Plan Review Details - Permit 11120379
Plan Review Stops For Permit 11120379
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-22 Cont ID  
Sent By hmoser Date 2011-12-22 Time 14:02 Rev Time 0.00
Received By hmoser Date 2011-12-22 Time 14:02 Sent To  
Notes
2011-12-22 09:52:36INCOMING SENT TO MECH BOX < 5K. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-15 Cont ID  
Sent By hmoser Date 2011-12-15 Time 12:16 Rev Time 0.00
Received By hmoser Date 2011-12-14 Time 16:54 Sent To  
Notes
2011-12-14 16:54:42******************EXPEDITED*******************
 GAVE TO HAROLD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-12-22 Cont ID  
Sent By hmoser Date 2011-12-22 Time 13:58 Rev Time 0.00
Received By hmoser Date 2011-12-22 Time 13:54 Sent To  
Notes
2011-12-22 14:02:17PASS PROVISO
 REFER TO SECTION 601.4 BALANCED RETURN AIR.
 HAVE A COMPLETE SET OF INSTALLATION INSTRUCTIONS ON THE
 FIRE DAMPERS AT FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-12-15 Cont ID  
Sent By hmoser Date 2011-12-15 Time 11:58 Rev Time 0.00
Received By hmoser Date 2011-12-15 Time 11:58 Sent To  
Notes
2011-12-15 12:16:31PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 2) REFER TO SECTION 604.1 BALANCED RETURN AIR EXCEPTION
 # 1
 2007 FBC (M)
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM. AND
 SECTION 606.3 INSTALLATION.
 2007 FBC (M)
 4) REFER TO SECTION 606.4.1 SUPERVISION. 2007 FBC (M)
 5) PROVIDE A COPE OF THE FIRE DAMPER MANUFACTURE
 INSTALLATION INSTRUCTION
 WITH THE PLANS PER SECTION 607.2 2007 FBC ( M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]