| Plan Review Stops For Permit 11120399 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-02-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-01 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-01 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2011-12-15 09:37:08 | PER JAMES SCHUCKMAN, HUSBAND OF OWNER), ADDRESSING WILL | | | BE CHANGING ADDR AFTER DEMO IS COMPLETE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-02-10 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-02-10 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2014-02-10 12:07:15 | ****CORRECTIONS**** | | | ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D. | | | LAING DATED 1/28/14 AND PLANS ON FILE*** | | | ****3RD REVIEW (SOME COMMENTS REVISED)**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | CFM US-12-06546 | | | 561-805-6724 | | | [email protected] | | | | | | 1. OK | | | | | | 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS | | | WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN | | | SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE | | | ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH | | | WERE INSTALLED. | | | | | | 3. N/A | | | | | | 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES | | | OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE | | | ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT | | | 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES | | | PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR | | | REVISE. NOTE THAT THIS IS TO BE NET AREA. | | | | | | 5-9. OK | | | | | | | | | | | | | | | INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO | | | CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL | | | INFORMATION) : | | | | | | NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE | | | (REVISED) SHEET A-1. BASED ON THE ELEVATION | | | CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE | | | GARAGE SLAB. | | | | | | FLOOD VENT INSTALLATION ON PLAN (SEE REVISION | | | #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO | | | FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY | | | INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE | | | ITEM 2) | | | | | | FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME | | | (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510) | | | AND THE EVALUATION REPORT NUMBER (ESR-2074). | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2014-01-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-01-22 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-01-22 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2014-01-22 14:14:13 | ****CORRECTIONS**** | | | ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D. | | | LAING DATED 12/9/13 AND PLANS ON FILE*** | | | ****2ND REVIEW (SOME COMMENTS REVISED)**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | CFM US-12-06546 | | | 561-805-6724 | | | [email protected] | | | | | | 1. SHEET A-1 SHOWS GARAGE AS 534 SF, BUT ELEVATION | | | CERTIFICATE A9(A) STATES GARAGE IS 400 SF. PLEASE | | | CORRELATE. NOTE THAT INSTRUCTIONS STATE TO TAKE | | | MEASUREMENTS FROM THE OUTSIDE OF THE GARAGE. | | | | | | 2ND REVIEW, PLEASE PROVIDE EXPLANATION AS TO WHY THE | | | SQUARE FOOT AREA OF GARAGE IS LESS THAN THE PLAN. THE | | | DIMENSIONS OF THE LAUNDRY AREA IS 8' X 3'8" (APPROX 30 | | | SF). PLANS SHOWS A 534 SF GARAGE, BUT ITEM A9(A) IS | | | 474. IF ELEVATION C | | | | | | 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS | | | WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN | | | SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE | | | ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH | | | WERE INSTALLED. | | | | | | 3. N/A | | | | | | 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES | | | OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE | | | ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT | | | 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES | | | PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR | | | REVISE. NOTE THAT THIS IS TO BE NET AREA. | | | | | | 5-6. OK | | | | | | 7. ITEM C2 (E), EQUIPMENT IS INSTALLED AT 7.4', MUST BE | | | 7.5' MINIMUM. | | | | | | 8-9. OK | | | | | | | | | INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO | | | CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL | | | INFORMATION) : | | | | | | NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE | | | (REVISED) SHEET A-1. BASED ON THE ELEVATION | | | CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE | | | GARAGE SLAB. | | | | | | FLOOD VENT INSTALLATION ON PLAN (SEE REVISION | | | #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO | | | FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY | | | INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE | | | ITEM 2) | | | | | | FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME | | | (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510) | | | AND THE EVALUATION REPORT NUMBER (ESR-2074). | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2014-01-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-01-05 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-01-05 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2014-01-05 12:45:34 | ****CORRECTIONS**** | | | ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D. | | | LAING DATED 12/9/13 AND PLANS ON FILE*** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | CFM US-12-06546 | | | 561-805-6724 | | | [email protected] | | | | | | 1. SHEET A-1 SHOWS GARAGE AS 534 SF, BUT ELEVATION | | | CERTIFICATE A9(A) STATES GARAGE IS 400 SF. PLEASE | | | CORRELATE. NOTE THAT INSTRUCTIONS STATE TO TAKE | | | MEASUREMENTS FROM THE OUTSIDE OF THE GARAGE. | | | | | | 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS | | | WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN | | | SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE | | | ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH | | | WERE INSTALLED. | | | | | | 3. N/A | | | | | | 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES | | | OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE | | | ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT | | | 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES | | | PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR | | | REVISE. NOTE THAT THIS IS TO BE NET AREA. | | | | | | 5. ITEM B6, FIRM INDEX DATE IS INCORRECT (SHOULD BE | | | MARCH 1, 1979). | | | | | | 6. ITEM B7, FIRM PANEL IS INCORRECT (SHOULD BE MARCH 1, | | | 1979). | | | | | | 7. ITEM C2 (E), EQUIPMENT IS INSTALLED AT 6.5', MUST BE | | | 7.5' MINIMUM. | | | | | | 8. IN COMMENTS, EQUIPMENT IS NOTED AS AIR CONDITIONER | | | PAD. THIS "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE | | | IS TO BE DONE AFTER ALL EQUIPMENT AND FINAL GRADING HAS | | | BEEN DONE, SEE INSTRUCTIONS. | | | | | | PROVIDE ELEVATIONS FOR THE FOLLOWING ITEMS: | | | | | | CONDENSING UNIT (NOT THE CONCRETE PAD) | | | WATER HEATER LOCATED IN GARAGE | | | AIR HANDLER LOCATED IN GARAGE | | | ANY OTHER EQUIPMENT SERVICING THE BUILDING | | | | | | ALL ITEMS SHOULD BE NOTED IN "COMMENTS" SECTION | | | INCLUDING LOCATION AND PLATFORM INFORMATION IF | | | APPLICABLE, SEE EC INSTRUCTIONS. | | | | | | 9. ITEM C2(H) STATES "N/A" BUT PLANS SHOW THREE SETS OF | | | STAIRS, PLEASE CORRELATE. | | | | | | 10. SECTION D, IF LAT/LONG PROVIDED BY A SURVEYOR, | | | SOURCE OF INFORMATION TO BE NOTED IN COMMENTS SECTION, | | | SEE INSTRUCTIONS. | | | | | | | | | INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO | | | CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL | | | INFORMATION) : | | | | | | NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE | | | (REVISED) SHEET A-1. BASED ON THE ELEVATION | | | CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE | | | GARAGE SLAB. | | | | | | FLOOD VENT INSTALLATION ON PLAN (SEE REVISION | | | #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO | | | FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY | | | INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE | | | ITEM 2) | | | | | | FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME | | | (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510) | | | AND THE EVALUATION REPORT NUMBER (ESR-2074). | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2012-05-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-22 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-16 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2012-05-22 10:48:15 | BUILDING PROVISO | | | REVISION REQUIRED | | | | | | 1) SUBMIT REVISED PLANS SHOWING THAT THE ATTACHED | | | GARAGE HAS A FINISHED FLOOR ELEVATION OF 7.5 FEET OR IS | | | DESIGNED IN COMPLIANCE WITH NFIP REGULATIONS AND FEMA | | | REQUIREMENTS FOR ENCLOSED GARAGES AND NON-HABITABLE | | | SPACES WITH FLOORS BELOW BFE. NOTE: NO EQUIPMENT OR | | | MATERIALS THAT ARE NOT FLOOD DAMAGE-RESISTANT ARE | | | ALLOWED BELOW THE BFE. | | | WWW.FEMA.GOV/LIBRARY/FILE?TYPE=PUBLISHEDFILE&FILE=FEMA. | | | | | | NOTE: THE TRUSS DRAWINGS AND LAYOUT THAT WAS SUBMITTED | | | IS FOR THE 2010 FBC AND ASCE7-10. PROVIDE TRUSS DRAWING | | | AND LAYOUT DESIGNED TO THE 2007 FBC AND ASCE 7-05 TO | | | CORRESPOND WITH THE BUILDINGS DESIGN TO THE STRUCTURAL | | | INSPECTOR IN THE FIELD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-02-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-01 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-24 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2012-01-31 14:57:23 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY THE PROPOSED FINISHED FLOOR ELEVATIONS ON | | | THE PLANS. THE MINIMUM F.F. ELEVATION FOR THIS PROJECT | | | IS 7.5' BFE. SEE CITY AMENDMENTS 106.1.1 AND WPB | | | MUNICIPAL CODE. | | | | | | 2) ON SHEET A-7 R-19 SPRAY FOAM INSULATION AND A | | | NON-VENTED ATTIC IS SPECIFIED AND ON THE ENERGY | | | CALCULATION FORM SPECIFIES A VENTED ATTIC WITH R-30 | | | INSULATION. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 | | | | | | 3) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE | | | SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBC R314 | | | | | | 4)THE COMPONENT AND CLADDING PRESSURES SPECIFIED FOR | | | THE DOORS AND WINDOWS ARE TOO LOW FOR 140 MPH, EXPOSURE | | | CATEGORY C WITH A MEAN ROOF HEIGHT OF 30 FEET. FOR | | | EXAMPLE THE 20 SQFT WINDOWS IN WALL ZONE 5 ARE LISTED | | | AS +45.2, -58.9 PSF AND THEY SHOULD BY +47.2,-61.7 PSF. | | | PLEASE REVIEW THE PRESSURES. FBC R301.2.1 | | | | | | 5) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE | | | INTER-COASTAL WATERWAY, THEREFORE, FBC R301.2.1.4.3 | | | REQUIRES THE ROOF TO WALL AND ROOF SHEATHING UPLIFT | | | LOADS TO BE INCREASED BY 20 PERCENT. SHOW COMPLIANCE. | | | | | | 6) THE ENERGY CALCULATION FORMS SPECIFY R-5 WALL | | | INSULATION AND SHEET A-7 OF THE PLANS HAS R3.3. PLEASE | | | CORRECT. | | | | | | 7) THE ROOF ZONE DIAGRAM ON SHEET A-8 IS INCORRECT. THE | | | CORNERS OF THE ROOFS ARE ZONE 3, INCLUDING HIP ROOFS. | | | PLEASE CORRECT. SEE FBCR FIGURE R301.2(7). | | | | | | 8) SPECIFY THE WATERPROOFING ASSEMBLY THAT WILL BE | | | INSTALLED ON THE BALCONIES. TWO LAYERS OF 30# FELT | | | BETWEEN THE CDX SHEATHING AND CEMENT BOARD IS NOT | | | ACCEPTABLE. FBC R903 | | | | | | 9) SPECIFY THE TYPE OF WELDS THAT WILL BE USED TO | | | ATTACH THE BASE AND CAPS TO THE TUBE STEEL COLUMNS. | | | CITY AMENDMENTS 106.1.1 | | | | | | 10) SHOW COMPLIANCE WITH FBC R311.4.3 FOR MINIMUM | | | DIMENSION REQUIREMENTS OF LANDINGS THAT ARE REQUIRED AT | | | EXTERIOR DOORS. | | | | | | 11) PROVIDE A TRUSS ANCHOR SCHEDULE. SPECIFY TRUSS | | | ANCHORS AND UPLIFT PRESSURES. FBCR802.1.6.5 | | | | | | 12) SHOW COMPLIANCE WITH FBC R 309.2 FOR GARAGE | | | SEPARATION FROM HABITABLE ROOMS LOCATED ABOVE. | | | | | | 13) SHOW COMPLIANCE WITH FBC R 313.4 FOR CARBON | | | MONOXIDE ALARMS. | | | | | | 14) THE COMPONENT & CLADDING PRESSURES FOR THE OVERHEAD | | | GARAGE DOOR AND THE DOOR FROM THE MASTER BEDROOM TO THE | | | BALCONY ARE NOT SPECIFIED ON THE PLANS. PLEASE PROVIDE. | | | FBC R301.2.1 | | | | | | 15) THE FOLLOWING PRODUCT APPROVALS HAVE BEEN | | | SUPERSEDED: NOA NO.10-0819.05 MULLIONS, NOA NO. | | | 07-0629.10 FRENCH DOORS AND NOA NO. 08-0820.14 SINGLE | | | HUNG WINDOWS. SUBMIT CURRENT PRODUCT APPROVALS. DCA | | | RULE 9N-3. NOAS CAN BE FOUND AT THE FOLLOWING WEBSITE: | | | HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP | | | | | | 16) THE PRODUCT APPROVAL FOR THE DOUBLE OUTSWING STEEL | | | DOORS, NOA NO.07-0509.07, ARE LIMITED TO A MAXIMUM | | | HEIGHT OF 6' 8" FOR DOUBLE DOORS AND 7'0" FOR SINGLE | | | DOORS. THE PLANS SPECIFY 8'0" DOORS. PLEASE CORRECT. | | | | | | 17) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS, | | | NOA NO. 08-0820.15, HAS A MAXIMUM SIZE LIMIT OF 63" X | | | 31.5" FOR THE ARCHED WINDOWS AND 48" X 62" FOR THE | | | RECTANGULAR WINDOWS. THE ONES ON THE PLANS ARE LARGER. | | | PLEASE CORRECT. | | | | | | 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 48" | | | ROUND FIXED GLASS WINDOW, AS REQUIRED BY DCA RULE 9N-3. | | | | | | 19) PLEASE SUBMIT A RESPONSE LETTER THAT INDICATES HOW | | | EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2012-05-23 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-05-23 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-23 |
Time |
14:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2012-05-16 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-05-16 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-16 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-05-23 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-05-23 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-16 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-01-18 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-01-18 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-01-17 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2012-01-18 17:47:52 | 11120399 | | | 103 ARLINGTON PL | | | CONSTRUCT A NEW SFD | | | | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED | | | WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC 210.12 | | | CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF | | | ALL SLEEPING AREAS. FBC R313 | | | MINIMUM SIZE ELECTRIC SERVICE CONDUCTORS ARE 3/0 COPPER | | | OR 250 MCM ALUMINUM. NEC T. 310.15 (B) (6) | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND NEC 250.94 | | | BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | TAMPER RESISTANCE RECEPTACLES ARE REQUIRED. NEC 406.11 | | | NEC | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2012-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-01-31 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-31 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2012-01-31 10:16:52 | SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR | | | A GAS PERMIT. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2012-05-29 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2012-05-29 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2012-05-29 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2012-05-29 10:41:34 | DEMO OK - NOT HISTORIC |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-02-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2014-02-10 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2014-01-31 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2014-01-31 11:08:11 | INCOMING SENT TO S. H. DESK. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-05-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-22 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-03 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2012-05-14 14:23:30 | MOVED PLANS TO R--23 | | 2012-05-03 14:19:10 | INCOMING SENT TO R-8. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-02-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-01 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2011-12-15 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2011-12-16 17:15:58 | SENT TO R8 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2012-05-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-23 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-23 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2012-05-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-22 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-05-22 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2012-05-22 11:45:04 | OWNER WILL TAKE ONE SET OF PLANS TO COUNTY FOR IMPACT | | | FEE REVIEW AND RETURN STAMPED PLANS AND COPY OF PAID | | | RECEIPT. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2012-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-01-31 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-31 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2012-01-31 10:10:31 | AN IMPACT FEE REVIEW WILL BE REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2012-05-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-21 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-21 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2012-05-21 15:43:35 | REVISION REQUIRED | | | | | | THE LAUNDRY ROOM IS A PROHIBITED SOURCE OF RETURN AIR | | | PER FBCR M1602.2. THE HVAC RETURN CAN NOT SERVE AS A | | | SOURCE OF MAKE UP AIR FOR THE GAS DRYER PER FBCR | | | M1701.1. SUBMIT A REVISED PLAN SHOWING AN APPROVED | | | SOURCE OF COMBUSTION AIR FOR THE GAS DRYER AS SPECIFIED | | | IN FBCR M1701.1. NOTE: A LOUVER DOOR ON THE LAUNDRY | | | ROOM WOULD BE ACCEPTABLE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2012-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-01-31 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-31 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2012-01-31 11:43:40 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED | | | BY THE OWNER/AGENT. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | | PLANS THAT CORRESPONDS WITH THE EQUIPMENT SIZING | | | CALCULATIONS. SPECIFY THE SERIAL NUMBERS OF THE | | | EQUIPMENT THAT WILL BE USED. | | | | | | 3) FBCR M1602.4 REQUIRES TRANSFER DUCTS TO TO BE ONE | | | AND ONE HALF TIMES THE CROSS SECTIONAL AREA OF THE | | | SUPPLY DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND | | | THE DOOR HAVING AT LEAST AN UNRESTRICTED 1 INCH | | | UNDERCUT TO ACHIEVE PROPER RETURN AIR BALANCE. | | | | | | 4) SHOW COMPLIANCE WITH FBCR G2407 (304) AND G2439.4 | | | (614.5) AS TO HOW MAKEUP AIR FOR THE GAS DRYER WILL BE | | | PROVIDED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-05-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-05-21 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-05-21 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2012-01-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-01-26 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-26 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2012-01-31 09:13:31 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) FBCR P 3108.2 STATES THAT IN A HORIZONTAL WET- VENT | | | SYSTEM, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN | | | SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE | | | DRAIN. TWO SECOND FLOOR BATHROOMS AND THE FIRST FLOOR | | | BATH AND LAUNDRY DO NOT COMPLY. | | | | | | 2) SHEET A-1 SHOWS A WET BAR ON THE FIRST FLOOR THAT IS | | | NOT INDICATED ON THE PLUMBING RISER PLAN ON SHEET S-1. | | | PLEASE CORRECT. CITY AMENDMENTS 106.1.1 | | | | | | 3) THE PLUMBING RISER PLANS SHOWS AN EXTRA LAVATORY AND | | | WATER CLOSET THAT IS NOT SHOWN ON THE ARCHITECTURAL | | | DRAWINGS. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2014-02-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-02-13 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-02-13 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2014-02-13 15:30:20 | SUBMITTED LETTER FROM ARCHITECT CHANGING THE NUMBER OF | | | FLOOD VENTS (SMART VENTS) IN THE GARAGE FROM FOUR TO | | | THREE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2012-05-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2012-05-15 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2012-05-15 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2012-05-15 13:03:55 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.15.2012 | | | PERMIT NO.: 11120399 | | | ADDRESS: 103 ARLINGTON ROAD | | | CONTRACTOR/CONTACT: JAMES SCHEICKMAN | | | TELEPHONE NO.: 561.358.5192 | | | SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | (CO): | | | | | | A. ALL LANDSCAPE AND IRRIGATION PERMITS SHALL BE ISSUED | | | AND ALL MATERIAL SHALL BE INSTALLED AND INSPECTED. | | | | | | B. SEPARATE PERMITS SHALL BE OBTAINED FOR THE POOL AND | | | SURROUNDING CONCRETE AND ALL MATERIAL SHALL BE | | | INSTALLED AND INSPECTED. | | | | | | 2. IN NO CIRCUMSTANCE SHALL THE OVERALL HEIGHT OF THE | | | BUILDING (AS MEASURED FROM GRADE TO THE MEAN POINT OF | | | THE PITCHED ROOF) EXCEED 30 FEET. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3366 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.CITYOFWPB.COM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2012-05-14 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2012-05-14 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2012-05-11 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2012-05-14 14:08:15 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.14.2012 | | | PERMIT NO.: 11120399 | | | ADDRESS: 103 ARLINGTON PLACE | | | CONTRACTOR/CONTACT: JAMES SCHUCKMAN | | | TELEPHONE NO.: 561.358.5192 | | | SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. THE MAXIMUM BUILDING HEIGHT SHALL NOT EXCEED 30 | | | FEET. MAXIMUM BUILDING HEIGHT SHALL BE MEASURED FROM | | | GRADE TO THE MEAN POINT OF THE PITCHED ROOF...NOT FROM | | | FINISHED FLOOR. | | | | | | 2. PRIOR TO THE RELOCATION OR REMOVAL OF ANY EXISTING | | | LANDSCAPING, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT - | | | PLANNING DIVISION. | | | | | | 3. THE PROPOSED CONCRETE APRON SHALL BE SET BACK FROM | | | THE SOUTH PROPERTY LINE A MINIMUM OF FIVE (5) FEET TO | | | ALLOW DRAINAGE ON THE SUBJECT PROPERTY, AND NOT ONTO | | | THE PUBLIC SIDEWALK. PLEASE NOTE THAT ALL NONPAVED | | | AREAS SHALL BE LANDSCAPED WITH LIVING PLANT MATERIAL. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3366 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.CITYOFWPB.COM | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-01-03 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2012-01-03 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2011-12-29 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2012-01-03 14:13:22 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 01.02.2012 | | | PERMIT NO.: 11120399 | | | ADDRESS: 103 ARLINGTON PLACE | | | CONTRACTOR/CONTACT: JAMES SCHUCKMAN | | | TELEPHONE NO.: 561.358.5192 | | | SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. THE SITE PLAN (SHEET L-1) SHALL PROVIDE THE | | | FOLLOWING: | | | A. NORTH ARROW | | | B. STREET NAMES | | | C. DIMENSIONS OF PROPERTY LINES | | | | | | 2. THE MAXIMUM BUILDING HEIGHT SHALL NOT EXCEED 30 | | | FEET. MAXIMUM BUILDING HEIGHT SHALL BE MEASURED FROM | | | GRADE TO THE MEAN POINT OF THE PITCHED ROOF?.NOT FROM | | | FINISHED FLOOR. | | | | | | 3. PLEASE PROVIDE THE LOCATION OF ALL MECHANICAL | | | EQUIPMENT AND THE DIMENSIONS FROM SUCH EQUIPMENT TO THE | | | PROPERTY LINE. | | | | | | 4. A SEPARATE PERMIT APPLICATION WILL NEED TO BE | | | SUBMITTED FOR THE LANDSCAPING. THE LANDSCAPE PERMIT | | | APPLICATION SHALL PROVIDE A LANDSCAPE PLAN WITH THE | | | FOLLOWING: | | | A. A TABLE INDICATING THE SPECIES, SIZE, AND QUANTITY | | | OF PLANT MATERIAL. | | | B. IDENTIFY WHICH PLANTS ARE EXISTING AND WHICH ONES | | | ARE PROPOSED. | | | | | | 5. SHEET L-1 INDICATES THAT PLANT MATERIAL IS BEING | | | RELOCATED TO ACCOMMODATE THE LOCATION OF THE NEW | | | RESIDENCE. PRIOR TO THE RELOCATION OR REMOVAL OF ANY | | | EXISTING LANDSCAPING, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT ? | | | PLANNING DIVISION. | | | | | | 6. LANDSCAPING IS SHOWN WITHIN THE EXISTING 10 FOOT | | | EASEMENT ALONG THE NORTH PROPERTY LINE. ARE THESE | | | PLANTS EXISTING? PLANTS SHALL NOT BE INSTALLED WITHIN | | | THE EASEMENT WITHOUT WRITTEN CONSENT FROM ALL | | | APPLICABLE UTILITY COMPANIES. | | | | | | 7. PLEASE PROVIDE THE VISIBILITY TRIANGLE ON ALL PLANS, | | | AS DEFINED IN SECTION 94-305(E) OF THE CITY'S ZONING | | | AND LAND DEVELOPMENT REGULATIONS. NO OBJECTS BETWEEN 18 | | | INCHES AND 8 FEET IN HEIGHT SHALL BE LOCATED WITHIN | | | THIS AREA. PLEASE CONFIRM THAT ALL PROPOSED LANDSCAPING | | | CONFORMS TO THIS PROVISION. | | | | | | 8. THE EXISTING DRIVEWAY APRON WILL NEED TO BE REMOVED | | | AND REPLACED WITH THE PROPER SIDEWALK, CURB, ETC. | | | | | | 9. A SEPARATE PERMIT APPLICATION WILL NEED TO BE | | | SUBMITTED FOR THE IRRIGATION. | | | | | | 10. ALL LANDSCAPE AREAS ARE TO BE IRRIGATED WITH AT | | | LEAST 120 PERCENT COVERAGE. A NOTE ON SHEET I-1 | | | INDICATES THAT THOSE AREAS NOT COVERED BY DRIP | | | IRRIGATION WILL NOT BE PLANTED. PLEASE CLARIFY. THE | | | LAWN AREAS TO THE REAR AND SIDES OF THE HOUSE SHALL BE | | | PLANTED WITH SOME TYPE OF LIVE PLANT MATERIAL, AND | | | SHALL BE IRRIGATED IN ACCORDANCE WITH THE | | | ABOVE-REFERENCED IRRIGATION REQUIREMENTS. PLEASE | | | SPECIFY IN THE LANDSCAPE PLANS WHAT MATERIAL WILL BE | | | LOCATED IN THESE AREAS AND PROVIDE THE APPROPRIATE | | | IRRIGATION ON THE IRRIGATION PLANS. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, SENIOR PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3366 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1435 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.CITYOFWPB.COM | | | |
|
|