Plan Review Details - Permit 11120013
Plan Review Stops For Permit 11120013
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-12-15 Cont ID  
Sent By jgomez Date 2011-12-15 Time 11:28 Rev Time 0.00
Received By jgomez Date 2011-12-15 Time 11:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-12-12 Cont ID  
Sent By jgomez Date 2011-12-12 Time 10:56 Rev Time 0.00
Received By jgomez Date 2011-12-15 Time 11:27 Sent To  
Notes
2011-12-12 11:23:31RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- MRI BUILDING SECTION C: RAS 117 CALCULATIONS
 SUBMITTED SPECIFIES NOA 10-0719.02 WITH APPROVED
 ASSEMBLY ON PAGE 118 AND THE DESIGN PRESSURES OF -52.5.
 THERE IS NO PAGE 118. CONTRACTOR SUBMITTED APPROVED
 ASSEMBLY ON PAGE 8. PLEASE REVISE AS REQUIRED TO MATCH.
  
 2- FOR YOUR INFORMATION: A) ANY RETROFIT ROOF DRAINS
 REQUIRE PLUMBING REVIEW.
 B) ANY ROOF EQUIPMENT REMOVAL/RELOCATION REQUIRES
 SEPARATE PERMIT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By jgomez Date 2011-12-01 Time 11:59 Rev Time 0.00
Received By jgomez Date 2011-12-01 Time 11:37 Sent To  
Notes
2011-12-01 12:15:05RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- MRI SECTION A: PLEASE PROVIDE SIGNED AND SEALED RAS
 117 CALCULATIONS (2 COPIES) AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA 10-1230.07 SUBMITTED.
 NEED NAIL ENHANCING TO MEET THE DESIGN PRESSURES OF
 SEC. 1609 FBC.
  
 2- MRI BUILDING SECTION C: PLEASE PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA 10-0719.02
 SUBMITTED. NEED NAIL ENHANCING TO MEET THE DESIGN
 PRESSURES OF SEC. 1609 FBC.
  
 3- PLEASE PROVIDE 2 COPIES OF TAS 105 AND TAS 126
 ENGINEERING TESTING. ONLY ONE COPY WAS SUBMITTED. BOTH
 COPIES TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE.
  
 4- PLEASE PROVIDE 2 COPIES OF ALL PRODUCT APPROVALS.
 ONLY 1 WAS SUBMITTED.
  
 5- FOR YOUR INFORMATION: A) ANY RETROFIT ROOF DRAINS
 REQUIRE PLUMBING REVIEW.
 B) ANY ROOF EQUIPMENT REMOVAL/RELOCATION REQUIRES
 SEPARATE PERMIT.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-12-15 Cont ID  
Sent By jgomez Date 2011-12-15 Time 11:27 Rev Time 0.00
Received By jgomez Date 2011-12-15 Time 11:28 Sent To  
Notes
2011-12-15 11:28:49CONTRATOR SUBMITTED REVISED ENGINEERING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-12-12 Cont ID  
Sent By jgomez Date 2011-12-12 Time 10:56 Rev Time 0.00
Received By jgomez Date 2011-12-12 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-01 Cont ID  
Sent By jgomez Date 2011-12-01 Time 11:37 Rev Time 0.00
Received By jgomez Date 2011-12-01 Time 11:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved