Plan Review Details - Permit 11120254
Plan Review Stops For Permit 11120254
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-12-13 Cont ID  
Sent By shill Date 2011-12-13 Time 14:05 Rev Time 0.00
Received By shill Date 2011-12-13 Time 07:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-14 Cont ID  
Sent By rlecky Date 2011-12-14 Time 17:35 Rev Time 0.00
Received By rlecky Date 2011-12-14 Time 17:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-12-19 Cont ID  
Sent By wjolin Date 2011-12-19 Time 13:54 Rev Time 0.00
Received By wjolin Date 2011-12-19 Time 13:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2011-12-19 Cont ID  
Sent By fmittner Date 2011-12-19 Time 11:21 Rev Time 0.00
Received By fmittner Date 2011-12-19 Time 11:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-19 Cont ID  
Sent By hmoser Date 2011-12-19 Time 15:18 Rev Time 0.00
Received By hmoser Date 2011-12-12 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2011-12-20 Cont ID  
Sent By hmoser Date 2011-12-19 Time 15:14 Rev Time 0.00
Received By hmoser Date 2011-12-19 Time 15:14 Sent To  
Notes
2011-12-19 16:04:19PROVISO - MECHANICAL APPLICATION AND PLANS REQUIRED
 PRIOR TO FIRST INSPECTION
  
 PLANS TO SHOW COMPLIANCE WITH FBC MECHANICAL TABLE
 403.3.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-12-13 Cont ID  
Sent By hmoser Date 2011-12-13 Time 13:41 Rev Time 0.00
Received By hmoser Date 2011-12-13 Time 13:41 Sent To  
Notes
2011-12-13 14:05:15****CORRECTIONS****
  
 1. PROVIDE INFORMATION REGARDING THE DRYER EXHAUST, FBC
 MECHANICAL 504.4. IT IS NOT CLEAR WHERE THE EXHAUST
 TERMINATES.
  
 2. SHOW COMPLIANCE WITH FBC MECHANICAL TABLE 403.3,
 REQUIRED VENTILATION. SEE FOOTNOTES, MECHANICAL EXHAUST
 REQUIRED AND REQUIRED EXHAUST SYSTEM SHALL CAPTURE THE
 CONTAMINANTS AND ODORS AT THEIR SOURCE. SHOW REQUIRED
 VENTILATION FOR ALL MANICURE STATIONS, BOTH SIDES.
  
 HAROLD MOSER, MECHANICAL PLANS EXAMINER
 561-805-6732
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-12-19 Cont ID  
Sent By lwagner Date 2011-12-19 Time 14:47 Rev Time 0.00
Received By lwagner Date 2011-12-19 Time 13:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-12-19 Cont ID  
Sent By aaponte Date 2011-12-15 Time 15:23 Rev Time 0.00
Received By aaponte Date 2011-12-15 Time 15:23 Sent To  
Notes
***NONE***