Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-25 Cont ID  
Sent By jwitmer Date 2012-01-25 Time 15:56 Rev Time 0.70
Received By jwitmer Date 2012-01-25 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-28 Cont ID  
Sent By jwitmer Date 2011-12-28 Time 15:42 Rev Time 0.50
Received By jwitmer Date 2011-12-28 Time 15:02 Sent To  
Notes
2011-12-28 15:46:07BUILDING PLAN REVIEW
 PERMIT: 11120478
 ADD: 3111 S DIXIE HWY
 CONT: FISHER CONTRACTING CORP
 TEL: (561)691-4716
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PERMIT APPLICATION INDICATES THE PERMIT VALUE OF
 $122,000. THE FLORIDA ACCESIBILITY CODE UNDER
 11-4.1.6(2) (2) ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION. IN ADDITION TO THE REQUIREMENTS OF
 SECTION 11-4.1.6(1), AN ALTERATION THAT AFFECTS OR
 COULD AFFECT THE USABILITY OF OR ACCESS TO AN AREA
 CONTAINING A PRIMARY FUNCTION SHALL BE MADE SO AS TO
 ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, THE PATH
 OF TRAVEL TO THE ALTERED AREA AND THE RESTROOMS,
 TELEPHONES, AND DRINKING FOUNTAINS SERVING THE ALTERED
 AREA, ARE READILY ACCESSIBLE TO AND USABLE BY
 INDIVIDUALS WITH DISABILITIES, UNLESS SUCH ALTERATIONS
 ARE DISPROPORTIONATE TO THE OVERALL ALTERATIONS TIN
 TERMS OF COST AND SCOPE.
  
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20 PERCENT OF THE COST OF THE ALTERATION
 TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 11-4.1.6(2)(1) WHEN THE COST OF ALTERATIONS NECESSARY
 TO MAKE THE PATH OF TRAVEL TO THE ALTERED AREA FULLY
 ACCESSIBLE IS DISPROPORTIONATE TO THE COST OF THE
 OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE MADE
 ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE ACCESSIBLE
 WITHOUT INCURRING DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS;
  
  
 1A) THE DISPROPORTIONATE COST ALLOWS FOR $24,400 IN
 MAKING THIS TENANT SPACE ACCESSIBLE. DOOR 103 DOES NOT
 HAVE THE 18 INCHES ON THE LATCH SIDE OFTHE DOOR.
  
 1B) IT IS NOT CLEAR AS TO WHICH OF THE RESTROOMS ARE TO
 BE THE ACCESSBILE RESTROOM
  
 1C) OPEN OFFICE SPACE FOUND ON SHEET A-1.0 & A-1.1 BOTH
 APPEAR TO HAVE A RAISED FLOOR DECK BUT NO VERTICAL
 ACCESSIBILITY (RAMPS) TO GAIN ACCESS.
 PLEASE REVIEW 11-4.8 RAMP REQUIREMENTS.
  
 2) DOOR # 103 SWINGS THE WRONG WAY FOR EGRESS WITH AN
 OCCUPANT LOAD OF 50 OR GREATER. FBC-B 1008.1.2.
  
 3) RAISED FLOORING SHEETS A-1.0, A-1.1 & A-3.0 DETAILS
 9 & 10 1003.5.2 . WHERE RAMPS ARE REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-01-06 Cont ID  
Sent By rlecky Date 2012-01-06 Time 16:14 Rev Time 0.00
Received By rlecky Date 2012-01-06 Time 16:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-01-31 Cont ID  
Sent By wjolin Date 2012-01-31 Time 11:02 Rev Time 0.00
Received By wjolin Date 2012-01-31 Time 10:37 Sent To  
Notes
2012-01-31 10:48:023111 SOUTH DIXIE HIGHWAY - SUITES 101, 101A, 101B &
 101C
 PERMIT #11120478
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 THIS WILL AFFECT DOOR #132.
  
 DOOR #144 SWINGS INTO THE CORRIDOR EGRESS PATH.
  
 ELECTRICAL DRAWINGS TO COORDINATE EXIT SIGN LOCATIONS
 AND CHEVRONS WITH LIFE SAFETY PLANS.
  
 SHEET E2.1 THE EXIT SIGN IN CORRIDOR #107 IS LEADING TO
 A DEAD END CORRIDOR. PROVIDE EXIT SIGN IN VESTIBULE
 #103.
  
 SHEET E2.1.1 THE EXIT SIGN IN CORRIDOR #123 IS LEADING
 TO OFFICE #130.
  
 PROVIDE FIRE ALARM NOTIFICATION APPLIANCE LAYOUT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-12-20 Cont ID  
Sent By wjolin Date 2011-12-20 Time 14:14 Rev Time 0.00
Received By wjolin Date 2011-12-20 Time 13:33 Sent To  
Notes
2011-12-20 14:14:343111 SOUTH DIXIE HIGHWAY - SUITES 101, 101A, 101B &
 101C
 PERMIT #11120478
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 THIS WILL AFFECT DOOR #103 AND #132.
  
 DOOR #144 SWINGS INTO THE CORRIDOR EGRESS PATH.
  
 ELECTRICAL DRAWINGS TO COORDINATE EXIT SIGN LOCATIONS
 AND CHEVRONS WITH LIFE SAFETY PLANS.
  
 SHEET E2.1 THE EXIT SIGN IN CORRIDOR #107 IS LEADING TO
 A DEAD END CORRIDOR. PROVIDE EXIT SIGN IN VESTIBULE
 #103.
  
 SHEET E2.1.1 THE EXIT SIGN IN CORRIDOR #123 IS LEADING
 TO OFFICE #130.
  
 PROVIDE FIRE ALARM NOTIFICATION APPLIANCE LAYOUT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-31 Cont ID  
Sent By jwitmer Date 2012-01-31 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2012-01-23 Time 09:16 Sent To  
Notes
2012-01-24 09:17:28C15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By rmcdouga Date 2012-01-24 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2011-12-19 Time 17:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-01-11 Cont ID  
Sent By hmoser Date 2012-01-11 Time 09:13 Rev Time 0.00
Received By hmoser Date 2012-01-11 Time 08:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By jroach Date 2012-02-07 Time 15:13 Rev Time 0.00
Received By jroach Date 2012-02-03 Time 16:53 Sent To  
Notes
2012-02-07 15:15:49ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.07.2012
 PERMIT NO.: 11120478
 ADDRESS: 3111 SOUTH DIXIE HIGHWAY
 CONTRACTOR/CONTACT: FISHER CONTRACTING CORP.
 TELEPHONE NO.: 561.691.4716
 SCOPE OF REVIEW: TENANT BUILD-OUT FOR ADMINISTRATIVE
 OFFICE AND CUSTOMER SERVICE CENTER.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SUBJECT TENANT SPACE SHALL NOT BE USED FOR ANY
 SCHOOLS, COLLEGES, OR UNIVERSITIES. THE BUILD-OUT
 APPROVED HEREWITH SHALL BE FOR AN ADMINISTRATIVE OFFICE
 AND CUSTOMER SERVICE CENTER ONLY. NO TEACHING OR
 CLASSES SHALL OCCUR ON-SITE. THESE RESTRICTIONS SHALL
 ALSO BE NOTED REGARDING ANY FUTURE APPLICATION FOR A
 BUSINESS TAX/CERTIFICATE OF USE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-05 Cont ID  
Sent By jroach Date 2012-01-05 Time 12:43 Rev Time 0.00
Received By jroach Date 2012-01-03 Time 14:22 Sent To  
Notes
2012-01-05 12:43:46ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.05.2012
 PERMIT NO.: 11120478
 ADDRESS: 3111 SOUTH DIXIE HIGHWAY #101A-C
 CONTRACTOR/CONTACT: JEFF FISHER
 TELEPHONE NO.: 561.691.9716
 SCOPE OF REVIEW: TENANT IMPROVEMENTS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-272 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), "SCHOOLS,
 COLLEGES AND UNIVERSITIES", ARE PROHIBITED WITHIN THE
 OFFICE COMMERCIAL (OC) ZONING DISTRICT. ACCORDING TO
 THE NORTH AMERICAN INDUSTRY CLASSIFICATION SYSTEM,
 INSTITUTIONS FURNISHING ACADEMIC COURSES AND GRANTING
 DEGREES AT BACCALUAUREATE OR GRADUATE LEVELS,
 REGARDLESS OF THE INSTRUCTIONAL SETTING (I.E.
 EDUCATIONAL INSTITUTION, HOME, TELEVISION, INTERNET, OR
 OTHER DISTANCE-LEARNING METHODS), ARE CLASSIFIED AS
 "COLLEGES, UNIVERSITY, AND PROFESSIONAL SCHOOLS".
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved