| Plan Review Stops For Permit 11120371 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2012-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-04-19 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-04-18 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2012-02-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-29 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-28 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2012-02-29 08:34:03 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS | | | OF +49.3 & - 66.0 PSF ARE HIGHER THAN THE PRODUCT | | | APPROVAL DESIGN PRESSURES FOR THE WINDOWS (+ / - 55.7 | | | PSF) AND DOORS ( + / - 50 PSF). SUBMIT TWO COPIES OF | | | PRODUCT APPROVALS FOR WINDOWS AND DOORS WITH ADEQUATE | | | DESIGN PRESSURES. FBC R301.2.1 AND DCA RULE 9N-3. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2012-01-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-01-10 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-04 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2012-01-10 10:44:51 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE SURVEYS THAT WERE SUBMITTED ARE NOT FOR THIS | | | PROPERTY. SUBMIT THE CORRECT SURVEYS. CITY AMENDMENTS | | | 106.1 | | | | | | 2) SHEET E-1 OF THE PLANS SPECIFIES THAT THIS IS AN | | | EXISTING DUPLEX. THE ZONING COMMENTS AND TENANT | | | SEPARATION WALL DETAIL ON PLAN SHEET 1 INDICATE THAT | | | THIS IS A SINGLE FAMILY RESIDENCE THAT IS BEING | | | CONVERTED TO A DUPLEX. IF THIS IS AN EXISTING DUPLEX, | | | PLEASE PROVIDE DOCUMENTATION THAT IT WAS BUILT WITH THE | | | REQUIRED PERMITS. CITY AMENDMENTS 105 | | | | | | 3) SHOW COMPLIANCE WITH FBC R 317.1 WHICH REQUIRES THE | | | ONE HOUR FIRE RATED DWELLING SEPARATION WALL TO EXTEND | | | TO THE UNDERSIDE OF THE ROOF SHEATHING. EXCEPTION (2) | | | ALLOWS THE SEPARATION WALL TO STOP AT THE CEILING, IF | | | IT IS PROTECTED WITH 5/8" TYPE X GYPSUM BOARD AND THERE | | | IS AN ATTIC DRAFTSTOP CONSTRUCTED AS SPECIFIED IN | | | R502.12.1 ABOVE AND ALONG THE WALL ASSEMBLY SEPARATING | | | THE DWELLINGS. | | | | | | 4) AT THE ONE FIRE RATED SEPARATION WALL THE 5/8" TYPE | | | X DRYWALL IS REQUIRED TO EXTEND PAST THE TUB DOWN TO | | | THE FLOOR AND ALL PENETRATIONS ARE REQUIRED TO BE | | | PROTECTED PER FBCR 317.3. | | | | | | 5) SHOW THE LOCATIONS AND SIZES OF THE ATTIC ACCESSES | | | IN EACH UNIT. FBC R807.1 | | | | | | 6) THE SUBMITTED PLANS INCLUDE AN ISOMETRIC PLUMBING | | | RISER PLAN AND ELECTRIC PLANS WHICH INDICATE THAT A | | | SINGLE FAMILY DWELLING IS BEING CONVERTED TO A TWO | | | FAMILY DWELLING OR HAS BEEN ILLEGALLY CONVERTED. PLEASE | | | PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR | | | PLAN TO CLARIFY THE SCOPE OF WORK. CITY AMENDMENTS | | | 106.1.1 | | | | | | 7) IF A SINGLE FAMILY DWELLING IS BEING CONVERTED TO A | | | TWO FAMILY DWELLING, THEN THE PLANS ARE REQUIRED TO BE | | | REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEES. | | | | | | 8) ON PLAN SHEET 2, THE WINDOW AND DOOR PRESSURES ARE | | | SPECIFIED AS +35.3 PSF AND -47.2 PSF AND THE EXPOSURE | | | CATEGORY THAT IS SPECIFIED IS C. THESE PRESSURES ARE | | | WORSE CASE FOR EXPOSURE CATEGORY B. PLEASE CORRECT. FBC | | | R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2012-03-28 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-03-28 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-03-28 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2012-02-29 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-02-29 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-02-29 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2012-02-29 16:00:19 | PLANS REDLINED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2012-01-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-01-11 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2012-01-09 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2012-01-10 17:41:49 | 11120371 | | | 437 8TH STREET | | | RESIDENTIAL ADDITION | | | | | | SHOW LOCATION OF THE NEW SERVICE. NEC 215.15 | | | THE REQUIRED INTERSYSTEM BONDING STRIP NEEDS TO BEEN | | | SHOWN ON THE SERVICE RISER PLAN. NEC 250.94 | | | ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC | | | FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12 | | | MAIN ELECTRICAL DISCONNECTS MUST BE SERVICE RATED AND | | | GROUPED IN ONE LOCATION. THE DRAWING IS UNCLEAR AS TO | | | HOW THE TWO METERS AND RISERS FUNCTION. A BUILDING | | | SHOULD ONLY HAVE ONE POINT OF SERVICE. NEC 230.2, | | | 230.40 | | | AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED | | | OUTSIDE FRONT AND BACK. NEC 210.70 | | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 | | | SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED AND | | | LOCATED BOTH INSIDE AND OUT SIDE EACH SLEEPING AREA. | | | FBC R313.3 | | | EACH BATHROOM REQUIRES A DEDICATED 20 AMPERE BRANCH | | | CIRCUIT. NEC 210.11 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-05-02 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2012-05-02 08:52:12 | TO ZONING | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2012-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-04-19 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-03-26 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2012-03-27 10:12:26 | SENT TO R13 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2012-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2012-03-09 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2012-02-15 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2012-02-28 09:02:59 | SENT TO R21 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2012-01-11 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2012-01-11 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-12-14 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2011-12-22 11:07:24 | R 11 | | | | | | | | 2011-12-14 15:17:47 | MISC. #1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2012-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-02-28 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-02-28 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2012-01-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2012-01-05 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2012-01-05 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2012-05-09 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2012-05-09 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2012-05-03 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2012-05-09 12:01:04 | PROVISO: SCREENING SHALL BE PROVIDED AROUND THE | | | DUMPSTER. MINIMUM HEIGHT 6 FEET. | | 2012-05-03 09:51:33 | GIVEN TO AA |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2012-04-10 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2012-04-10 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2012-04-10 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2012-04-10 08:57:07 | 1. PROPOSED DUMPSTER IS LOCATED IN THE MIDDLE OF THE | | | PARKING AREA, BLOCKING EXISTING PARKING SPACES. | | | 2. LANDSCAPE DRAWING SHALL BE SUBMITTED FOR THE | | | SCCREEENING OF THE DUMPSTER. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. | | 2012-03-27 10:02:44 | DUMPSTER PLANS SUBMITTED. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2012-03-09 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2012-03-09 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2012-03-09 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2012-03-09 11:00:39 | PROVISO: | | | 1. SITE PLAN DOES NOT INDICATE LOCATION OF TRASH | | | RECEPTACLES. PLEASE CONTACT PUBLIC UTILITIES FOR | | | REQUIREMENTS. IF CONTAINERS NEEDED, EXTERIOR LOCATIONS | | | SHALL BE ENCLOSED AND SCREENED. BUILDING PERMIT FOR | | | SUCH ENCLOSURE AND LANDSCAPE SHALL BE SUBMITTED AND | | | APPROVED BEFORE FINAL CO. | | | 2. MAXIMUM 3 UNITS PERMITTED FOR THE ENTIRE PROPERTY. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2012-01-04 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2012-01-04 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2012-01-04 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2012-01-04 14:14:54 | 1. SURVEY PROVIDED IS FOR THE WRONG PROPERTY. PLEASE | | | PROVIDE CORRECT SURVEY. | | | 2. CITY RECORDS INDICATE FRONT BUILDING AT 437 8TH | | | STREET IS ONLY A SINGLE FAMILY RESIDENTIAL UNIT. PLEASE | | | PROVIDE INFORMATION TO CONFIRM LEGAL SUBDIVISION | | | OCCURRED. | | | FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|