Plan Review Details - Permit 11120372
Plan Review Stops For Permit 11120372
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-05-09 Cont ID  
Sent By jgomez Date 2012-05-08 Time 16:22 Rev Time 0.00
Received By jgomez Date 2012-05-08 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-04-13 Cont ID  
Sent By jgomez Date 2012-04-13 Time 16:41 Rev Time 0.00
Received By jgomez Date 2012-04-13 Time 16:41 Sent To  
Notes
2012-04-13 16:42:42RESIDENTIAL ALTERATION BUILDING REVIEW THIRD CHECKLIST.
  
 1- ENGINEER NEEDS TO SIGN AND SEAL BOTH SETS OF PLANS
 AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. ONLY ONE
 SET WAS SIGNED AND SEALED.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM
 ALSO.
  
 3- ORIGINAL COMMENT: PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE TENANT
 SEPARATION REQUIREMENTS OF SEC. R317.1. SPECIFY UL FIRE
 RATED ASSEMBLY OR ANY OTHER APPROVED ASSEMBLY. ANY
 PENETRATIONS NEED TO BE RATED AS REQUIRED BY SEC.
 R317.3.
 PLANS SUBMITTED DON'T SPECIFY ANY TESTED AND APPROVED
 ASSEMBLY. ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE
 WITH ASTM E 119. AND, FIRE-RESISTANCE-RATED
 FLOOR-CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL AS REQUIRED BY SEC.
 R317.1. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE. PLEASE SPECIFY ANY UL OR DRYWALL
 APPROVED AND LISTED ASSEMBLY.
  
 ENGINEER'S RESPONSE: UL ASSEMBLY U-419 AND GYPSUM
 ASSOCIATION ASSEMBLY WP1200 ARE FOR INTERIOR
 NON-BEARING PARTITIONS USING STEEL STUDS. THIS IS NOT
 THE TYPE OF CONSTRUCTION FOR THIS BUILDING. PROVIDE
 COMPLETE AND CORRECT SPECIFICATIONS FOR TYPE OF
 CONSTRUCTION IN THIS BUILDING.
  
 ***NOTE: ENGINEER TO REVIEW FLORIDA STATUTE
 553.80(2)(B) REGARDING DESIGN PROFESSIONAL DOCUMENTS. A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW SHALL BE
 CHARGED TO THE ENGINEER EACH TIME AFTER THE THIRD
 REVIEW IS REJECTED FOR THE SAME COMMENT.
  
 4- ORIGINAL COMMENT: PROVIDE COMPLETE INFORMATION FOR
 STAIRWAY HANDRAILS AND GUARDRAILS TO SHOW COMPLIANCE
 WITH SEC. R311.5.6 THRU SEC. R311.5.6.3 AND SEC. R312.
 IN ADDITION THE GUARDRAIL AND HANDRAIL NEED TO COMPLY
 WITH THE DESIGN LOADS OF TABLE R301.5. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS. ALSO, NEED TO PROVIDE
 FRAMING DETAILS FOR STAIRS TOP LANDING. ALSO, SPECIFY
 COMPLIANCE WITH THE STAIR CONSTRUCTION AS REQUIRED BY
 SEC. R311.2.
  
 A) PLANS SUBMITTED DON'T PROVIDE ANY DETAILS/
 SPECIFICATIONS FOR THE HANDRAIL AND GUARDRAIL
 CONSTRUCTION SHOWING COMPLIANCE WITH THE LOADS OF TABLE
 R301.5.
 B) GUARDRAIL HEIGHT IS NOT GIVEN. SEC. R311.5.6.1 AND
 SEC. R312.1.
 C) HOW IS THE 2X TOP LANDING LEDGER ATTACHED TO
 EXISTING WALL?. INFORMATION GIVEN IS NOT CLEAR AND IT
 DOESN'T MENTION ATTACHMENT OF THE LEDGER TO THE WALL.
 D) HOW ARE THE 3-2X12 STRINGERS ATTACHED TO THE BASE?.
 SIMPSON LU28 HANGER SPECIFIED CAN'T BE BENT DOWN TO
 RECEIVE THE STRINGER. NEED TO SPECIFY CORRECT CONNECTOR
 THAT IS DESIGNED TO RECEIVED SLOPED STRINGER.
  
 5- ORIGINAL COMMENT: PROVIDE PRODUCT APPROVAL (2
 COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NO PRODUCT APPROVALS SUBMITTED. PROVIDE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC
 CONNECTOR ONLY.
  
 6- SHEET #1:
 A) ORIGINAL COMMENT. REVISE TENANT SEPARATION WALL
 SECTION TO COMPLY WITH ITEM #3 ABOVE. AND, COORDINATE
 WITH INFORMATION SHOWN ON THE 2 STORY WALL SECTION.
 NEED TO COORDINATE INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-29 Cont ID  
Sent By jgomez Date 2012-02-28 Time 08:46 Rev Time 0.00
Received By jgomez Date 2012-02-28 Time 08:06 Sent To  
Notes
2012-02-28 08:49:00BUILDING REVIEW COMMENTS FOR RE-SUBMITTAL:
  
 1- FIRST FLOOR PLAN ON SHEET SHEET NO 1 SPECIFIES
 NON-AC STORAGE, WHILE FIRST FLOOR PLAN ON SHEET E-1
 SPECIFIES STUDIO UNIT. ACCORDING TO PALM BEACH COUNTY
 REVIEW STAMP DATED 2/14/12 THE SCOPE OF WORK IS
 RENOVATION TO EXISTING STUDIO UNIT, WHICH IS THE ONE ON
 THE SECOND FLOOR AND THE TOTAL SQUARE FOOTAGE IS 360
 SF. THEREFORE 1ST FLOOR IS STORAGE NO STUDIO UNIT.
 REVISE AS REQUIRED. PLEASE COORDINATE WITH ZONING.
 ALSO, CLARIFY IF SCOPE OF WORK IS ONLY FOR SECOND
 FLOOR. PLANS SUBMITTED SHOW WORK ON BOTH FLOORS.
 ***NOTE: IF THE INTENTION IS TO HAVE 2 DWELLING UNITS,
 THEN THIS MAY BE ACHIEVED BY GETTING THE PROPER ZONING
 APPROVALS, IMPACT FEES IF REQUIRED BY PALM BEACH COUNTY
 DEPENDING ON THE NUMBER OF UNITS AND BY PROVIDING THE
 PROPER DWELLING UNIT SEPARATION ON PLANS.
  
 2- ENERGY CALCULATIONS SUBMITTED:
  
 A) FORM 1100B-07 SUBMITTED WAS REVISED IN MARCH 1ST OF
 2009. NEED TO PROVIDE REVISED FORM 1100B-08. SEE SEC.
 N1100.3
 B) ITEM #B(B) NEEDS TO BE COMPLETED.
 C) R-VALUE SPECIFIED ON ITEM 8(B) NEEDS TO BE REVISED.
 NEED R-13 MIN. SEE TABLE 11B-1 ON THE SECOND PAGE OF
 FORM SUBMITTED.
 D) R-VALUE SPECIFIED ON ITEM 9(B) NEEDS TO BE REVISED.
 NEED R-13 MIN. SEE TABLE 11B-1.
 E) CLARIFY AREA OF WORK. FIRST AND SECOND FLOOR.
 COORDINATE WITH ITEM #1 ABOVE. CHECK TOTAL SQUARE
 FOOTAGE.
 F) OWNER/AGENT NEEDS TO SIGN AND DATE BOTTOM OF FORM
 ALSO.
  
 3- ORIGINAL COMMENT: PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE TENANT
 SEPARATION REQUIREMENTS OF SEC. R317.1. SPECIFY UL FIRE
 RATED ASSEMBLY OR ANY OTHER APPROVED ASSEMBLY. ANY
 PENETRATIONS NEED TO BE RATED AS REQUIRED BY SEC.
 R317.3.
  
 PLANS SUBMITTED DON'T SPECIFY ANY TESTED AND APPROVED
 ASSEMBLY. ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE
 WITH ASTM E 119. AND, FIRE-RESISTANCE-RATED
 FLOOR-CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL AS REQUIRED BY SEC.
 R317.1. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE. PLEASE SPECIFY ANY UL OR DRYWALL
 APPROVED AND LISTED ASSEMBLY.
 ***NOTE: THIS NEED TO BE COORDINATED WITH ITEM #1
 ABOVE.
  
 4- ORIGINAL COMMENT: OPENINGS ARE NOT ALLOWED ON WALL
 THAT IS LESS THAN 3'-0" FROM THE PROPERTY LINE. SEE
 SEC. R302.1 AND REVISE OPENINGS ON WEST WALL THAT IS
 LESS THAN 3"-0" FROM THE PROPERTY LINE. IN ADDITION
 NEED TO SPECIFY FIRE RATED WALL AS REQUIRED BY SEC.
 R302.1. ONE HOUR FIRE RATING WITH EXPOSURE ON BOTH
 SIDES. SEE TABLE R302.1.
  
 PLANS SUBMITTED DELETED THE WINDOWS. NEED TO SPECIFY
 FIRE RATED WALL AS REQUIRED BY SEC. R302.1. COORDINATE
 WITH ITEM #1 ABOVE.
  
 5- ORIGINAL COMMENT: PROVIDE COMPLETE INFORMATION FOR
 STAIRWAY HANDRAILS AND GUARDRAILS TO SHOW COMPLIANCE
 WITH SEC. R311.5.6 THRU SEC. R311.5.6.3 AND SEC. R312.
 IN ADDITION THE GUARDRAIL AND HANDRAIL NEED TO COMPLY
 WITH THE DESIGN LOADS OF TABLE R301.5. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS. ALSO, NEED TO PROVIDE
 FRAMING DETAILS FOR STAIRS TOP LANDING. ALSO, SPECIFY
 COMPLIANCE WITH THE STAIR CONSTRUCTION AS REQUIRED BY
 SEC. R311.2.
  
 A) PLANS SUBMITTED DON'T PROVIDE ANY DETAILS/
 SPECIFICATIONS FOR THE HANDRAIL AND GUARDRAIL
 CONSTRUCTION SHOWING COMPLIANCE WITH THE LOADS OF TABLE
 R301.5.
 B) THE RISER AND TREAD RATIO SHOWN ON STAIR DETAIL ON
 SHEET NO 2 DOESN'T COMPLY WITH SEC. R311.5.3.2.
 C) HANDRAIL AND GUARDRAIL HEIGHTS ARE NOT GIVEN. SEC.
 R311.5.6.1 AND SEC. R312.1.
 D) HOW IS THE 2X TOP LANDING LEDGER ATTACHED TO
 EXISTING WALL?. NO INFORMATION WAS GIVEN.
 E) HOW ARE THE 3-2X12 STRINGERS ATTACHED TO THE BASE?
 F) THERE ARE NO SPECIFICATIONS FOR FINISHED DECK ON TOP
 LANDING. SPECIFY DECK TYPE AND FASTENING.
  
 6- ORIGINAL COMMENT: PROVIDE PRODUCT APPROVAL (2
 COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR:
 A) EXTERIOR DOORS. DESIGN PRESSURES SHOWN ON THE
 FLORIDA PRODUCT APPROVAL FL11321.1 SUBMITTED DON'T MEET
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER ON
 SHEET 2.
  
 NO PRODUCT APPROVAL WAS SUBMITTED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
  
 NO PRODUCT APPROVALS SUBMITTED. PROVIDE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC
 CONNECTOR ONLY.
  
 C) WINDOWS PRODUCT APPROVAL FL10350.18 SUBMITTED
 DOESN'T MEET THE ENGINEER REVISED DESIGN PRESSURES
 SHOWN ON SHEET NO 2. NEED PRODUCT APPROVAL THAT MEETS
 THE CALCULATED DESIGN PRESSURES.
  
 7- ORIGINAL COMMENT: ENGINEER OF RECORD TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVALS, INCLUDING THE DOORS AND WINDOWS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS.
  
 NO DONE.
  
 8- SHEET #1:
 A) EXISTING WALL SECTION: REVISE INSULATION R-VALUE
 SHOWN ON THE WALLS. COORDINATE WITH THE ENERGY
 CALCULATIONS. SEE ITEM #2 ABOVE.
  
 B) ORIGINAL COMMENT. REVISE TENANT SEPARATION WALL
 SECTION TO COMPLY WITH ITEM #3 ABOVE. AND, COORDINATE
 WITH INFORMATION SHOWN ON THE 2 STORY WALL SECTION.
 NEED TO COORDINATE INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-13 Cont ID  
Sent By jgomez Date 2012-01-13 Time 17:05 Rev Time 0.00
Received By jgomez Date 2012-01-17 Time 11:12 Sent To  
Notes
2012-01-13 17:09:41RESIDENTIAL ALTERATION BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO CITY RECORDS, THE FIRST FLOOR IS A
 GARAGE. PLANS SUBMITTED SHOW A NEW STUDIO DWELLING.
 THERE ARE NOT PERMITS FOR THE NEW STUDIO UNIT. PLANS TO
 SHOW PROPOSED NEW USE. SEC. 106.1.1 CITY AMENDMENTS.
  
 2- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM
 BEACH COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES
 ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF THE
 PAID RECEIPT IF FEES ARE DUE.
  
 3- PROVIDE ENERGY CALCULATIONS. SEC. N1100.3.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE VALUE TO INCLUDE ALL SCOPE OF WORK SHOWN ON
 PLANS. COORDINATE WITH ITEM #1 ABOVE AND INCLUDE THE
 ENGINEERING FEES. SEC. 108.3 CITY AMENDMENTS.
  
 5- SCOPE OF WORK DESCRIBED ON THE PERMIT APPLICATION
 DOESN'T MATCH INFORMATION SHOWN ON PLANS. ALSO, UPDATE
 VALUATION DECLARED IN THE PERMIT APPLICATION AS
 REQUIRED TO INCLUDE ALL THE SCOPE OF WORK SHOWN ON
 PLANS AND THE ENGINEERING FEES AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC. COORDINATE SCOPE OF WORK
 WITH ITEM #1 ABOVE.
  
 5- SPECIFY FINISH FLOOR ELEVATION FOR THE GARAGE AREA
 TO BE CONVERTED TO LIVABLE AREA. HEIGHT ABOVE FINISH
 GRADE TO BE 6" MIN. AS REQUIRED BY SEC. R404.1.6.
 REVISE PLANS AND WALL SECTIONS AS REQUIRED.
  
 6- PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE TENANT SEPARATION REQUIREMENTS OF
 SEC. R317.1. SPECIFY UL FIRE RATED ASSEMBLY OR ANY
 OTHER APPROVED ASSEMBLY. ANY PENETRATIONS NEED TO BE
 RATED AS REQUIRED BY SEC. R317.3
  
 7- OPENINGS ARE NOT ALLOWED ON WALL THAT IS LESS THAN
 3'-0" FROM THE PROPERTY LINE. SEE SEC. R302.1 AND
 REVISE OPENINGS ON WEST WALL THAT IS LESS THAN 3"-0"
 FROM THE PROPERTY LINE. IN ADDITION NEED TO SPECIFY
 FIRE RATED WALL AS REQUIRED BY SEC. R302.1. ONE HOUR
 FIRE RATING WITH EXPOSURE ON BOTH SIDES. SEE TABLE
 R302.1.
  
 8- SPECIFY ON PLANS STAIRWAY ILLUMINATION AS REQUIRED
 BY SEC. R303.6.
  
 9- SPECIFY HOW PROVIDING HEATING TO BOTH DWELLING
 UNITS. SEC. R303.8.
  
 10- SECOND FLOOR DWELLING UNIT NEED TO HAVE AT LEAST
 ONE HABITABLE ROOM WITH NOT LESS THAN 120S.F. AS
 REQUIRED BY SEC. R304.1.
  
 11- SPECIFY HOW PROVIDING HOT WATER TO THE FIRST FLOOR
 DWELLING UNIT AS REQUIRED BY SEC. R306.4 AND P2801.1.
  
 12- WATER CLOSET ON SECOND FLOOR BATHROOM DOESN'T HAVE
 THE CLEARANCE REQUIRED BY SEC. R307.1. REVISE AS
 REQUIRED. SPECIFY AL ROOM DIMENSIONS.
  
 13- PROVIDE COMPLETE INFORMATION FOR STAIRWAY HANDRAILS
 AND GUARDRAILS TO SHOW COMPLIANCE WITH SEC. R311.5.6
 THRU SEC. R311.5.6.3 AND SEC. R312. IN ADDITION THE
 GUARDRAIL AND HANDRAIL NEED TO COMPLY WITH THE DESIGN
 LOADS OF TABLE R301.5. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS. ALSO, NEED TO PROVIDE FRAMING DETAILS
 FOR STAIRS TOP LANDING. ALSO, SPECIFY COMPLIANCE WITH
 THE STAIR CONSTRUCTION AS REQUIRED BY SEC. R311.2.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOORS. DESIGN PRESSURES SHOWN ON THE
 FLORIDA PRODUCT APPROVAL FL11321.1 SUBMITTED DON'T MEET
 THE DESIGN PRESSURES CALCULATED BY THE ENGINEER ON
 SHEET 2.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
  
 15- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS,
 INCLUDING THE DOORS AND WINDOWS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS.
  
 16- SHEET #1:
 A) EXISTING WALL SECTION: REVISE INSULATION R-VALUE
 SHOWN ON THE CEILING AREA ON SECOND FLOOR. SEE SEC.
 N1104.AB FOR MINIMUM R-VALUE REQUIRED AND REVISE AS
 REQUIRED. ALSO, COORDINATE WITH THE ENERGY
 CALCULATIONS.
  
 B) REVISE TENANT SEPARATION WALL SECTION TO COMPLY WITH
 ITEM #6 ABOVE. AND, COORDINATE WITH INFORMATION SHOWN
 ON THE 2 STORY WALL SECTION.
  
 C) SPECIFY SIZE OF ENTRY DOOR ON SECOND FLOOR UNIT.
 NEED TO COMPLY WITH SEC. R311.4.2
  
 D) REVISE TYPE OF ALTERATION SPECIFIED ON THE GENERAL
 NOTES IN THE MIDDLE OF THE SHEET. THIS IS NOT LEVEL I
 ALTERATION TYPE. SEE SEC. 403 OF EXISTING BUILDING CODE
 AND REVISE AS REQUIRED.
  
 17- SHEET #2: REVISE THE RIGHT ELEVATION. COORDINATE
 STAIR RAILINGS WITH ITEM #13 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2012-05-14 Cont ID  
Sent By rlecky Date 2012-05-14 Time 11:53 Rev Time 0.00
Received By rlecky Date 2012-05-14 Time 11:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2012-05-08 Cont ID  
Sent By rlecky Date 2012-05-08 Time 09:17 Rev Time 0.00
Received By rlecky Date 2012-05-08 Time 08:34 Sent To  
Notes
2012-05-08 09:12:10NEW PLANS DO NOT MATCH PREVIOUSLY REVIEWED PLANS.
 PLEASE PROVIDE THE FOLLOWING.
  
 11120372
 437 8TH ST.
 REMODEL
  
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 SHOW SERVICE RISER PLAN AND LOCATION OF SERVICE. NEC
 215.15
 ADD RECEPTACLES IN THE KITCHEN, FOR THE COUNTER TOP AND
 THE ADJOINING ROOM OF THE SECOND FLOOR UNIT. NEC 210.52
 PROVIDE AN INTERSYSTEM BONDING STRIP AT THE ELECTRICAL
 SERVICE. NEC 250.94
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-03-28 Cont ID  
Sent By rlecky Date 2012-03-28 Time 09:52 Rev Time 0.00
Received By rlecky Date 2012-03-27 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-02-29 Cont ID  
Sent By rlecky Date 2012-02-29 Time 15:40 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 14:59 Sent To  
Notes
2012-02-29 15:41:1111120372
 437 8TH ST.
 REMODEL
  
 ALL GENERAL PURPOSE BRANCH CIRCUITS MUST BE PROTECTED
 WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 PROVIDE AN AS BUILT ELECTRIC SERVICE RISER PLAN FOR THE
 BUILDING. INDICATE THE LOCATION OF THE SERVICE AND ALL
 SERVICE DISCONNECTS FOR ALL UNITS. NEC 215.15
 ADD RECEPTACLES IN THE KITCHEN. NEC 201.52
 CLARIFY THE USE OF THE FIRST FLOOR STUDIO. IS IT AN
 APARTMENT OR STORAGE?
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By rlecky Date 2012-01-09 Time 16:39 Rev Time 0.00
Received By rlecky Date 2012-01-09 Time 15:33 Sent To  
Notes
2012-01-09 16:40:3111120372
 437 8TH ST.
 REMODEL
  
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.70
 PROVIDE AN EXTERIOR LIGHT FOR THE TOP UNIT. NEC 210.70
 SHOW SERVICE RISER PLAN AND LOCATION OF SERVICE. NEC
 215.15
 ADD RECEPTACLES IN THE KITCHEN AND THE ADJOINING ROOM
 OF THE SECOND FLOOR UNIT. NEC 201.52
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2012-05-14 Cont ID  
Sent By rlecky Date 2012-05-14 Time 11:54 Rev Time 0.00
Received By rlecky Date 2012-05-14 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-05-08 Cont ID  
Sent By jgomez Date 2012-05-08 Time 17:30 Rev Time 0.00
Received By jgomez Date 2012-05-01 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-13 Cont ID  
Sent By jgomez Date 2012-04-13 Time 16:42 Rev Time 0.00
Received By jgomez Date 2012-03-26 Time 10:14 Sent To  
Notes
2012-03-27 10:15:11SENT TO R13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-09 Cont ID  
Sent By rlecky Date 2012-03-09 Time 12:51 Rev Time 0.00
Received By shill Date 2012-02-15 Time 12:14 Sent To  
Notes
2012-02-15 12:15:03R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-13 Cont ID  
Sent By jgomez Date 2012-01-13 Time 17:13 Rev Time 0.00
Received By jgomez Date 2011-12-14 Time 15:22 Sent To  
Notes
2011-12-22 11:10:21R12
  
  
2011-12-14 15:23:11MISC. #1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-02-28 Cont ID  
Sent By jgomez Date 2012-02-28 Time 14:10 Rev Time 0.00
Received By jgomez Date 2012-02-28 Time 14:10 Sent To  
Notes
2012-02-28 14:16:25STAMPED BY PALM BEACH COUNTY ON 2/14/12. NO FEES.
 RENOVATION TO EXISTING STUDIO 360 S.F. ONE DWELLING
 ONLY.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-01-13 Cont ID  
Sent By jgomez Date 2012-01-13 Time 17:09 Rev Time 0.00
Received By jgomez Date 2012-01-13 Time 14:17 Sent To  
Notes
2012-01-13 17:10:40PLEASE BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-01-13 Cont ID  
Sent By jgomez Date 2012-01-13 Time 17:13 Rev Time 0.00
Received By jgomez Date 2012-01-13 Time 17:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-09 Cont ID  
Sent By aaponte Date 2012-03-09 Time 10:45 Rev Time 0.00
Received By aaponte Date 2012-03-08 Time 16:25 Sent To  
Notes
2012-03-09 10:46:25ONLY ONE UNIT PERMITTED. FIRST FLOOR NOT ALLOWED AS
 ADDITIONAL RESIDENTIAL UNIT. MAXIMUM TOTAL OF UNITS FOR
 THE PROPERTY IS 3.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-09 Cont ID  
Sent By aaponte Date 2012-01-09 Time 13:42 Rev Time 0.00
Received By aaponte Date 2012-01-04 Time 14:15 Sent To  
Notes
2012-01-04 14:18:011. SURVEY SUBMITTED IS FOR THE WRONG PROPERTY. PLEASE
 PROVIDE CORRECT SURVEY.
 2. CITY RECORDS INDICATE A TWO STORY GARAGE APARTMENT
 WITH ONLY ONE UNIT. PLEASE PROVIDE INFORMATION TO
 CONFIRM CONVERSION OF GARAGE INTO AN ADDITIONAL
 RESIDENTIAL UNIT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439