Plan Review Details - Permit 11110707
Plan Review Stops For Permit 11110707
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-02-01 Cont ID  
Sent By jwitmer Date 2012-02-01 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2012-02-01 Time 10:22 Sent To  
Notes
2012-02-01 10:23:28INSERTED NEW SHEETS INTO PLANS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-06 Cont ID  
Sent By jwitmer Date 2012-01-06 Time 15:49 Rev Time 1.00
Received By jwitmer Date 2012-01-06 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-12-20 Cont ID  
Sent By jwitmer Date 2011-12-20 Time 11:57 Rev Time 1.22
Received By jwitmer Date 2011-12-19 Time 15:52 Sent To  
Notes
2011-12-20 12:01:18BUILDING PLAN REVIEW
 PERMIT: 11110707
 ADD: 400 N CONGRESS # 220
 CONT: ROBB CONSTRUCTION
 TEL: (561) 346-9509
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE REVIEW SHEET LS1.1 DESIGN STANDARDS AND CODE
 REQUIREMENTS. THE REQUIREMENTS UNDER COMMON PATH OF
 TRAVEL THE EXCEPTION # 2. THE CODE EXCEPTION READS
 WHERE A TENANT SPACE HAS AN OCCUPANT LOAD OF NOT
 GREATER THAN 30, YOUR TENANT SPACE HAS AN OCCUPANT LOAD
 OF 40. I AGREE THAT THE CORRIDORS SERVING ROOMS 201-
 209 DOES HAVE AN OCCUPANT LOAD LESS THAN 30 BUT THE
 TENANT SPACE DOES HAVE AN OCCUPANT LOAD OF 40 AND THE
 CODE SECTION INDICATES THE OCCUPANT LOAD OF THE TENANT
 SPACE.
  
 2) IN NOT BEING ABLE TO MEET THE REQUIREMENTS OF 1014.3
 EXCEPTION 2 WE WILL NEED TO REVIEW 1015.1 EXIT ACCESS.
 WHEN 1015.1.2 COMMON PATH OF TRAVEL CAN NOT BE MET THEN
 THE REQUIREMENTS OF EXIT ACCESS CORRIDORS NEED TO BE
 REVIEWED AND THE REQUIREMENT FOR TWO EXITS AND THEIR
 ARRANGEMENT 1015.1.2.1. IN SHORT IF A FIRE BREAKS OUT
 LETS SAY IN ROOM 202 WILL THE OCCUPANTS IN THE OTHER
 OFFICES BE ABLE TO USE THE DOOR # 213 FOR EGRESS
 PURPOSES?
  
 3) ANOTHER CONCERN IS DOOR # 213 AND NOTE # 1 DOOR
 SCHEDULE ON A3.1 INDICATING TO VERIFY ALL HARDWARE
 REQUIREMENTS WITH OWNERS. 11-4.13.9.
  
 4) SHEET A1.1 & A4.1 INDICATE OPENINGS WITHIN CORRIDOR
 222 & 223 PLEASE PROVIDE OPENING PROTECTION FOR THESE
 OPENINGS IN COMPLIANCE WITH FBC-B TABLE 715.4.
  
 5) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 6) PLEASE PROVIDE CODE COMPLIANCE WITH: 712.3
 FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR
 THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER
 WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS
 712.3.1 THROUGH 712.3.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-12-13 Cont ID  
Sent By rlecky Date 2011-12-13 Time 19:13 Rev Time 0.00
Received By rlecky Date 2011-12-13 Time 18:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-01-31 Cont ID  
Sent By wjolin Date 2012-01-31 Time 11:52 Rev Time 0.00
Received By wjolin Date 2012-01-31 Time 11:23 Sent To B
Notes
2012-01-31 11:41:11400 NORTH CONGRESS AVENUE - SUITE #220
 PERMIT #11110707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEWLY CREATED EXIT PASSAGEWAY WILL BE TREATED AS AN
 EXTENSION OF THE STAIR ENCLOSURE. CONFIRM NO UTILITIES
 OR THROUGH-PENETRATIONS ARE LOCATED IN THE EXIT
 PASSAGEWAY, OTHERWISE A FIRE-RATED CEILING MAY BE
 NEEDED.
  
 PROVIDE AN EXIT SIGN ON THE NORTH SIDE OF THE EXIT
 PASSAGEWAY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-01-09 Cont ID  
Sent By wjolin Date 2012-01-09 Time 15:51 Rev Time 0.00
Received By wjolin Date 2012-01-09 Time 14:58 Sent To  
Notes
2012-01-09 15:51:09400 NORTH CONGRESS AVENUE - SUITE #220
 PERMIT #11110707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A SINGLE MEANS OF EGRESS (COMMON PATH OF TRAVEL) IS
 LIMITED TO 75 FEET OF TRAVEL IN AN UNSPRINKLERED
 BUSINESS OCCUPANCY. THE TRAVEL DISTANCE NEEDS TO BE
 MEASURED ALONG THE CENTERLINE OF THE NATURAL PATH OF
 TRAVEL AND CURVING AROUND ANY CORNERS OR OBSTRUCTIONS,
 WITH A 12-INCH CLEARANCE THEREFROM. RECONFIGURE TRAVEL
 DISTANCES USING CRITERIA STATED. INDICATE TRAVEL
 DISTANCE FROM ROOM #208 AND #209. TRAVEL DISTANCE NEEDS
 TO BE MEASURED TO THE FIRE-RATED STAIR ENCLOSURE. ALSO,
 A FIRE EVENT AT CUSTOMER SERVICE #221.1 WOULD FORCE
 OCCUPANTS IN THE BREAK ROOM TO USE THE CORRIDOR AS THE
 NATURAL PATH OF EGRESS.
  
 NO FIRE ALARM CONSTRUCTION DOCUMENTS SUBMITTED WITH
 DRAWING PACKAGE. THE NEW CONFIGURATION OF DOORS AND
 WALLS MAY REQUIRE NOTIFICATION APPLIANCES TO BE ADDED
 OR RELOCATED.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-12-01 Cont ID  
Sent By wjolin Date 2011-12-01 Time 14:59 Rev Time 0.00
Received By wjolin Date 2011-12-01 Time 13:41 Sent To  
Notes
2011-12-01 14:58:56400 NORTH CONGRESS AVENUE - SUITE #220
 PERMIT #11110707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 **THE TWO EXIT DOORS (#200 & #217) DO NOT MEET THE
 REQUIRED SEPARATION DISTANCE OF THE LIFE SAFETY CODE.
 EXITS SHALL BE SPACED AT LEAST ONE-HALF THE DIAGONAL
 DISTANCE OF THE FLOOR PLAN.
  
 INSUFFICIENT EXIT SIGNS PROVIDED TO ALERT OCCUPANTS OF
 TWO SEPARATE PATHS OF EGRESS.
  
 INDICATE HOW THE LOCK/LATCH WILL BE RELEASED FROM THE
 EGRESS SIDE OF THE DOORS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 NO EMERGENCY LIGHTING INDICATED ON PLANS.
  
 NO FIRE ALARM CONSTRUCTION DOCUMENTS SUBMITTED WITH
 DRAWING PACKAGE.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-02-01 Cont ID  
Sent By jwitmer Date 2012-02-01 Time 10:23 Rev Time 0.00
Received By jwitmer Date 2012-01-27 Time 17:22 Sent To  
Notes
2012-01-30 17:22:31GAVE TO WESLEY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-10 Cont ID  
Sent By wjolin Date 2012-01-10 Time 13:08 Rev Time 0.00
Received By wjolin Date 2011-12-28 Time 17:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-12-27 Cont ID  
Sent By shill Date 2011-12-20 Time 10:52 Rev Time 0.00
Received By shill Date 2011-11-30 Time 16:22 Sent To  
Notes
2011-11-30 16:22:47INCOMING SENT TO C-13. JW

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-12-16 Cont ID  
Sent By lwagner Date 2011-12-16 Time 10:29 Rev Time 0.00
Received By lwagner Date 2011-12-16 Time 10:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-12-02 Cont ID  
Sent By eschneid Date 2011-12-02 Time 11:29 Rev Time 0.25
Received By eschneid Date 2011-12-02 Time 11:29 Sent To  
Notes
2011-12-02 11:29:21PERMITS OVER PAST YEAR LESS THAN 50% STRUCTURE VALUE.