Plan Review Details - Permit 11120371
Plan Review Stops For Permit 11120371
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-04-19 Cont ID  
Sent By rmcdouga Date 2012-04-19 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2012-04-18 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-02-29 Cont ID  
Sent By rmcdouga Date 2012-02-29 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2012-02-28 Time 16:48 Sent To  
Notes
2012-02-29 08:34:032007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS
 OF +49.3 & - 66.0 PSF ARE HIGHER THAN THE PRODUCT
 APPROVAL DESIGN PRESSURES FOR THE WINDOWS (+ / - 55.7
 PSF) AND DOORS ( + / - 50 PSF). SUBMIT TWO COPIES OF
 PRODUCT APPROVALS FOR WINDOWS AND DOORS WITH ADEQUATE
 DESIGN PRESSURES. FBC R301.2.1 AND DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-10 Cont ID  
Sent By rmcdouga Date 2012-01-10 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2012-01-04 Time 16:57 Sent To  
Notes
2012-01-10 10:44:512007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE SURVEYS THAT WERE SUBMITTED ARE NOT FOR THIS
 PROPERTY. SUBMIT THE CORRECT SURVEYS. CITY AMENDMENTS
 106.1
  
 2) SHEET E-1 OF THE PLANS SPECIFIES THAT THIS IS AN
 EXISTING DUPLEX. THE ZONING COMMENTS AND TENANT
 SEPARATION WALL DETAIL ON PLAN SHEET 1 INDICATE THAT
 THIS IS A SINGLE FAMILY RESIDENCE THAT IS BEING
 CONVERTED TO A DUPLEX. IF THIS IS AN EXISTING DUPLEX,
 PLEASE PROVIDE DOCUMENTATION THAT IT WAS BUILT WITH THE
 REQUIRED PERMITS. CITY AMENDMENTS 105
  
 3) SHOW COMPLIANCE WITH FBC R 317.1 WHICH REQUIRES THE
 ONE HOUR FIRE RATED DWELLING SEPARATION WALL TO EXTEND
 TO THE UNDERSIDE OF THE ROOF SHEATHING. EXCEPTION (2)
 ALLOWS THE SEPARATION WALL TO STOP AT THE CEILING, IF
 IT IS PROTECTED WITH 5/8" TYPE X GYPSUM BOARD AND THERE
 IS AN ATTIC DRAFTSTOP CONSTRUCTED AS SPECIFIED IN
 R502.12.1 ABOVE AND ALONG THE WALL ASSEMBLY SEPARATING
 THE DWELLINGS.
  
 4) AT THE ONE FIRE RATED SEPARATION WALL THE 5/8" TYPE
 X DRYWALL IS REQUIRED TO EXTEND PAST THE TUB DOWN TO
 THE FLOOR AND ALL PENETRATIONS ARE REQUIRED TO BE
 PROTECTED PER FBCR 317.3.
  
 5) SHOW THE LOCATIONS AND SIZES OF THE ATTIC ACCESSES
 IN EACH UNIT. FBC R807.1
  
 6) THE SUBMITTED PLANS INCLUDE AN ISOMETRIC PLUMBING
 RISER PLAN AND ELECTRIC PLANS WHICH INDICATE THAT A
 SINGLE FAMILY DWELLING IS BEING CONVERTED TO A TWO
 FAMILY DWELLING OR HAS BEEN ILLEGALLY CONVERTED. PLEASE
 PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN TO CLARIFY THE SCOPE OF WORK. CITY AMENDMENTS
 106.1.1
  
 7) IF A SINGLE FAMILY DWELLING IS BEING CONVERTED TO A
 TWO FAMILY DWELLING, THEN THE PLANS ARE REQUIRED TO BE
 REVIEWED BY PALM BEACH COUNTY FOR IMPACT FEES.
  
 8) ON PLAN SHEET 2, THE WINDOW AND DOOR PRESSURES ARE
 SPECIFIED AS +35.3 PSF AND -47.2 PSF AND THE EXPOSURE
 CATEGORY THAT IS SPECIFIED IS C. THESE PRESSURES ARE
 WORSE CASE FOR EXPOSURE CATEGORY B. PLEASE CORRECT. FBC
 R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-03-28 Cont ID  
Sent By rlecky Date 2012-03-28 Time 09:56 Rev Time 0.00
Received By rlecky Date 2012-03-28 Time 09:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-29 Cont ID  
Sent By rlecky Date 2012-02-29 Time 15:55 Rev Time 0.00
Received By rlecky Date 2012-02-29 Time 15:45 Sent To  
Notes
2012-02-29 16:00:19PLANS REDLINED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-11 Cont ID  
Sent By rlecky Date 2012-01-11 Time 08:11 Rev Time 0.00
Received By rlecky Date 2012-01-09 Time 15:31 Sent To  
Notes
2012-01-10 17:41:4911120371
 437 8TH STREET
 RESIDENTIAL ADDITION
  
 SHOW LOCATION OF THE NEW SERVICE. NEC 215.15
 THE REQUIRED INTERSYSTEM BONDING STRIP NEEDS TO BEEN
 SHOWN ON THE SERVICE RISER PLAN. NEC 250.94
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. 2008 NEC 210.12
 MAIN ELECTRICAL DISCONNECTS MUST BE SERVICE RATED AND
 GROUPED IN ONE LOCATION. THE DRAWING IS UNCLEAR AS TO
 HOW THE TWO METERS AND RISERS FUNCTION. A BUILDING
 SHOULD ONLY HAVE ONE POINT OF SERVICE. NEC 230.2,
 230.40
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.70
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
 SMOKE ALARMS ARE REQUIRED TO BE INTERCONNECTED AND
 LOCATED BOTH INSIDE AND OUT SIDE EACH SLEEPING AREA.
 FBC R313.3
 EACH BATHROOM REQUIRES A DEDICATED 20 AMPERE BRANCH
 CIRCUIT. NEC 210.11
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2012-05-02 Time 08:52 Sent To  
Notes
2012-05-02 08:52:12TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-19 Cont ID  
Sent By rmcdouga Date 2012-04-19 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2012-03-26 Time 10:11 Sent To  
Notes
2012-03-27 10:12:26SENT TO R13 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-09 Cont ID  
Sent By shill Date 2012-03-09 Time 13:01 Rev Time 0.00
Received By shill Date 2012-02-15 Time 09:02 Sent To  
Notes
2012-02-28 09:02:59SENT TO R21 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-11 Cont ID  
Sent By rlecky Date 2012-01-11 Time 08:12 Rev Time 0.00
Received By rlecky Date 2011-12-14 Time 15:17 Sent To  
Notes
2011-12-22 11:07:24R 11
  
  
2011-12-14 15:17:47MISC. #1

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-02-28 Cont ID  
Sent By rmcdouga Date 2012-02-28 Time 15:29 Rev Time 0.00
Received By rmcdouga Date 2012-02-28 Time 15:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-01-05 Cont ID  
Sent By rmcdouga Date 2012-01-05 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2012-01-05 Time 08:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2012-05-09 Cont ID  
Sent By aaponte Date 2012-05-09 Time 11:57 Rev Time 0.00
Received By aaponte Date 2012-05-03 Time 09:51 Sent To  
Notes
2012-05-09 12:01:04PROVISO: SCREENING SHALL BE PROVIDED AROUND THE
 DUMPSTER. MINIMUM HEIGHT 6 FEET.
2012-05-03 09:51:33GIVEN TO AA

Review Stop Z ZONING
Rev No 3 Status F Date 2012-04-10 Cont ID  
Sent By aaponte Date 2012-04-10 Time 08:54 Rev Time 0.00
Received By aaponte Date 2012-04-10 Time 08:54 Sent To  
Notes
2012-04-10 08:57:071. PROPOSED DUMPSTER IS LOCATED IN THE MIDDLE OF THE
 PARKING AREA, BLOCKING EXISTING PARKING SPACES.
 2. LANDSCAPE DRAWING SHALL BE SUBMITTED FOR THE
 SCCREEENING OF THE DUMPSTER.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
2012-03-27 10:02:44DUMPSTER PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-09 Cont ID  
Sent By aaponte Date 2012-03-09 Time 10:53 Rev Time 0.00
Received By aaponte Date 2012-03-09 Time 10:53 Sent To  
Notes
2012-03-09 11:00:39PROVISO:
 1. SITE PLAN DOES NOT INDICATE LOCATION OF TRASH
 RECEPTACLES. PLEASE CONTACT PUBLIC UTILITIES FOR
 REQUIREMENTS. IF CONTAINERS NEEDED, EXTERIOR LOCATIONS
 SHALL BE ENCLOSED AND SCREENED. BUILDING PERMIT FOR
 SUCH ENCLOSURE AND LANDSCAPE SHALL BE SUBMITTED AND
 APPROVED BEFORE FINAL CO.
 2. MAXIMUM 3 UNITS PERMITTED FOR THE ENTIRE PROPERTY.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-01-04 Cont ID  
Sent By aaponte Date 2012-01-04 Time 14:00 Rev Time 0.00
Received By aaponte Date 2012-01-04 Time 14:00 Sent To  
Notes
2012-01-04 14:14:541. SURVEY PROVIDED IS FOR THE WRONG PROPERTY. PLEASE
 PROVIDE CORRECT SURVEY.
 2. CITY RECORDS INDICATE FRONT BUILDING AT 437 8TH
 STREET IS ONLY A SINGLE FAMILY RESIDENTIAL UNIT. PLEASE
 PROVIDE INFORMATION TO CONFIRM LEGAL SUBDIVISION
 OCCURRED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved