Plan Review Details - Permit 11120396
Plan Review Stops For Permit 11120396
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By jwitmer Date 2012-02-07 Time 08:07 Rev Time 0.00
Received By jwitmer Date 2012-02-06 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-29 Cont ID  
Sent By jwitmer Date 2011-12-29 Time 09:44 Rev Time 2.00
Received By jwitmer Date 2011-12-29 Time 08:00 Sent To  
Notes
2011-12-29 10:47:04BUILDING PLAN REVIEW
 PERMIT: 11120396
 ADD: 1810 S DIXIE HWY
 CONT: MARTINO CONSTRUCTION CORP
 TEL: (561)632-2338
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE FIRST OF TWO ISSUES ARE, THERE APPEARS TO BE TWO
 TYPES OF OCCUPANCIES, RETAIL AND BUSINESS. 2007/09
 FBC-B TABLE 508.3.3 INDICATES NO SEPERATION IS
 REQUIRED.
 THE TRUE ISSUE IS IF THERE ARE TWO SEPERATE TENANTS,
 ONE FOR THE BUSINESS OCCUPANCY, THE OTHER FOR THE
 MERCANTILE OCCUPANCY. IF SO TENANT SEPERATION WILL BE
 REQUIRED.
 2007/09 FBC-B 708.1(7) WALLS SEPERATING INDIVIDUAL
 TENANT SEPERATION WALLS.
  
 2) TENANT SEPERATION WALLS (FIRE PARTITIONS) SHALL BE
 CONSTRUCTED TO THE ROOF DECK ABOVE. SHEET 2 INDICATES
 THE TENANT SEPERATION WALL STOPPING AT THE 12'-0"
 LEVEL.
 FBC-B 708.4 SEE CONTINUITY.
  
 3) PLEASE PROVIDE A DOOR SCHEDULE FOR PROTECTED
 OPENINGS ( RATED DOORS & WINDOWS) PER 2007 / 09 FBC-B
 TABLE 715.4.
  
 4) PLEASE NOTE ON PLANS AT DROPED CEILING SIDE OF RATED
 WALL: 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 5) PLEASE PROVIDE A THROUGH PENETRATION FIRE STOP
 SYSTEM (FBC-B 712.3.1.2 FOR RATED WALL ASSEMBLY.
  
 6) SHEET 3 INDICATESS ONE OF THE BUSINESS OCCUPANCIES
 MEANS OF EGRESS (EXIT SIGN) IS THROUGH THE MERCANTILE
 SECTION OF THE BUILDING. FBC-B 1014.2.1 MULTIPLE
 TENANTS.
 THE EXIT SIGN SHOULD BE REMOVED SINCE THE BUSINESS
 OCCUPANTS HAVE TO TRAVEL THROUGH THE MERCANTILE
 OCCUPANCY WHICH IS NOT UNDERTHEIR CONTROL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By rlecky Date 2012-02-09 Time 12:36 Rev Time 0.00
Received By rlecky Date 2012-02-09 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-04 Cont ID  
Sent By rlecky Date 2012-01-04 Time 14:53 Rev Time 0.00
Received By rlecky Date 2012-01-04 Time 10:11 Sent To  
Notes
2012-01-04 14:54:0611120396
  
 SHOW LOCATION OF ALL ELECTRICAL SERVICE EQUIPMENT ON
 THE PLAN. UNUSED ELECTRIC FIXTURES ETC. SHALL BE
 REMOVED. SOME RECEPTACLES ARE NOT SHOWN ON PLAN. IS
 THIS A NEW SERVICE OR EXISTING? DOES THE ELECTRIC
 SERVICE SHOWN PROVIDE POWER TO THE WHOLE BUILDING? NEC
 215.5
 ALL ELECTRICAL SERVICE DISCONNECTS SHALL BE GROUPED IN
 ONE LOCATION. NEC 230 72
 GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC WATER
 COOLER.
 GFCI PROTECTION IS REQUIRED FOR RECEPTACLES SERVING THE
 KITCHENETTE (NOT SHOWN). NEC 210.8
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE SERVICE.
 NEC 250.94
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By wjolin Date 2012-02-07 Time 14:23 Rev Time 0.00
Received By wjolin Date 2012-02-07 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-12-16 Cont ID  
Sent By wjolin Date 2011-12-16 Time 12:03 Rev Time 0.00
Received By wjolin Date 2011-12-16 Time 11:31 Sent To  
Notes
2011-12-16 12:03:361810 SOUTH DIXIE HIGHWAY
 PERMIT #11120396
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE. FOR SEPARATED USE,
 THE BUSINESS OCCUPANCY REQUIRES A TWO-HOUR FIRE
 SEPARATION FROM THE MERCANTILE OCCUPANCY PER TABLE
 6.1.14.4.1B OF NFPA 101 FLORIDA EDITION 2006.
  
 NOTE: A ONE-HOUR TENANT SEPARATION IS REQUIRED.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 OPENINGS AND PENETRATIONS THROUGH A FIRE-RATED WALL
 ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR
 DEVICE. REFERENCE SECTION 8.3.5.1 OF FLORIDA FIRE
 PREVENTION CODE - NFPA 101
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2011-12-28 Cont ID  
Sent By fmittner Date 2011-12-28 Time 10:16 Rev Time 0.00
Received By fmittner Date 2011-12-28 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-14 Cont ID  
Sent By hmoser Date 2012-02-14 Time 13:52 Rev Time 0.00
Received By hmoser Date 2012-01-27 Time 14:52 Sent To  
Notes
2012-01-30 15:00:43B-21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-09 Cont ID  
Sent By hmoser Date 2012-01-09 Time 14:13 Rev Time 0.00
Received By hmoser Date 2011-12-15 Time 17:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-14 Cont ID  
Sent By hmoser Date 2012-02-14 Time 13:52 Rev Time 0.00
Received By hmoser Date 2012-02-14 Time 13:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By hmoser Date 2012-01-09 Time 13:56 Rev Time 0.00
Received By hmoser Date 2012-01-09 Time 13:30 Sent To  
Notes
2012-01-09 14:12:31PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.PER
 SECTION 403.3 2007 FBC (M).
 2) SHOW FRESH AIR DUCT ON THE PLANS.
 3) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROL. 2007 ENERGY CODE.
 4) PROVIDE BATHROOM EXHAUST ON THE PLANS. PER SECTION
 402.3.1 FBC (M) 2007.
 5) PROVIDE EQUIPMENT SCHEDULE SHOWING SEER, VOLTAGE.
 6) PROVIDE COOLING LOAD CALCULATIONS WITH THE PLANS
 .PER SECTION 13-407.AB.1
 2007 ENERGY CODE.
 7) SHOW VOLUME DAMPERS ON THE PLANS. PER SECTION 603.17
 FBC(M) 2007
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2011-12-28 Cont ID  
Sent By fmittner Date 2011-12-28 Time 10:16 Rev Time 0.00
Received By fmittner Date 2011-12-28 Time 10:16 Sent To  
Notes
***NONE***