIR WOULD BE NO STORAGE OF COMBUSTILES UNDER THE |
| | STAIRS AND WAS REQUESTED THAT NOTES BE APPLIED TO THE |
| | PLAN AS SUCH. THE REVISION THAT IS LABELED REVISION # 2 |
| | DATED 12/19/2011 NOW HAS A ROOM UNDERNEATH THE STAIR |
| | WITH NEW DOORWAY, NOT PART OF THE AGREEMENT, WILL NEED |
| | TO BE REVIEWED AND AGREED TO BY FIRE & BUILDING. |
| | |
| | 3) SHEET A.100 REVISION TO THE ELEVATOR LOBBY AND |
| | DOORWAY IDENTIFIED AS # 41 DOES NOT PROVIDE SIZE NOR |
| | RATING OF DOORWAY THAT SEPERATES THE ELEVATOR LOBBY AND |
| | THE STAIRWELL LOBBY BEING THE EXTENSION OF THE OPEN |
| | STAIRS LEADING TO THE SECOND FLOOR. PLANS ALSO DO NOT |
| | PROVIDE A DOOR SCHEDULE INDICATING THE FIRE RATING, |
| | HARDWARE, & CLOSERS TO BE INSTALLED ON THE PAIR OF |
| | DOORS. FROM THE APPROVED SET OF PLANS THERE IS ALSO A |
| | HAND WRITEN NOTE FROM THE DESIGNER OF RECORD OF THERE |
| | BEING A VIEW PANEL IN THE DOORS, WILL THERE BE A VIEW |
| | PANEL IN THE NEW PAIR OF DOORS, IF SO WHAT SIZE AND OF |
| | WHAT TYPE OF GLAZING FBC-B TABLE 715.4? |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |