| 2012-02-28 08:49:00 | BUILDING REVIEW COMMENTS FOR RE-SUBMITTAL: |
| | |
| | 1- FIRST FLOOR PLAN ON SHEET SHEET NO 1 SPECIFIES |
| | NON-AC STORAGE, WHILE FIRST FLOOR PLAN ON SHEET E-1 |
| | SPECIFIES STUDIO UNIT. ACCORDING TO PALM BEACH COUNTY |
| | REVIEW STAMP DATED 2/14/12 THE SCOPE OF WORK IS |
| | RENOVATION TO EXISTING STUDIO UNIT, WHICH IS THE ONE ON |
| | THE SECOND FLOOR AND THE TOTAL SQUARE FOOTAGE IS 360 |
| | SF. THEREFORE 1ST FLOOR IS STORAGE NO STUDIO UNIT. |
| | REVISE AS REQUIRED. PLEASE COORDINATE WITH ZONING. |
| | ALSO, CLARIFY IF SCOPE OF WORK IS ONLY FOR SECOND |
| | FLOOR. PLANS SUBMITTED SHOW WORK ON BOTH FLOORS. |
| | ***NOTE: IF THE INTENTION IS TO HAVE 2 DWELLING UNITS, |
| | THEN THIS MAY BE ACHIEVED BY GETTING THE PROPER ZONING |
| | APPROVALS, IMPACT FEES IF REQUIRED BY PALM BEACH COUNTY |
| | DEPENDING ON THE NUMBER OF UNITS AND BY PROVIDING THE |
| | PROPER DWELLING UNIT SEPARATION ON PLANS. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | |
| | A) FORM 1100B-07 SUBMITTED WAS REVISED IN MARCH 1ST OF |
| | 2009. NEED TO PROVIDE REVISED FORM 1100B-08. SEE SEC. |
| | N1100.3 |
| | B) ITEM #B(B) NEEDS TO BE COMPLETED. |
| | C) R-VALUE SPECIFIED ON ITEM 8(B) NEEDS TO BE REVISED. |
| | NEED R-13 MIN. SEE TABLE 11B-1 ON THE SECOND PAGE OF |
| | FORM SUBMITTED. |
| | D) R-VALUE SPECIFIED ON ITEM 9(B) NEEDS TO BE REVISED. |
| | NEED R-13 MIN. SEE TABLE 11B-1. |
| | E) CLARIFY AREA OF WORK. FIRST AND SECOND FLOOR. |
| | COORDINATE WITH ITEM #1 ABOVE. CHECK TOTAL SQUARE |
| | FOOTAGE. |
| | F) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM |
| | ALSO. |
| | |
| | 3- ORIGINAL COMMENT: PROVIDE COMPLETE DRAWINGS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE TENANT |
| | SEPARATION REQUIREMENTS OF SEC. R317.1. SPECIFY UL FIRE |
| | RATED ASSEMBLY OR ANY OTHER APPROVED ASSEMBLY. ANY |
| | PENETRATIONS NEED TO BE RATED AS REQUIRED BY SEC. |
| | R317.3. |
| | |
| | PLANS SUBMITTED DON'T SPECIFY ANY TESTED AND APPROVED |
| | ASSEMBLY. ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE |
| | WITH ASTM E 119. AND, FIRE-RESISTANCE-RATED |
| | FLOOR-CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND |
| | BE TIGHT AGAINST THE EXTERIOR WALL AS REQUIRED BY SEC. |
| | R317.1. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | SHOWING COMPLIANCE. PLEASE SPECIFY ANY UL OR DRYWALL |
| | APPROVED AND LISTED ASSEMBLY. |
| | ***NOTE: THIS NEED TO BE COORDINATED WITH ITEM #1 |
| | ABOVE. |
| | |
| | 4- ORIGINAL COMMENT: OPENINGS ARE NOT ALLOWED ON WALL |
| | THAT IS LESS THAN 3'-0" FROM THE PROPERTY LINE. SEE |
| | SEC. R302.1 AND REVISE OPENINGS ON WEST WALL THAT IS |
| | LESS THAN 3"-0" FROM THE PROPERTY LINE. IN ADDITION |
| | NEED TO SPECIFY FIRE RATED WALL AS REQUIRED BY SEC. |
| | R302.1. ONE HOUR FIRE RATING WITH EXPOSURE ON BOTH |
| | SIDES. SEE TABLE R302.1. |
| | |
| | PLANS SUBMITTED DELETED THE WINDOWS. NEED TO SPECIFY |
| | FIRE RATED WALL AS REQUIRED BY SEC. R302.1. COORDINATE |
| | WITH ITEM #1 ABOVE. |
| | |
| | 5- ORIGINAL COMMENT: PROVIDE COMPLETE INFORMATION FOR |
| | STAIRWAY HANDRAILS AND GUARDRAILS TO SHOW COMPLIANCE |
| | WITH SEC. R311.5.6 THRU SEC. R311.5.6.3 AND SEC. R312. |
| | IN ADDITION THE GUARDRAIL AND HANDRAIL NEED TO COMPLY |
| | WITH THE DESIGN LOADS OF TABLE R301.5. PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS. ALSO, NEED TO PROVIDE |
| | FRAMING DETAILS FOR STAIRS TOP LANDING. ALSO, SPECIFY |
| | COMPLIANCE WITH THE STAIR CONSTRUCTION AS REQUIRED BY |
| | SEC. R311.2. |
| | |
| | A) PLANS SUBMITTED DON'T PROVIDE ANY DETAILS/ |
| | SPECIFICATIONS FOR THE HANDRAIL AND GUARDRAIL |
| | CONSTRUCTION SHOWING COMPLIANCE WITH THE LOADS OF TABLE |
| | R301.5. |
| | B) THE RISER AND TREAD RATIO SHOWN ON STAIR DETAIL ON |
| | SHEET NO 2 DOESN'T COMPLY WITH SEC. R311.5.3.2. |
| | C) HANDRAIL AND GUARDRAIL HEIGHTS ARE NOT GIVEN. SEC. |
| | R311.5.6.1 AND SEC. R312.1. |
| | D) HOW IS THE 2X TOP LANDING LEDGER ATTACHED TO |
| | EXISTING WALL?. NO INFORMATION WAS GIVEN. |
| | E) HOW ARE THE 3-2X12 STRINGERS ATTACHED TO THE BASE? |
| | F) THERE ARE NO SPECIFICATIONS FOR FINISHED DECK ON TOP |
| | LANDING. SPECIFY DECK TYPE AND FASTENING. |
| | |
| | 6- ORIGINAL COMMENT: PROVIDE PRODUCT APPROVAL (2 |
| | COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR: |
| | A) EXTERIOR DOORS. DESIGN PRESSURES SHOWN ON THE |
| | FLORIDA PRODUCT APPROVAL FL11321.1 SUBMITTED DON'T MEET |
| | THE DESIGN PRESSURES CALCULATED BY THE ENGINEER ON |
| | SHEET 2. |
| | |
| | NO PRODUCT APPROVAL WAS SUBMITTED. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. |
| | |
| | NO PRODUCT APPROVALS SUBMITTED. PROVIDE PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC |
| | CONNECTOR ONLY. |
| | |
| | C) WINDOWS PRODUCT APPROVAL FL10350.18 SUBMITTED |
| | DOESN'T MEET THE ENGINEER REVISED DESIGN PRESSURES |
| | SHOWN ON SHEET NO 2. NEED PRODUCT APPROVAL THAT MEETS |
| | THE CALCULATED DESIGN PRESSURES. |
| | |
| | 7- ORIGINAL COMMENT: ENGINEER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL |
| | PRODUCT APPROVALS, INCLUDING THE DOORS AND WINDOWS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS. |
| | |
| | NO DONE. |
| | |
| | 8- SHEET #1: |
| | A) EXISTING WALL SECTION: REVISE INSULATION R-VALUE |
| | SHOWN ON THE WALLS. COORDINATE WITH THE ENERGY |
| | CALCULATIONS. SEE ITEM #2 ABOVE. |
| | |
| | B) ORIGINAL COMMENT. REVISE TENANT SEPARATION WALL |
| | SECTION TO COMPLY WITH ITEM #3 ABOVE. AND, COORDINATE |
| | WITH INFORMATION SHOWN ON THE 2 STORY WALL SECTION. |
| | NEED TO COORDINATE INFORMATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |