Plan Review Details - Permit 11120485
Plan Review Stops For Permit 11120485
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 08:40 Rev Time 0.00
Received By jgomez Date 2012-02-06 Time 08:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-18 Cont ID  
Sent By jgomez Date 2012-01-18 Time 14:06 Rev Time 0.00
Received By jgomez Date 2012-01-18 Time 11:09 Sent To  
Notes
2012-01-18 14:34:43REVISION, BUILDING REVIEW COMMENTS.
  
 1- PRODUCT APPROVALS SUBMITTED FOR SINGLE HUNG WINDOWS,
 FIXED WINDOWS AND HORIZONTAL SLIDER WINDOWS DON'T MEET
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD. NEED TO PROVIDE PRODUCT APPROVALS THAT MEET THE
 CALCULATED DESIGN PRESSURES REQUIRED BY SEC. R301.2.4.3
 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- DRAWINGS SUBMITTED FOR FIXED WINDOW ARE FOR
 NON-IMPACT WINDOWS. NEED TO PROVIDE IMPACT WINDOWS OR
 OPENING PROTECTION AS REQUIRED BY SEC. R301.2.1.2.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL TO THIS OFFICE. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-02 Cont ID  
Sent By rlecky Date 2012-02-02 Time 09:50 Rev Time 0.00
Received By rlecky Date 2012-02-02 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-04 Cont ID  
Sent By rlecky Date 2012-01-04 Time 17:04 Rev Time 0.00
Received By rlecky Date 2012-01-04 Time 16:30 Sent To  
Notes
2012-01-04 17:04:54RELOCATED PANEL IN FAMILY ROOM NEEDS TO BE ADDED TO THE
 ELECTRICAL RISER PLAN. INCLUDE THE PANEL SIZE, AND
 WIRING METHOD. UPDATE THE LOAD CALCULATION IF NEEDED.
 ALL MAIN ELECTRIC DISCONNECTS MUST BE GROUPED IN ONE
 LOCATION. ADD THE SUB PANEL TO THE PANEL SCHEDULE IF
 APPROPRIATE. NEC 215.5, 230.72
  
 ADD A RECEPTACLE AT THE BAR KITCHEN COUNTER TO SERVE
 THE FAMILY ROOM. NEC 210.52
  
 AN INTER SYSTEM BONDING STRIP IS REQUIRED AT THE
 SERVICE. NEC 250.94
  
 SECOND FLOOR MASTER BEDROOM REQUIRES A CARBON MONOXIDE
 DETECTOR.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 09:57 Rev Time 0.00
Received By jgomez Date 2012-01-30 Time 08:50 Sent To  
Notes
2012-02-02 08:51:16GAVE TO LECKY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-18 Cont ID  
Sent By jgomez Date 2012-01-18 Time 14:34 Rev Time 0.00
Received By jgomez Date 2011-12-19 Time 17:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-06 Cont ID  
Sent By jgomez Date 2012-02-06 Time 09:57 Rev Time 0.00
Received By jgomez Date 2012-02-06 Time 09:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-18 Cont ID  
Sent By jgomez Date 2012-01-18 Time 14:03 Rev Time 0.00
Received By jgomez Date 2012-01-18 Time 14:03 Sent To  
Notes
2012-01-18 14:06:06REVISION PLUMBING REVIEW COMMENTS.
  
 1- PLUMBING RISER DIAGRAM SHOWING THE PROPOSED CHANGES
 WAS NOT PROVIDED. SEC. 106.3.5.4(9) CITY AMENDMENTS TO
 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 (561)805-6712