Plan Review Details - Permit 11120399
Plan Review Stops For Permit 11120399
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2012-02-01 Cont ID  
Sent By rmcdouga Date 2012-02-01 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2012-02-01 Time 11:33 Sent To  
Notes
2011-12-15 09:37:08PER JAMES SCHUCKMAN, HUSBAND OF OWNER), ADDRESSING WILL
 BE CHANGING ADDR AFTER DEMO IS COMPLETE

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2014-02-10 Cont ID  
Sent By shill Date 2014-02-10 Time 12:06 Rev Time 0.00
Received By shill Date 2014-02-10 Time 12:06 Sent To  
Notes
2014-02-10 12:07:15****CORRECTIONS****
 ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D.
 LAING DATED 1/28/14 AND PLANS ON FILE***
 ****3RD REVIEW (SOME COMMENTS REVISED)****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 CFM US-12-06546
 561-805-6724
 [email protected]
  
 1. OK
  
 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS
 WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN
 SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE
 ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH
 WERE INSTALLED.
  
 3. N/A
  
 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES
 OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE
 ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT
 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES
 PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR
 REVISE. NOTE THAT THIS IS TO BE NET AREA.
  
 5-9. OK
  
  
  
  
 INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO
 CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL
 INFORMATION) :
  
 NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE
 (REVISED) SHEET A-1. BASED ON THE ELEVATION
 CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE
 GARAGE SLAB.
  
 FLOOD VENT INSTALLATION ON PLAN (SEE REVISION
 #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO
 FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY
 INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE
 ITEM 2)
  
 FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME
 (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510)
 AND THE EVALUATION REPORT NUMBER (ESR-2074).
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-01-22 Cont ID  
Sent By shill Date 2014-01-22 Time 13:58 Rev Time 0.00
Received By shill Date 2014-01-22 Time 13:58 Sent To  
Notes
2014-01-22 14:14:13****CORRECTIONS****
 ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D.
 LAING DATED 12/9/13 AND PLANS ON FILE***
 ****2ND REVIEW (SOME COMMENTS REVISED)****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 CFM US-12-06546
 561-805-6724
 [email protected]
  
 1. SHEET A-1 SHOWS GARAGE AS 534 SF, BUT ELEVATION
 CERTIFICATE A9(A) STATES GARAGE IS 400 SF. PLEASE
 CORRELATE. NOTE THAT INSTRUCTIONS STATE TO TAKE
 MEASUREMENTS FROM THE OUTSIDE OF THE GARAGE.
  
 2ND REVIEW, PLEASE PROVIDE EXPLANATION AS TO WHY THE
 SQUARE FOOT AREA OF GARAGE IS LESS THAN THE PLAN. THE
 DIMENSIONS OF THE LAUNDRY AREA IS 8' X 3'8" (APPROX 30
 SF). PLANS SHOWS A 534 SF GARAGE, BUT ITEM A9(A) IS
 474. IF ELEVATION C
  
 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS
 WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN
 SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE
 ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH
 WERE INSTALLED.
  
 3. N/A
  
 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES
 OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE
 ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT
 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES
 PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR
 REVISE. NOTE THAT THIS IS TO BE NET AREA.
  
 5-6. OK
  
 7. ITEM C2 (E), EQUIPMENT IS INSTALLED AT 7.4', MUST BE
 7.5' MINIMUM.
  
 8-9. OK
  
  
 INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO
 CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL
 INFORMATION) :
  
 NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE
 (REVISED) SHEET A-1. BASED ON THE ELEVATION
 CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE
 GARAGE SLAB.
  
 FLOOD VENT INSTALLATION ON PLAN (SEE REVISION
 #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO
 FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY
 INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE
 ITEM 2)
  
 FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME
 (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510)
 AND THE EVALUATION REPORT NUMBER (ESR-2074).
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-01-05 Cont ID  
Sent By shill Date 2014-01-05 Time 10:58 Rev Time 0.00
Received By shill Date 2014-01-05 Time 10:57 Sent To  
Notes
2014-01-05 12:45:34****CORRECTIONS****
 ****BASED ON ELEVATION CERTIFICATE PREPARED BY MARK D.
 LAING DATED 12/9/13 AND PLANS ON FILE***
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 CFM US-12-06546
 561-805-6724
 [email protected]
  
 1. SHEET A-1 SHOWS GARAGE AS 534 SF, BUT ELEVATION
 CERTIFICATE A9(A) STATES GARAGE IS 400 SF. PLEASE
 CORRELATE. NOTE THAT INSTRUCTIONS STATE TO TAKE
 MEASUREMENTS FROM THE OUTSIDE OF THE GARAGE.
  
 2. A9 (B) STATES THAT THREE PERMANENT FLOOD OPENINGS
 WITHIN 1' ABOVE ADJACENT GRADE WERE INSTALLED. PLAN
 SHOWS THAT FOUR ARE REQUIRED. REVISE A-1. SUBMIT THE
 ICC EVALUATION REPORT FOR THE ENGINEERED VENTS WHICH
 WERE INSTALLED.
  
 3. N/A
  
 4. EC STATES IN A9(C) THAT THERE ARE 376 SQUARE INCHES
 OF NET AREA FLOOD OPENINGS. IT ALSO STATES THAT THREE
 ARE INSTALLED, AND THE EVALUATION REPORT FOR SMARTVENT
 1540-510 STATES THAT EACH VENT YIELDS 51 SQUARE INCHES
 PER VENT FOR VENTILATION. PROVIDE CALCULATIONS OR
 REVISE. NOTE THAT THIS IS TO BE NET AREA.
  
 5. ITEM B6, FIRM INDEX DATE IS INCORRECT (SHOULD BE
 MARCH 1, 1979).
  
 6. ITEM B7, FIRM PANEL IS INCORRECT (SHOULD BE MARCH 1,
 1979).
  
 7. ITEM C2 (E), EQUIPMENT IS INSTALLED AT 6.5', MUST BE
 7.5' MINIMUM.
  
 8. IN COMMENTS, EQUIPMENT IS NOTED AS AIR CONDITIONER
 PAD. THIS "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE
 IS TO BE DONE AFTER ALL EQUIPMENT AND FINAL GRADING HAS
 BEEN DONE, SEE INSTRUCTIONS.
  
 PROVIDE ELEVATIONS FOR THE FOLLOWING ITEMS:
  
 CONDENSING UNIT (NOT THE CONCRETE PAD)
 WATER HEATER LOCATED IN GARAGE
 AIR HANDLER LOCATED IN GARAGE
 ANY OTHER EQUIPMENT SERVICING THE BUILDING
  
 ALL ITEMS SHOULD BE NOTED IN "COMMENTS" SECTION
 INCLUDING LOCATION AND PLATFORM INFORMATION IF
 APPLICABLE, SEE EC INSTRUCTIONS.
  
 9. ITEM C2(H) STATES "N/A" BUT PLANS SHOW THREE SETS OF
 STAIRS, PLEASE CORRELATE.
  
 10. SECTION D, IF LAT/LONG PROVIDED BY A SURVEYOR,
 SOURCE OF INFORMATION TO BE NOTED IN COMMENTS SECTION,
 SEE INSTRUCTIONS.
  
  
 INSPECTOR TO VERIFY THE FOLLOWING (ITEMS SUBJECT TO
 CHANGE PURSUANT TO SUBMITTAL OF REVISION OR ADDITIONAL
 INFORMATION) :
  
 NO DRYWALL TO BE INSTALLED (IN GARAGE) BELOW 7'6", SEE
 (REVISED) SHEET A-1. BASED ON THE ELEVATION
 CERTIFICATE, NO DRYWALL ALLOWED FROM SLAB TO 1'4" ABOVE
 GARAGE SLAB.
  
 FLOOD VENT INSTALLATION ON PLAN (SEE REVISION
 #12060640, REVISED SHEET A1 DATED 4/9/12) SHOWS TWO
 FLOOD VENTS ON EACH EXTERIOR SIDE OF GARAGE; VERIFY
 INSTALLATION LOCATIONS. (NOTE CONFLICT WITH EC, SEE
 ITEM 2)
  
 FLOOD VENT HAS LABEL BEARING THE MANUFACTURER'S NAME
 (SMARTVENT PRODUCTS, INC.), THE MODEL NUMBER (1540-510)
 AND THE EVALUATION REPORT NUMBER (ESR-2074).
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-22 Cont ID  
Sent By rmcdouga Date 2012-05-22 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2012-05-16 Time 14:48 Sent To  
Notes
2012-05-22 10:48:15BUILDING PROVISO
 REVISION REQUIRED
  
 1) SUBMIT REVISED PLANS SHOWING THAT THE ATTACHED
 GARAGE HAS A FINISHED FLOOR ELEVATION OF 7.5 FEET OR IS
 DESIGNED IN COMPLIANCE WITH NFIP REGULATIONS AND FEMA
 REQUIREMENTS FOR ENCLOSED GARAGES AND NON-HABITABLE
 SPACES WITH FLOORS BELOW BFE. NOTE: NO EQUIPMENT OR
 MATERIALS THAT ARE NOT FLOOD DAMAGE-RESISTANT ARE
 ALLOWED BELOW THE BFE.
 WWW.FEMA.GOV/LIBRARY/FILE?TYPE=PUBLISHEDFILE&FILE=FEMA.
  
 NOTE: THE TRUSS DRAWINGS AND LAYOUT THAT WAS SUBMITTED
 IS FOR THE 2010 FBC AND ASCE7-10. PROVIDE TRUSS DRAWING
 AND LAYOUT DESIGNED TO THE 2007 FBC AND ASCE 7-05 TO
 CORRESPOND WITH THE BUILDINGS DESIGN TO THE STRUCTURAL
 INSPECTOR IN THE FIELD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-01 Cont ID  
Sent By rmcdouga Date 2012-02-01 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2012-01-24 Time 13:48 Sent To  
Notes
2012-01-31 14:57:232007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SPECIFY THE PROPOSED FINISHED FLOOR ELEVATIONS ON
 THE PLANS. THE MINIMUM F.F. ELEVATION FOR THIS PROJECT
 IS 7.5' BFE. SEE CITY AMENDMENTS 106.1.1 AND WPB
 MUNICIPAL CODE.
  
 2) ON SHEET A-7 R-19 SPRAY FOAM INSULATION AND A
 NON-VENTED ATTIC IS SPECIFIED AND ON THE ENERGY
 CALCULATION FORM SPECIFIES A VENTED ATTIC WITH R-30
 INSULATION. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1
  
 3) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBC R314
  
 4)THE COMPONENT AND CLADDING PRESSURES SPECIFIED FOR
 THE DOORS AND WINDOWS ARE TOO LOW FOR 140 MPH, EXPOSURE
 CATEGORY C WITH A MEAN ROOF HEIGHT OF 30 FEET. FOR
 EXAMPLE THE 20 SQFT WINDOWS IN WALL ZONE 5 ARE LISTED
 AS +45.2, -58.9 PSF AND THEY SHOULD BY +47.2,-61.7 PSF.
 PLEASE REVIEW THE PRESSURES. FBC R301.2.1
  
 5) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTER-COASTAL WATERWAY, THEREFORE, FBC R301.2.1.4.3
 REQUIRES THE ROOF TO WALL AND ROOF SHEATHING UPLIFT
 LOADS TO BE INCREASED BY 20 PERCENT. SHOW COMPLIANCE.
  
 6) THE ENERGY CALCULATION FORMS SPECIFY R-5 WALL
 INSULATION AND SHEET A-7 OF THE PLANS HAS R3.3. PLEASE
 CORRECT.
  
 7) THE ROOF ZONE DIAGRAM ON SHEET A-8 IS INCORRECT. THE
 CORNERS OF THE ROOFS ARE ZONE 3, INCLUDING HIP ROOFS.
 PLEASE CORRECT. SEE FBCR FIGURE R301.2(7).
  
 8) SPECIFY THE WATERPROOFING ASSEMBLY THAT WILL BE
 INSTALLED ON THE BALCONIES. TWO LAYERS OF 30# FELT
 BETWEEN THE CDX SHEATHING AND CEMENT BOARD IS NOT
 ACCEPTABLE. FBC R903
  
 9) SPECIFY THE TYPE OF WELDS THAT WILL BE USED TO
 ATTACH THE BASE AND CAPS TO THE TUBE STEEL COLUMNS.
 CITY AMENDMENTS 106.1.1
  
 10) SHOW COMPLIANCE WITH FBC R311.4.3 FOR MINIMUM
 DIMENSION REQUIREMENTS OF LANDINGS THAT ARE REQUIRED AT
 EXTERIOR DOORS.
  
 11) PROVIDE A TRUSS ANCHOR SCHEDULE. SPECIFY TRUSS
 ANCHORS AND UPLIFT PRESSURES. FBCR802.1.6.5
  
 12) SHOW COMPLIANCE WITH FBC R 309.2 FOR GARAGE
 SEPARATION FROM HABITABLE ROOMS LOCATED ABOVE.
  
 13) SHOW COMPLIANCE WITH FBC R 313.4 FOR CARBON
 MONOXIDE ALARMS.
  
 14) THE COMPONENT & CLADDING PRESSURES FOR THE OVERHEAD
 GARAGE DOOR AND THE DOOR FROM THE MASTER BEDROOM TO THE
 BALCONY ARE NOT SPECIFIED ON THE PLANS. PLEASE PROVIDE.
 FBC R301.2.1
  
 15) THE FOLLOWING PRODUCT APPROVALS HAVE BEEN
 SUPERSEDED: NOA NO.10-0819.05 MULLIONS, NOA NO.
 07-0629.10 FRENCH DOORS AND NOA NO. 08-0820.14 SINGLE
 HUNG WINDOWS. SUBMIT CURRENT PRODUCT APPROVALS. DCA
 RULE 9N-3. NOAS CAN BE FOUND AT THE FOLLOWING WEBSITE:
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
  
 16) THE PRODUCT APPROVAL FOR THE DOUBLE OUTSWING STEEL
 DOORS, NOA NO.07-0509.07, ARE LIMITED TO A MAXIMUM
 HEIGHT OF 6' 8" FOR DOUBLE DOORS AND 7'0" FOR SINGLE
 DOORS. THE PLANS SPECIFY 8'0" DOORS. PLEASE CORRECT.
  
 17) THE PRODUCT APPROVAL FOR THE FIXED GLASS WINDOWS,
 NOA NO. 08-0820.15, HAS A MAXIMUM SIZE LIMIT OF 63" X
 31.5" FOR THE ARCHED WINDOWS AND 48" X 62" FOR THE
 RECTANGULAR WINDOWS. THE ONES ON THE PLANS ARE LARGER.
 PLEASE CORRECT.
  
 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 48"
 ROUND FIXED GLASS WINDOW, AS REQUIRED BY DCA RULE 9N-3.
  
 19) PLEASE SUBMIT A RESPONSE LETTER THAT INDICATES HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2012-05-23 Cont ID  
Sent By rlecky Date 2012-05-23 Time 12:15 Rev Time 0.00
Received By rlecky Date 2012-05-23 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-05-16 Cont ID  
Sent By rlecky Date 2012-05-16 Time 09:57 Rev Time 0.00
Received By rlecky Date 2012-05-16 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-05-23 Cont ID  
Sent By rlecky Date 2012-05-23 Time 14:24 Rev Time 0.00
Received By rlecky Date 2012-05-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-18 Cont ID  
Sent By rlecky Date 2012-01-18 Time 17:46 Rev Time 0.00
Received By rlecky Date 2012-01-17 Time 13:00 Sent To  
Notes
2012-01-18 17:47:5211120399
 103 ARLINGTON PL
 CONSTRUCT A NEW SFD
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC 210.12
 CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN 10 FEET OF
 ALL SLEEPING AREAS. FBC R313
 MINIMUM SIZE ELECTRIC SERVICE CONDUCTORS ARE 3/0 COPPER
 OR 250 MCM ALUMINUM. NEC T. 310.15 (B) (6)
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 TAMPER RESISTANCE RECEPTACLES ARE REQUIRED. NEC 406.11
 NEC
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2012-01-31 Cont ID  
Sent By rmcdouga Date 2012-01-31 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2012-01-31 Time 10:14 Sent To  
Notes
2012-01-31 10:16:52SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR
 A GAS PERMIT.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-05-29 Cont ID  
Sent By fmittner Date 2012-05-29 Time 10:40 Rev Time 0.00
Received By fmittner Date 2012-05-29 Time 10:40 Sent To  
Notes
2012-05-29 10:41:34DEMO OK - NOT HISTORIC

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-10 Cont ID  
Sent By shill Date 2014-02-10 Time 12:07 Rev Time 0.00
Received By shill Date 2014-01-31 Time 11:07 Sent To  
Notes
2014-01-31 11:08:11INCOMING SENT TO S. H. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-22 Cont ID  
Sent By rmcdouga Date 2012-05-22 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2012-05-03 Time 14:18 Sent To  
Notes
2012-05-14 14:23:30MOVED PLANS TO R--23
2012-05-03 14:19:10INCOMING SENT TO R-8. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-01 Cont ID  
Sent By rmcdouga Date 2012-02-01 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2011-12-15 Time 17:14 Sent To  
Notes
2011-12-16 17:15:58SENT TO R8 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-05-23 Cont ID  
Sent By rmcdouga Date 2012-05-23 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2012-05-23 Time 15:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-05-23 Cont ID  
Sent By rmcdouga Date 2012-05-22 Time 11:43 Rev Time 0.00
Received By rlecky Date 2012-05-22 Time 11:43 Sent To  
Notes
2012-05-22 11:45:04OWNER WILL TAKE ONE SET OF PLANS TO COUNTY FOR IMPACT
 FEE REVIEW AND RETURN STAMPED PLANS AND COPY OF PAID
 RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-01-31 Cont ID  
Sent By rmcdouga Date 2012-01-31 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2012-01-31 Time 10:07 Sent To  
Notes
2012-01-31 10:10:31AN IMPACT FEE REVIEW WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-21 Cont ID  
Sent By rmcdouga Date 2012-05-21 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2012-05-21 Time 15:37 Sent To  
Notes
2012-05-21 15:43:35REVISION REQUIRED
  
 THE LAUNDRY ROOM IS A PROHIBITED SOURCE OF RETURN AIR
 PER FBCR M1602.2. THE HVAC RETURN CAN NOT SERVE AS A
 SOURCE OF MAKE UP AIR FOR THE GAS DRYER PER FBCR
 M1701.1. SUBMIT A REVISED PLAN SHOWING AN APPROVED
 SOURCE OF COMBUSTION AIR FOR THE GAS DRYER AS SPECIFIED
 IN FBCR M1701.1. NOTE: A LOUVER DOOR ON THE LAUNDRY
 ROOM WOULD BE ACCEPTABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-31 Cont ID  
Sent By rmcdouga Date 2012-01-31 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2012-01-31 Time 10:21 Sent To  
Notes
2012-01-31 11:43:402007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS THAT CORRESPONDS WITH THE EQUIPMENT SIZING
 CALCULATIONS. SPECIFY THE SERIAL NUMBERS OF THE
 EQUIPMENT THAT WILL BE USED.
  
 3) FBCR M1602.4 REQUIRES TRANSFER DUCTS TO TO BE ONE
 AND ONE HALF TIMES THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND
 THE DOOR HAVING AT LEAST AN UNRESTRICTED 1 INCH
 UNDERCUT TO ACHIEVE PROPER RETURN AIR BALANCE.
  
 4) SHOW COMPLIANCE WITH FBCR G2407 (304) AND G2439.4
 (614.5) AS TO HOW MAKEUP AIR FOR THE GAS DRYER WILL BE
 PROVIDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-05-21 Cont ID  
Sent By rmcdouga Date 2012-05-21 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2012-05-21 Time 14:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-01-26 Cont ID  
Sent By rmcdouga Date 2012-01-26 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2012-01-26 Time 09:11 Sent To  
Notes
2012-01-31 09:13:312007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) FBCR P 3108.2 STATES THAT IN A HORIZONTAL WET- VENT
 SYSTEM, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN. TWO SECOND FLOOR BATHROOMS AND THE FIRST FLOOR
 BATH AND LAUNDRY DO NOT COMPLY.
  
 2) SHEET A-1 SHOWS A WET BAR ON THE FIRST FLOOR THAT IS
 NOT INDICATED ON THE PLUMBING RISER PLAN ON SHEET S-1.
 PLEASE CORRECT. CITY AMENDMENTS 106.1.1
  
 3) THE PLUMBING RISER PLANS SHOWS AN EXTRA LAVATORY AND
 WATER CLOSET THAT IS NOT SHOWN ON THE ARCHITECTURAL
 DRAWINGS. PLEASE CORRECT. CITY AMENDMENTS 106.1.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-02-13 Cont ID  
Sent By rmcdouga Date 2014-02-13 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2014-02-13 Time 14:50 Sent To  
Notes
2014-02-13 15:30:20SUBMITTED LETTER FROM ARCHITECT CHANGING THE NUMBER OF
 FLOOD VENTS (SMART VENTS) IN THE GARAGE FROM FOUR TO
 THREE.

Review Stop Z ZONING
Rev No 3 Status P Date 2012-05-15 Cont ID  
Sent By jroach Date 2012-05-15 Time 13:03 Rev Time 0.00
Received By jroach Date 2012-05-15 Time 09:33 Sent To  
Notes
2012-05-15 13:03:55ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.15.2012
 PERMIT NO.: 11120399
 ADDRESS: 103 ARLINGTON ROAD
 CONTRACTOR/CONTACT: JAMES SCHEICKMAN
 TELEPHONE NO.: 561.358.5192
 SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (CO):
  
 A. ALL LANDSCAPE AND IRRIGATION PERMITS SHALL BE ISSUED
 AND ALL MATERIAL SHALL BE INSTALLED AND INSPECTED.
  
 B. SEPARATE PERMITS SHALL BE OBTAINED FOR THE POOL AND
 SURROUNDING CONCRETE AND ALL MATERIAL SHALL BE
 INSTALLED AND INSPECTED.
  
 2. IN NO CIRCUMSTANCE SHALL THE OVERALL HEIGHT OF THE
 BUILDING (AS MEASURED FROM GRADE TO THE MEAN POINT OF
 THE PITCHED ROOF) EXCEED 30 FEET.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 2 Status F Date 2012-05-14 Cont ID  
Sent By jroach Date 2012-05-14 Time 13:54 Rev Time 0.00
Received By jroach Date 2012-05-11 Time 13:42 Sent To  
Notes
2012-05-14 14:08:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.14.2012
 PERMIT NO.: 11120399
 ADDRESS: 103 ARLINGTON PLACE
 CONTRACTOR/CONTACT: JAMES SCHUCKMAN
 TELEPHONE NO.: 561.358.5192
 SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE MAXIMUM BUILDING HEIGHT SHALL NOT EXCEED 30
 FEET. MAXIMUM BUILDING HEIGHT SHALL BE MEASURED FROM
 GRADE TO THE MEAN POINT OF THE PITCHED ROOF...NOT FROM
 FINISHED FLOOR.
  
 2. PRIOR TO THE RELOCATION OR REMOVAL OF ANY EXISTING
 LANDSCAPING, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION.
  
 3. THE PROPOSED CONCRETE APRON SHALL BE SET BACK FROM
 THE SOUTH PROPERTY LINE A MINIMUM OF FIVE (5) FEET TO
 ALLOW DRAINAGE ON THE SUBJECT PROPERTY, AND NOT ONTO
 THE PUBLIC SIDEWALK. PLEASE NOTE THAT ALL NONPAVED
 AREAS SHALL BE LANDSCAPED WITH LIVING PLANT MATERIAL.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-03 Cont ID  
Sent By jroach Date 2012-01-03 Time 14:13 Rev Time 0.00
Received By jroach Date 2011-12-29 Time 14:43 Sent To  
Notes
2012-01-03 14:13:22ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.02.2012
 PERMIT NO.: 11120399
 ADDRESS: 103 ARLINGTON PLACE
 CONTRACTOR/CONTACT: JAMES SCHUCKMAN
 TELEPHONE NO.: 561.358.5192
 SCOPE OF REVIEW: NEW SINGLE FAMILY RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE SITE PLAN (SHEET L-1) SHALL PROVIDE THE
 FOLLOWING:
 A. NORTH ARROW
 B. STREET NAMES
 C. DIMENSIONS OF PROPERTY LINES
  
 2. THE MAXIMUM BUILDING HEIGHT SHALL NOT EXCEED 30
 FEET. MAXIMUM BUILDING HEIGHT SHALL BE MEASURED FROM
 GRADE TO THE MEAN POINT OF THE PITCHED ROOF?.NOT FROM
 FINISHED FLOOR.
  
 3. PLEASE PROVIDE THE LOCATION OF ALL MECHANICAL
 EQUIPMENT AND THE DIMENSIONS FROM SUCH EQUIPMENT TO THE
 PROPERTY LINE.
  
 4. A SEPARATE PERMIT APPLICATION WILL NEED TO BE
 SUBMITTED FOR THE LANDSCAPING. THE LANDSCAPE PERMIT
 APPLICATION SHALL PROVIDE A LANDSCAPE PLAN WITH THE
 FOLLOWING:
 A. A TABLE INDICATING THE SPECIES, SIZE, AND QUANTITY
 OF PLANT MATERIAL.
 B. IDENTIFY WHICH PLANTS ARE EXISTING AND WHICH ONES
 ARE PROPOSED.
  
 5. SHEET L-1 INDICATES THAT PLANT MATERIAL IS BEING
 RELOCATED TO ACCOMMODATE THE LOCATION OF THE NEW
 RESIDENCE. PRIOR TO THE RELOCATION OR REMOVAL OF ANY
 EXISTING LANDSCAPING, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED TO THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION.
  
 6. LANDSCAPING IS SHOWN WITHIN THE EXISTING 10 FOOT
 EASEMENT ALONG THE NORTH PROPERTY LINE. ARE THESE
 PLANTS EXISTING? PLANTS SHALL NOT BE INSTALLED WITHIN
 THE EASEMENT WITHOUT WRITTEN CONSENT FROM ALL
 APPLICABLE UTILITY COMPANIES.
  
 7. PLEASE PROVIDE THE VISIBILITY TRIANGLE ON ALL PLANS,
 AS DEFINED IN SECTION 94-305(E) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS. NO OBJECTS BETWEEN 18
 INCHES AND 8 FEET IN HEIGHT SHALL BE LOCATED WITHIN
 THIS AREA. PLEASE CONFIRM THAT ALL PROPOSED LANDSCAPING
 CONFORMS TO THIS PROVISION.
  
 8. THE EXISTING DRIVEWAY APRON WILL NEED TO BE REMOVED
 AND REPLACED WITH THE PROPER SIDEWALK, CURB, ETC.
  
 9. A SEPARATE PERMIT APPLICATION WILL NEED TO BE
 SUBMITTED FOR THE IRRIGATION.
  
 10. ALL LANDSCAPE AREAS ARE TO BE IRRIGATED WITH AT
 LEAST 120 PERCENT COVERAGE. A NOTE ON SHEET I-1
 INDICATES THAT THOSE AREAS NOT COVERED BY DRIP
 IRRIGATION WILL NOT BE PLANTED. PLEASE CLARIFY. THE
 LAWN AREAS TO THE REAR AND SIDES OF THE HOUSE SHALL BE
 PLANTED WITH SOME TYPE OF LIVE PLANT MATERIAL, AND
 SHALL BE IRRIGATED IN ACCORDANCE WITH THE
 ABOVE-REFERENCED IRRIGATION REQUIREMENTS. PLEASE
 SPECIFY IN THE LANDSCAPE PLANS WHAT MATERIAL WILL BE
 LOCATED IN THESE AREAS AND PROVIDE THE APPROPRIATE
 IRRIGATION ON THE IRRIGATION PLANS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved