| 2012-01-04 16:48:08 | BUILDING PLAN REVIEW |
| | PERMIT: 11120482 |
| | ADD: 6501 N JOG RD |
| | CONT: D. S. EAKINS CONSTRUCTION CORP |
| | TEL: (561)719-6669 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) DISCREPANCY BETWEEN THE STATE APPROVED SOUTHEAST |
| | MODULAR MANUFACTURING PLAN (SHEET 2 OF 6) WITH 3920 SQ |
| | FT AND THE COPIED NOT SEALED FOUNDATION PLAN FROM |
| | WILLIAM SCOTSMAN PLAN (SHEET 4) FOR 2880 SQ FT. PLEASE |
| | PROVIDE THE FOUNDATION PLAN THAT MATCHES TO THE |
| | SOUTHEAST MANUFACTURING PLAN. NOTE THIS IS A SITE |
| | SPECIFIC ENGINEERING WITCH WILL REQUIRE A ENGINEER SEAL |
| | AND SIGNATURE. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 2) SHEET A1 RAMP DETAILS IS ALSO NOT SIGNED NOR SEALED |
| | BY THE DESIGN PROFESSIONAL. PLEASE NOTE THE SHEET A1 IS |
| | FOR A STRAIGHT RUN RAMP DETAIL WHILE THE STAGING PLAN |
| | FROM BE & K # 700-C0-020 INDICATES A RAMP WITH A SWITCH |
| | BACK AND A MID LANDING, PLEASE PROVIDE AN ENGINEERED |
| | PLAN THAT FITS THIS INSTALATION APPLICATION. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 3) THE PERMIT APPLICATION INDICATES THAT THE |
| | INSTALATION OF CONSTRUCTION TRAILERS ARE THESE ACTUALLY |
| | TRAILERS? ARE THEY GOING TO HAVE STORAGE OF |
| | CONSTRUCTION MATERIALS? OR ARE THEY MANUFACTURED |
| | BUILDING THAT WILL BE BROUGHT IN ARE FOR BUSINESS USAGE |
| | TO BE USED FOR THE ADMINISTRATION OF THE PROJECT? THE |
| | STATE APPROVED PLANS INDICATES THEY |
| | WERE BUILT WITH THE INTENT OF BUSINESS OFFICES. THIS |
| | REVIEW WILL BE WITH THE INTENDED USE AS APPROVED BY THE |
| | STATE, BUSINESS OCCUPANCY. |
| | |
| | 3A) THE DESIGNER OF RECORD WILL NEED TO CLARIFY IF EACH |
| | UNIT IS TO BE CONSIDERED A SINGLE BUILDING OF 3920 SQ |
| | FT OR IF MULTIPLE UNITS TWO OR MORE BUILDINGS ARE GOING |
| | TO BE CONSIDERED A SINGLE UNIT. PLEASE REVIEW FBC-B |
| | TABLE 503 FOR A BUSINESS OCCUPANCY A TYPE V-B ALLOWS AN |
| | AREA OF 9,000 SQ FT THESE UNITS ARE NOT FIRE |
| | SPRINKLERED NO INCREASE CAN BE TAKEN FOR FIRE |
| | SPRINKLERS BUT DEPENDING ON THE CONFIGURATION, FRONTAGE |
| | INCREASES MAY BE TAKEN FBC-B 506.2 WHICH WOULD CREATE A |
| | LARGER BUILDING. |
| | |
| | 3B) PLEASE REVIEW TABLE 502 FOR FIRE RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| | SEPERATION DISTANCE. THE STATE APPROVED PLANS INDICATES |
| | THAT THERE IS NO FIRE RATING OF THE EXTERIOR WALLS. FOR |
| | A TYPE V-B BUILDING THE MINIMUM DISTANCE FROM AN |
| | ASSUMED PROPERTY LINE WOULD BE 10 FEET TO AN ASSUMED |
| | PROPERTY LINE OR 20 FEET FROM ONE BUILDING TO ANOTHER. |
| | THE SITE PLAN INDICATES AN AREA WHERE TWO MORE UNITS |
| | MAY BE BROUGHT IN, THIS MAY NEED TO BE ADDRESSED AT |
| | THIS TIME AS FAR AS THE SQUARE FOOTAGE THAT WOULD BE |
| | ALLOWED AND THE ASSUMED PROPERTY LINE BETWEEN UNITS. |
| | THE 2007 FBC-B CODE COMMENTARY FIGURE 602A HAS MORE |
| | INFORMATION ON ASSUMED PROPERTY LINES. |
| | |
| | 4) PLEASE NOTE THAT SHEET 4 IS THE WRONG FOUNDATION |
| | PLAN THE REQUIREMENT FOR FOUNDATIONS IS OUT OF THE |
| | 2007/09 FBC-B AND THE REQUIREMENTS FOR DEPTH OF |
| | FOUNDATIONS |
| | 1805.2 IS STILL A MINIMUM OF 12 INCHES BELOW GRADE. |
| | PLEASE ALSO REVIEW 1805.5.7 FOR PIER FOUNDATIONS AND |
| | WIND SPEED. |
| | |
| | 5) PLEASE REVIEW SHEET # 1 OF SITE INSTALLED ITEMS |
| | PORTABLE FIRE EXTINGUISHERS, STORM SHUTTERS, GUTTERS & |
| | DOWN SPOUTS AND DRINKING FOUNTAINS. |
| | |
| | 6) STAGING PLAN DOES NOT PROVIDE DETAIL FOR THE |
| | HANDICAPPED PARKING AND ACCESS AILSE FBC11-4.6.2(1) & |
| | 11-4.6.4. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |